6GK7443-5FX01-0XE0
COMMUNICATION PROCESSOR CP 443-5 BASIC

From SIEMENS

Product type designationCP 443-5 Basic
SIMATIC NET, CP 443-5 BASIC COMMUNICATIONS PROCESSOR FOR CONNECTING SIMATIC S7-400 TO PROFIBUS, FMS, S5-COMPATIBLE PG/OP AND S7 COMMUNICATION
Transmission rate
Transfer rate
at the 1st interface / acc. to PROFIBUS9.6 kbit/s ... 12 Mbit/s
Interfaces
Number of interfaces / acc. to Industrial Ethernet0
Number of electrical connections
at the 1st interface / acc. to PROFIBUS1
Type of electrical connection
at the 1st interface / acc. to PROFIBUS9-pin Sub-D socket (RS485)
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage / 1 / from backplane bus5 V
Supply voltage5 V
Relative symmetrical tolerance / at DC
at 5 V5 %
Power loss [W]6.5 W
Permitted ambient conditions
Ambient temperature
during operation0 ... 60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP20
Design, dimensions and weight
Module formatCompact module S7-400 single width
Width25 mm
Height290 mm
Depth210 mm
Net weight0.7 kg
Product properties, functions, components / general
Number of units
per CPU / maximum14
Notedepending on CPU type
Performance data / open communication
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum32
Amount of data
as user data per connection / for open communication / by means of SEND/RECEIVE blocks / maximum240 byte
Performance data / FMS functions
Number of possible connections / for FMS connection / maximum48
Amount of data / of the variables
for READ job / maximum237 byte
for WRITE job / maximum233 byte
Number of variables
Configurable from server to FMS partner512
Loadable from server to FMS partner2640
Performance data / S7 communication
Number of possible connections / for S7 communication
maximum48
Performance data / multi-protocol mode
Number of possible connections / of which 2 reserved for PG/OP communication / with multi-protocol mode / maximum59
Product functions / management, configuration
Configuration software
requiredSTEP 7 V5.1 SP1 or higher and NCM S7 for PROFIBUS