6GK1562-4AA00
COMMUNICATION PROCESSOR CP 5624

From SIEMENS

Product type designationCP 5624
Communications processor CP 5624 PCI Express X1 (3, 3V) w. Master and slave connection to PB; incl. DP-Base software, NCM PC: DP-RAM interface for DP master incl. PG and FDL protocol, Single license for 1 installation, Runtime software, Class A; software and electr. manual on CD-ROM, 2 languages (de, en) ; Operating system support see SIMATIC NET software
Transmission rate
Transfer rate
at the 1st interface / acc. to PROFIBUS9.6 kbit/s ... 12 Mbit/s
at the 2nd interface / acc. to PROFIBUS9.6 kbit/s ... 12 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to PROFIBUS1
at the 2nd interface / acc. to PROFIBUS1
Type of electrical connection
at the 1st interface / acc. to PROFIBUS9-pin Sub-D socket (RS 485)
at the 2nd interface / acc. to PROFIBUS9-pin Sub-D socket (RS 485)
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage
1 / from backplane bus3.3 V
2 / from backplane bus12 V
Relative symmetrical tolerance / at DC
at 3.3 V9 %
at 12 V8 %
Consumed current
1 / from backplane bus / at DC / maximum0.75 A
2 / from backplane bus / at DC / maximum0.3 A
Power loss [W]6.1 W
Permitted ambient conditions
Ambient temperature
during operation5 ... 60 °C
during storage-20 ... +60 °C
during transport-20 ... +60 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum85 %
Protection class IPIP00
Design, dimensions and weight
Module formatPCI Express x1 (half length)
Width21.6 mm
Height126.3 mm
Depth180.5 mm
Net weight117 g
Number of plug-in cards of same design / plug-in / per PC station4
Number of units / NoteFMS-5613 supports up to two CP 5603 / CP 5613 A2 / CP 5614 A2 / CP 5623 / CP 5624 processors
Performance data
Performance data / open communication
Software / for open communication / by means of SEND/RECEIVE / requiredFDL driver included in scope of delivery of the CP
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum80
Performance data / PROFIBUS DP
Software / for DP master function / requiredNo
Service / as DP master
DPV0Yes
DPV1Yes
DPV2Yes
Number of DP slaves / on DP master / usable124
Amount of data
of the address area of the inputs / as DP master / total30256 byte
of the address area of the outputs / as DP master / total30256 byte
of the address area of the inputs / per DP slave244 byte
of the address area of the outputs / per DP slave244 byte
of the address area of the diagnostic data / per DP slave244 byte
Software / for DP slave function / requiredNo
Service / as DP slave
DPV0Yes
DPV1Yes
Amount of data
of the address area of the inputs / as DP slave / total244 byte
of the address area of the outputs / as DP slave / total244 byte
Performance data / FMS functions
Software / for FMS communication / requiredYes, FMS-5613
Number of possible connections / for FMS connection / maximum40
Performance data / S7 communication
Software / for S7 communication / requiredYes, HARDNET-PB S7 (S7-5613)
Number of possible connections / for S7/PG communication / maximum50
Performance data / multi-protocol mode
Number of active connections / with multi-protocol mode50
Number of configurable connections / per PC station207
Product functions / management, configuration
Configuration software / requiredIncluded in scope of supply
Product functions / Diagnosis
Product function
Port diagnosticsYes
Standards, specifications, approvals
Standard
for EMC2004/108/EC
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1
for emitted interferenceEN 61000-6-3, EN 61000-6-4
for interference immunityEN 61000-6-1, EN 61000-6-2
Certificate of suitability
CE markingYes
C-TickYes

External links