Product type designation | CP 1243-1 DNP3 |
| Communications processor CP 1243-1 DNP3 for connection of SIMATIC S7-1200 to control center with DNP3 protocol |
Transmission rate |
Transfer rate | |
at the 1st interface | 10 ... 100 Mbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet | 1 |
Number of electrical connections | |
at the 1st interface / acc. to Industrial Ethernet | 1 |
for power supply | 0 |
Type of electrical connection | |
at the 1st interface / acc. to Industrial Ethernet | RJ45 port |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage / 1 / from backplane bus | 5 V |
Consumed current | |
from backplane bus / at DC / at 5 V / typical | 0.25 A |
Power loss [W] | 1.25 W |
Permitted ambient conditions |
Ambient temperature | |
for vertical installation / during operation | -20 ... +60 °C |
for horizontally arranged busbars / during operation | -20 ... +70 °C |
during storage | -40 ... +70 °C |
during transport | -40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Module format | Compact module S7-1200 single width |
Width | 30 mm |
Height | 110 mm |
Depth | 75 mm |
Net weight | 0.122 kg |
Mounting type | |
35 mm DIN rail mounting | Yes |
wall mounting | Yes |
Product properties, functions, components / general |
Number of units | |
per CPU / maximum | 3 |
Performance data / S7 communication |
Number of possible connections / for S7 communication | |
Note | like CPU |
Performance data / IT functions |
Number of possible connections | |
as e-mail client / maximum | 1 |
Performance data / telecontrol |
Suitability for use | |
Node station | No |
substation | Yes |
TIM control center | No |
Control center connection | control center with DNP3 function |
by means of a permanent connection | supported |
Note | Connection to SCADA system using DNP3 services |
Protocol / is supported | |
DNP3 | Yes |
IEC 60870-5 | No |
Product function / data buffering if connection is aborted | Yes; 64,000 values |
Number of data points per station / maximum | 200 |
Performance data / Teleservice |
Diagnostics function / online diagnostics with SIMATIC STEP 7 | Yes |
Product function | |
program download with SIMATIC STEP 7 | Yes |
Remote firmware update | Yes |
Product functions / management, configuration |
Configuration software | |
required | STEP 7 Basic/Professional |
Product functions / Time |
Protocol / is supported | |
NTP | No |
time synchronization | |
from control center | Yes |