Product type designation | CP 5613 A3 |
| Communications processor CP 5613 A3, PCI card (32 bit; 3.3/5V; 33/66MHz); with a Interface for connection to PROFIBUS; incl. Configuration tool and DP-Base software: DP-RAM Interface for DP master; incl. PG and FDL protocol; Single License for 1 installation of runtime software, Class A; Software+Manuals on DVD; 2 languages (de, en); Operating system support see http:/support.automation. siemens.com/ WW/view/DE/22611503 |
Transmission rate |
Transfer rate | |
at the 1st interface / acc. to PROFIBUS | 9.6 kbit/s ... 12 Mbit/s |
Interfaces |
Number of electrical connections | |
at the 1st interface / acc. to PROFIBUS | 1 |
Type of electrical connection | |
at the 1st interface / acc. to PROFIBUS | 9-pin Sub-D socket (RS 485) |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage | |
1 / from backplane bus | 3.3 V |
2 / from backplane bus | 12 V |
Relative symmetrical tolerance / at DC | |
at 3.3 V | 9 % |
at 12 V | 8 % |
Consumed current | |
1 / from backplane bus / at DC / maximum | 0.15 A |
2 / from backplane bus / at DC / maximum | 0.25 A |
Power loss [W] | 3.5 W |
Permitted ambient conditions |
Ambient temperature | |
during operation | 5 ... 55 °C |
during storage | -20 ... +60 °C |
during transport | -20 ... +60 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 85 % |
Protection class IP | IP00 |
Design, dimensions and weight |
Module format | PCI |
Width | 18 mm |
Height | 107 mm |
Depth | 125 mm |
Net weight | 0.098 kg |
Number of plug-in cards of same design / plug-in / per PC station | 4 |
Number of units / Note | - |
Performance data |
Performance data / open communication |
Software / for open communication / by means of SEND/RECEIVE / required | FDL driver included in scope of delivery of the CP |
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum | 80 |
Performance data / PROFIBUS DP |
Software / for DP master function / required | No |
Service / as DP master | |
DPV0 | Yes |
DPV1 | Yes |
DPV2 | Yes |
Number of DP slaves / on DP master / usable | 124 |
Amount of data | |
of the address area of the inputs / as DP master / total | 30256 byte |
of the address area of the outputs / as DP master / total | 30256 byte |
of the address area of the inputs / per DP slave | 244 byte |
of the address area of the outputs / per DP slave | 244 byte |
of the address area of the diagnostic data / per DP slave | 244 byte |
Software / for DP slave function / required | No |
Service / as DP slave | |
DPV0 | Yes |
DPV1 | Yes |
Amount of data | |
of the address area of the inputs / as DP slave / total | 244 byte |
of the address area of the outputs / as DP slave / total | 244 byte |
Performance data / S7 communication |
Software / for S7 communication / required | Yes, HARDNET-PB S7 (S7-5613) |
Number of possible connections / for S7/PG communication / maximum | 50 |
Performance data / multi-protocol mode |
Number of active connections / with multi-protocol mode | 50 |
Number of configurable connections / per PC station | 207 |
Product functions / management, configuration |
Configuration software / required | Included in scope of supply |
Product functions / Diagnosis |
Product function | |
Port diagnostics | Yes |
Standards, specifications, approvals |
Standard | |
for EMC | 89/336/EEC |
for safety / from CSA and UL | CAN/CSA C22.2 & UL 60950-1, UL 1950 |
for emitted interference | EN 61000-6-3 |
for interference immunity | EN 61000-6-2 |
Certificate of suitability | |
CE marking | Yes |
C-Tick | Yes |