Product type designation | PROFIBUS OLM/G12-1300 V4.0 |
| PROFIBUS OLM/G12-1300 V4.0 optical link module with 1 RS485 and 2 glass FOC Interfaces (4 BFOC sockets), 1300 Nm shaft Length for large distances with signaling contact and test port |
Transmission rate |
Transfer rate / with PROFIBUS | 9.6 kbit/s ... 12 Mbit/s |
Transfer rate / with PROFIBUS PA | 45.45 kbit/s |
Interfaces |
Number of electrical/optical connections / for network components or terminal equipment / maximum | 3 |
Number of electrical connections | |
for network components or terminal equipment | 1 |
for measuring device | 1 |
for signaling contact | 1 |
for power supply | 1 |
for redundant voltage supply | 1 |
Type of electrical connection | |
for network components or terminal equipment | 9-pin Sub-D socket |
for measuring device | 2-pole terminal block |
for power supply and signaling contact | 5-pole terminal block |
Number of optical interfaces / for fiber optic cable | 2 |
Design of the optical interface / for fiber optic cable | BFOC port |
Optical data |
Damping ratio / of the FOC transmission link | |
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum | 8 dB |
propagation delay [bit] | 6.5 bit |
Connectable optical power relative to 1 mW | |
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km | -19 dB |
Optical sensitivity relating to 1 mW | |
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km | -29 dB |
Wavelength | |
for glass FOC with 10/125 µm or 9/125 µm / compatible with interface / at 0.5 dB/km | 1310 nm |
Wire length | |
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum | 15 km |
Signal-Inputs/outputs |
Operating voltage / of the signaling contacts / at DC / Rated value | 24 V |
Operating current / of the signaling contacts / at DC / maximum | 0.1 A |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage / at DC / Rated value | 24 V |
Supply voltage / at DC | 18.8 ... 28.8 V |
Product component / fusing at power supply input | Yes |
Consumed current / at DC / at 24 V / maximum | 0.2 A |
Permitted ambient conditions |
Ambient temperature | |
during operation | 0 ... 60 °C |
during storage | -40 ... +70 °C |
during transport | -40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % |
Protection class IP | IP40 |
Design, dimensions and weight |
Design | compact |
Width | 39.5 mm |
Height | 112 mm |
Depth | 74.5 mm |
Net weight | 340 g |
Mounting type | |
35 mm DIN rail mounting | Yes |
wall mounting | Yes |
Product functions / Redundancy |
Product function / Ring redundancy | Yes |
Standards, specifications, approvals |
Standard | |
for FM | FM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4 |
for hazardous zone | EN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0003X |
for safety / from CSA and UL | UL 60950-1, CSA C22.2 Nr. 60950-1 |
for hazardous zone / from CSA and UL | UL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4 |
for emitted interference | EN 61000-6-4 (Class A) |
for interference immunity | EN 61000-6-2 |
Certificate of suitability | EN 61000-6-2, EN 61000-6-4 |
CE marking | Yes |
C-Tick | Yes |
Marine classification association | |
American Bureau of Shipping Europe Ltd. (ABS) | Yes |
Bureau Veritas (BV) | Yes |
Det Norske Veritas (DNV) | Yes |
Germanische Lloyd (GL) | Yes |
Lloyds Register of Shipping (LRS) | Yes |
Nippon Kaiji Kyokai (NK) | Yes |