| SIMATIC NET, DP/AS-Interface Link advanced, Gateway PROFIBUS DP/AS-Interface with master profile M3, M4 according to AS-i specification V3.0 for integration in PROFIBUS DP, Single master with display, Degree of protection IP20 |
General technical data: |
Product designation | | PROFIBUS DP/AS-Interface Link |
Product type designation | | DP/AS-i LINK Advanced (single master) |
Protection class IP | | IP20 |
Type of electrical connection of the AS-interface | | Screw-type connection |
Type of voltage supply | | via AS-i or 24 V DC |
Operating condition separate power supply 24 V | | No |
Supply voltage from optional external supply voltage at DC | V | 24 |
Consumed current | | |
from profile conductors of the AS-interface | | |
— at 30 V maximum | mA | 250 |
— at 24 V with AS-i Power24V maximum | mA | 250 |
Power loss [W] | W | 7.5 |
Insulation voltage rated value | V | 500 |
Product function suitable for AS-i Power24V | | Yes |
Note | | from product status 4 / firmware V2.2 |
Product feature redundancy capability | | Yes |
Note | | in connection with Y-Link |
Product function | | |
web-based management | | Yes |
Diagnostics via email | | Yes |
Galvanic isolation | | Yes |
Display version | | |
as status display by LED | | SF, BF, ON, APF, CER, AUP, CM |
as status indication through display | | LCD display, full graphic, backlighting, 128 x 64 pixels |
Type of configuration of the AS-interface | | Operator display, integrated web server, STEP7, GSD, command interface |
Communication/ Protocol: |
Version of the AS-interface specification | | V 3.0 |
AS-interface master profile is supported | | M4 (in acc. with AS-interface specification V 3.0) |
Type of data transmission | | PROFIBUS |
Number of interfaces | | |
as AS-interface | | 1 |
acc. to RS 485 | | 1 |
acc. to Industrial Ethernet | | 1 |
acc. to PROFINET | | 0 |
acc. to wireless | | 0 |
acc. to USB | | 0 |
other | | 1 |
Product component optical interface | | No |
Protocol is supported | | |
ASIsafe (Safety at work) protocol | | No |
PROFIsafe protocol | | No |
PROFIBUS protocol | | Yes |
PROFINET IO protocol | | No |
PROFINET CBA protocol | | No |
TCP/IP | | Yes |
SNMP | | Yes |
Standard for wireless communication IEEE 802.11 | | No |
Inputs/ Outputs: |
Number of inputs for AS Interface maximum | | 496 |
Number of outputs for AS Interface maximum | | 496 |
Number of AS-i slaves per AS-Interface maximum | | 62 |
Bus cycle time of the AS-interface | | |
for 31 slaves | ms | 5 |
for 62 slaves | ms | 10 |
Access to digital I/O data | | via process image/peripheral addresses |
Access to analog I/O data | | via process diagram/peripheral addresses and data record transfer |
Mechanical data: |
Width | mm | 90 |
Height | mm | 132 |
Depth | mm | 88.5 |
Mounting type | | snap-on fastening on 35 mm standard rail |
Module format | | IP20 |
Ambient conditions: |
Ambient temperature | | |
if installed on horizontal mounting rail | °C | 0 ... 60 |
during transport | °C | -30 ... +70 |
during storage | °C | -30 ... +70 |
Relative humidity at 25 °C during operation maximum | % | 95 |
Installation altitude at height above sea level maximum | m | 3 000 |
Safety related data: |
Suitability for use safety-related function | | No |
Explosion protection marking for intrinsic safety of related equipment | | |
EEx ia | | No |
EEx ib | | No |
Explosion protection category for gas | | none |
Explosion protection category for dust | | none |