6GK1503-3CC00
PROFIBUS OLM/G12-1300 V4.0

From SIEMENS

Product type designationPROFIBUS OLM/G12-1300 V4.0
PROFIBUS OLM/G12-1300 V4.0 optical link module with 1 RS485 and 2 glass FOC Interfaces (4 BFOC sockets), 1300 Nm shaft Length for large distances with signaling contact and test port
Transmission rate
Transfer rate / with PROFIBUS9.6 kbit/s ... 12 Mbit/s
Transfer rate / with PROFIBUS PA45.45 kbit/s
Interfaces
Number of electrical/optical connections / for network components or terminal equipment / maximum3
Number of electrical connections
for network components or terminal equipment1
for measuring device1
for signaling contact1
for power supply1
for redundant voltage supply1
Type of electrical connection
for network components or terminal equipment9-pin Sub-D socket
for measuring device2-pole terminal block
for power supply and signaling contact5-pole terminal block
Number of optical interfaces / for fiber optic cable2
Design of the optical interface / for fiber optic cableBFOC port
Optical data
Damping ratio / of the FOC transmission link
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum8 dB
propagation delay [bit]6.5 bit
Connectable optical power relative to 1 mW
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km-19 dB
Optical sensitivity relating to 1 mW
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km-29 dB
Wavelength
for glass FOC with 10/125 µm or 9/125 µm / compatible with interface / at 0.5 dB/km1310 nm
Wire length
for glass FOC with 10/125 µm or 9/125 µm / at 0.5 dB/km / maximum15 km
Signal-Inputs/outputs
Operating voltage / of the signaling contacts / at DC / Rated value24 V
Operating current / of the signaling contacts / at DC / maximum0.1 A
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage / at DC / Rated value24 V
Supply voltage / at DC18.8 ... 28.8 V
Product component / fusing at power supply inputYes
Consumed current / at DC / at 24 V / maximum0.2 A
Permitted ambient conditions
Ambient temperature
during operation0 ... 60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP40
Design, dimensions and weight
Designcompact
Width39.5 mm
Height112 mm
Depth74.5 mm
Net weight340 g
Mounting type
35 mm DIN rail mountingYes
wall mountingYes
Product functions / Redundancy
Product function / Ring redundancyYes
Standards, specifications, approvals
Standard
for FMFM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4
for hazardous zoneEN 60079-0: 2006, EN60079-15: 2005, II 3 G Ex nA II T4 KEMA 07 ATEX 0003X
for safety / from CSA and ULUL 60950-1, CSA C22.2 Nr. 60950-1
for hazardous zone / from CSA and ULUL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4
for emitted interferenceEN 61000-6-4 (Class A)
for interference immunityEN 61000-6-2
Certificate of suitabilityEN 61000-6-2, EN 61000-6-4
CE markingYes
C-TickYes
Marine classification association
American Bureau of Shipping Europe Ltd. (ABS)Yes
Bureau Veritas (BV)Yes
Det Norske Veritas (DNV)Yes
Germanische Lloyd (GL)Yes
Lloyds Register of Shipping (LRS)Yes
Nippon Kaiji Kyokai (NK)Yes

External links