6GK1162-8AA00
COMMUNICATION PROCESSOR CP 1628

From SIEMENS

Product type designationCP 1628
Communications processor CP 1628 PCI Express X1 (3, 3 V/12 V) for connection to Industrial Ethernet (10/100/1000 Mbit/s) with 2-port switch (RJ45) and integrated security (firewall VPN) via HARDNET-IE S7 and S7-REDCONNECT Operating system support see SIMATIC NET software
Transmission rate
Transfer rate10 Mbit/s, 100 Mbit/s, 1000 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet2
for power supply1
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port
for power supply2-pole terminal block
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Type of voltage supply / optional external supplyYes
Supply voltage
1 / from backplane bus3.3 V
2 / from backplane bus12 V
external24 V
external10.5 ... 32 V
Relative symmetrical tolerance / at DC
at 3.3 V9 %
at 5 V5 %
at 12 V8 %
at 24 V33 %
Consumed current
1 / from backplane bus / at DC / maximum0.85 A
2 / from backplane bus / at DC / maximum0.4 A
from external supply voltage / at DC / at 12 V / maximum0.55 A
from external supply voltage / at DC / at 24 V / maximum0.3 A
Power loss [W]7.6 W
Power loss [W] / in switch mode / maximum7.2 W
Permitted ambient conditions
Ambient temperature
during operation5 ... 55 °C
during storage-20 ... +60 °C
during transport-20 ... +60 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP00
Design, dimensions and weight
Module formatPCI Express x1 (half length)
Width18 mm
Height111 mm
Depth167 mm
Net weight124 g
Number of plug-in cards of same design / plug-in / per PC station4
Number of units / Note-
Performance data
Performance data / open communication
Software / for open communication / by means of SEND/RECEIVE / requiredYes, HARDNET-IE S7 (S7-1613)
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum120
Performance data / S7 communication
Software / for S7 communication / requiredYes, HARDNET-IE S7 (S7-1613)
Number of possible connections / for S7/PG communication / maximum120
Number of possible connections / for optimized S7 communication / maximum64
Performance data / multi-protocol mode
Number of active connections / with multi-protocol mode120
Number of configurable connections / per PC station207
Performance data / PROFINET CBA
Software / for PROFINET CBA communication / requiredYes, PN CBA OPC server
Number of remote connection partners / with PROFINET CBA228
Number of connections / with PROFINET CBA / total10000
Product functions / management, configuration
Product function / MIB supportYes
Protocol / is supported
SNMP v1Yes
SNMP v3Yes
DCPYes
LLDPNo
Configuration software / requiredIncluded in the scope of delivery of the required software product
Configuration software / for PROFINET CBA / requiredYes, SIMATIC iMAP
Identification & maintenance function
I&M0 - device-specific informationYes
I&M1 – higher-level designation/location designationYes
I&M2 - installation dateNo
I&M3 - commentNo
I&M4 - signatureNo
I&M4 - OEM dataNo
Product functions / switch
Product feature / SwitchYes
Product function / switch-managedNo
Product function / with IRT / PROFINET IO switchNo
Product functions / Redundancy
Software / for redundancy function / requiredYes, HARDNET-IE S7-REDCONNECT for communication with SIMATIC S7 H systems
Product functions / Security
Firewall versionstateful inspection
Product function / with VPN connectionIPSec
Type of encryption algorithms / with VPN connectionAES-256, AES-192, AES-128, 3DES-168, DES-56
Type of authentication procedure / with VPN connectionPreshared key (PSK), X.509v3 certificates
Type of hashing algorithms / with VPN connectionMD5, SHA-1
Number of possible VPN tunnels64
Number of possible connections / for S7 communication
via ISO and VPN / with S7-REDCONNECT / maximum64
via TCP and VPN / with S7-REDCONNECT / maximum120
Number of available IP addresses / with VPN connection / maximum16
Product functions / Time
Product function / SICLOCK supportYes
Protocol / is supported / NTPYes
Standards, specifications, approvals
Standard
for EMC2004/108/EC
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1, UL 1950
for emitted interferenceEN 61000-6-3, EN 61000-6-4
for interference immunityEN 61000-6-1, EN 61000-6-2
Certificate of suitability
CE markingYes
C-TickYes