| SCALANCE X414-3E, modular IE switch, 2x 10/100/1000 Mbit/ and 12x 10/100 Mbit/s RJ45 ports, 1x Gbit and 2x 100 Mbit media module Slots, Extender interface, integrated redundancy manager, Office features (RSTP, VLAN,..) network management, C-plug in scope of delivery |
Product type designation | SCALANCE X414-3E |
Transmission rate |
Transfer rate | 10 Mbit/s, 100 Mbit/s, 1000 Mbit/s |
Interfaces / for communication / integrated |
Number of electrical connections | |
for network components or terminal equipment | 14 |
Number of 100 Mbit/s SC ports | |
for multimode | 4 |
Interfaces / others |
Number of electrical connections | |
for operator console | 1 |
for management purposes | 1 |
for signaling contact | 1 |
for media module | 3 |
for power supply | 1 |
for redundant voltage supply | 1 |
Type of electrical connection | |
for operator console | RS232 |
for management purposes | RJ45 |
for signaling contact | 4-pole terminal block |
for power supply | 4-pole terminal block |
Number of extender expansion interfaces | 1 |
Extender extension interface version | EM495-8 or EM496-4 |
design of the removable storage | |
C-PLUG | Yes |
Product feature / hot-swappable interface modules | Yes |
Signal-Inputs/outputs |
Operating voltage / of the signaling contacts | |
at DC / Rated value | 24 V |
Operating current / of the signaling contacts | |
at DC / maximum | 0.1 A |
Number of digital inputs | 2 |
Number of electrical connections / for digital input signals | 2 |
Type of electrical connection / for digital input signals | 5-pole terminal block |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage | |
external | 24 V |
external / minimum | 20.4 V |
external / maximum | 28.8 V |
Product component / fusing at power supply input | Yes |
Fuse protection type / at input for supply voltage | F 3.15 A / 250 V |
Consumed current / maximum | 2 A |
Power loss [W] | |
at DC / at 24 V | 15 W |
maximum | 48 W |
Permitted ambient conditions |
Ambient temperature | |
during operation | -40 ... +70 °C |
during storage | -40 ... +80 °C |
during transport | -40 ... +80 °C |
Relative humidity | |
at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP20 |
Design, dimensions and weight |
Design | modular |
Width | 344 mm |
Height | 145 mm |
Depth | 117 mm |
Net weight | 3.07 kg |
Mounting type | |
35 mm DIN rail mounting | Yes |
wall mounting | No |
S7-300 rail mounting | Yes |
S7-1500 rail mounting | No |
Product properties, functions, components / general |
Cascading in the case of a redundant ring / at reconfiguration time of <\~0.3\~s | 50 |
Cascading in cases of star topology | any (depending only on signal propagation time) |
Product functions / management, configuration |
Product function | |
CLI | Yes |
web-based management | Yes |
MIB support | Yes |
TRAPs via email | Yes |
Configuration with STEP 7 | Yes |
RMON | Yes |
Port mirroring | Yes |
multiport mirroring | No |
CoS | Yes |
PROFINET IO diagnosis | Yes |
PROFINET conformity class | B |
Product function / switch-managed | Yes |
Protocol / is supported | |
Telnet | Yes |
HTTP | Yes |
HTTPS | Yes |
TFTP | Yes |
FTP | Yes |
BOOTP | Yes |
GMRP | Yes |
DCP | Yes |
LLDP | Yes |
SNMP v1 | Yes |
SNMP v2 | Yes |
SNMP v3 | Yes |
IGMP (snooping/querier) | Yes |
Identification & maintenance function | |
I&M0 - device-specific information | Yes |
I&M1 – higher-level designation/location designation | Yes |
Product functions / Diagnosis |
Product function | |
Port diagnostics | Yes |
Statistics Packet Size | Yes |
Statistics packet type | Yes |
Error statistics | Yes |
SysLog | Yes |
Product functions / VLAN |
Product function | |
VLAN - port based | Yes |
VLAN - protocol-based | No |
VLAN - IP-based | No |
VLAN dynamic | Yes |
Number of VLANs / maximum | 64 |
Number of VLANs - dynamic / maximum | 64 |
Protocol / is supported / GVRP | Yes |
Product functions / DHCP |
Product function | |
DHCP client | Yes |
DHCP Option 82 | Yes |
DHCP Option 66 | Yes |
DHCP Option 67 | Yes |
Product functions / Routing |
Product function | |
Static IP routing | Yes |
Static IP routing IPv6 | No |
dynamic IP routing | Yes |
dynamic IP routing IPv6 | No |
Protocol / is supported | |
RIPv2 | Yes |
RIPnG for IPv6 | No |
OSPFv2 | Yes |
OSPFv3 for IPv6 | No |
VRRP | Yes |
VRRP for IPv6 | No |
Product functions / Redundancy |
Product function | |
Ring redundancy | Yes |
High Speed Redundancy Protocol (HRP) | Yes |
high speed redundancy protocol (HRP) with redundancy manager | Yes |
high speed redundancy protocol (HRP) with standby redundancy | Yes |
Protocol / is supported / Media Redundancy Protocol (MRP) | Yes |
Product function | |
media redundancy protocol (MRP) with redundancy manager | Yes |
redundancy procedure STP | Yes |
redundancy procedure RSTP | Yes |
redundancy procedure MSTP | No |
Parallel Redundancy Protocol (PRP)/operation in the PRP-network | Yes |
Parallel Redundancy Protocol (PRP)/Redundant Network Access (RNA) | No |
Passive listening | Yes |
Protocol / is supported | |
RSTP big network support | Yes |
LACP | Yes |
Product functions / Security |
Product function | |
ACL - MAC-based | Yes |
ACL - port/MAC-based | Yes |
IEEE 802.1x (radius) | Yes |
Broadcast/Multicast/Unicast Limiter | Yes |
broadcast blocking | Yes |
Protocol / is supported | |
SSH | Yes |
Product functions / Time |
Product function | |
SICLOCK support | Yes |
Protocol / is supported | |
NTP | No |
SNTP | Yes |
IEEE 1588 profile default | No |
Standards, specifications, approvals |
Standard | |
for FM | FM3611: Class 1, Divison 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4 |
for hazardous zone | EN 60079-0: 2009, EN60079-15: 2010, II 3 G Ex nA IIC T4 Gc, KEMA 07 ATEX 0145 X |
for safety / from CSA and UL | UL 60950-1, CSA C22.2 No. 60950-1-03 |
for hazardous zone / from CSA and UL | ISA 12.12.01-2012 (Hazardous Location), Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4 |
for emitted interference | EN 61000-6-4:2001 (Class A) |
for interference immunity | EN 61000-6-2:2001 |
Standards, specifications, approvals / CE |
Certificate of suitability / CE marking | Yes |
Standards, specifications, approvals / miscellaneous |
Certificate of suitability | EN 61000-6-2:2001, EN 61000-6-4:2001 |
C-Tick | Yes |
Railway application in accordance with EN 50155 | No |
KC approval | Yes |
Standards, specifications, approvals / ship classification |
Marine classification association | |
American Bureau of Shipping Europe Ltd. (ABS) | Yes |
Bureau Veritas (BV) | Yes |
Det Norske Veritas (DNV) | No |
Germanische Lloyd (GL) | No |
DNV GL | Yes |
Lloyds Register of Shipping (LRS) | Yes |
Nippon Kaiji Kyokai (NK) | Yes |
Polski Rejestr Statkow (PRS) | Yes |
Royal Institution of Naval Architects (RINA) | Yes |
Standards, specifications, approvals / product conformity |
MTBF | 18 y |