BVP:075731
LDC7615-VEV

From SIEMENS

LDC7615-VEV Knee for connection piece
Model
Product designationfeeder unit for LD busbar trunking system
Protection class
Protection class IPIP54
Main circuit
Operating frequency / rated value
minimum16.7 Hz
maximum60 Hz
Operating voltage / at AC
at 50 Hz / rated value / maximum1 000 V
at 60 Hz / rated value / maximum1 000 V
Operating current
for circuit 1 / at AC / at 50 Hz / for horizontal busbar box with flat busbars / rated value / maximum2 600 A
for circuit 1 / at AC / at 50 Hz / for vertical busbar box / rated value3 200 A
for circuit 1 / at AC / at 50 Hz / rated value / maximum3 200 A
for circuit 1 / at AC / at 60 Hz / for horizontal busbar box with flat busbars / rated value / maximum2 600 A
for circuit 1 / at AC / at 60 Hz / for vertical busbar box / rated value3 200 A
for circuit 1 / at AC / at 60 Hz / rated value / maximum3 200 A
Mechanical Design
Height300 mm
Width240 mm
Length0.8 m
Mounting typeceiling / wall
Material / of the busbarcopper

External links