6GK7243-1BX30-0XE0
Communication processor CP 1243-1

From SIEMENS

Product type designationCP 1243-1
Communications processor CP 1243-1 for connection of SIMATIC S7-1200 as additional Ethernet interface and for Connection to control centers via Remote effect protocols (DNP3, IEC 60870, TeleControl Basic), security (Firewall, VPN)
Transmission rate
Transfer rate
at the 1st interface10 ... 100 Mbit/s
Interfaces
Number of interfaces / acc. to Industrial Ethernet1
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet1
for power supply0
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage / 1 / from backplane bus5 V
Consumed current
from backplane bus / at DC / at 5 V / typical0.25 A
Power loss [W]1.25 W
Permitted ambient conditions
Ambient temperature
for vertical installation / during operation-20 ... +60 °C
for horizontally arranged busbars / during operation-20 ... +70 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP20
Design, dimensions and weight
Module formatCompact module S7-1200 single width
Width30 mm
Height110 mm
Depth75 mm
Net weight0.122 kg
Mounting type
35 mm DIN rail mountingYes
wall mountingYes
Product properties, functions, components / general
Number of units
per CPU / maximum3
Performance data / open communication
Number of possible connections / for open communication
by means of T blocks / maximumlike CPU
Performance data / S7 communication
Number of possible connections / for S7 communication
Notelike CPU
Performance data / IT functions
Number of possible connections
as e-mail client / maximum1
Performance data / telecontrol
Suitability for use
Node stationNo
substationYes
TIM control centerNo
Control center connectionFor use with TeleControl Server Basic, WinCC and PCS7
by means of a permanent connectionsupported
NoteConnection to SCADA system via Telecontrol Server Basic and Standard Telecontrol protocols
Protocol / is supported
DNP3Yes
IEC 60870-5Yes
Product function / data buffering if connection is abortedYes; 64,000 values
Number of data points per station / maximum200
Number of stations / for direct communication / with Telecontrol Server Basic
in send direction / maximum3
in receive direction / maximum15
Performance data / Teleservice
Diagnostics function / online diagnostics with SIMATIC STEP 7Yes
Product function
program download with SIMATIC STEP 7Yes
Remote firmware updateYes
Product functions / management, configuration
Configuration software
requiredSTEP 7 Basic/Professional
Product functions / Diagnosis
Product function / Web-based diagnosticsYes
Product functions / Security
Firewall versionstateful inspection
Product function / with VPN connectionIPSec, SINEMA RC
Type of encryption algorithms / with VPN connectionAES-256, AES-192, AES-128, 3DES-168
Type of authentication procedure / with VPN connectionPreshared key (PSK), X.509v3 certificates
Type of hashing algorithms / with VPN connectionMD5, SHA-1, SHA-2
Number of possible connections / with VPN connection8
Product function
password protection for Web applicationsNo
password protection for teleservice accessNo
encrypted data transmissionYes
ACL - IP-basedNo
ACL - IP-based for PLC/routingNo
switch-off of non-required servicesYes
Blocking of communication via physical portsNo
log file for unauthorized accessNo
Product functions / Time
Protocol / is supported
NTPYes
NTP (secure)Yes
time synchronization
from NTP-serverYes
from control centerYes