6GK1162-6AA01
Communication processor CP 1626

From SIEMENS

Product type designationCP 1626
Communications processor CP 1626 PCI Express X1 to Connection to PROFINET IO as Controller and Device with Power and Standard machine support
Transmission rate
Transfer rate100 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet2
at the 2nd interface / acc. to Industrial Ethernet2
for power supply1
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port
at the 2nd interface / acc. to Industrial EthernetRJ45 port
for power supply2-pin plug-in terminal with push-in spring connection
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage
1 / from backplane bus3.3 V
2 / from backplane bus12 V
external24 V
external10.5 ... 32 V
Relative symmetrical tolerance / at DC
at 3.3 V9 %
at 12 V8 %
Consumed current
1 / from backplane bus / at DC / maximum2.1 A
2 / from backplane bus / at DC / maximum0.1 A
from external supply voltage / at DC / at 12 V / maximum0.8 A
from external supply voltage / at DC / at 24 V / maximum0.4 A
Power loss [W]8.1 W
Power loss [W] / in switch mode / maximum9.6 W
Permitted ambient conditions
Ambient temperature
during operation0 ... 70 °C
during storage-20 ... +60 °C
during transport-20 ... +60 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP00
Design, dimensions and weight
Module formatPCI Express x1 (half length)
Width21.6 mm
Height126.3 mm
Depth180.5 mm
Net weight110 g
Number of plug-in cards of same design / plug-in / per PC station1
Number of units / Note-
Performance data
Performance data / PROFINET communication / as PN IO-Controller
Software / for PROFINET IO communication / requiredIncluded in the scope of supply
Number of PN IO devices / on PROFINET IO controller / usable / total256
Number of PN IO IRT devices / on PROFINET IO controller / usable64
Amount of data
as user data for input variables / as PROFINET IO controller / maximum100000 byte
as user data for input variables / as PROFINET IO controller / maximum100000 byte
as user data for input variables per PN IO device / as PROFINET IO controller / maximum1430 byte
as user data for output variables per PN IO device / as PROFINET IO controller / maximum1430 byte
Performance data / PROFINET communication / as PN IO-Device
Amount of data
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / for each sub-module as PROFINET IO device1024 byte
as user data for input variables / for each sub-module as PROFINET IO device1024 byte
as user data for the consistency area for each sub-module1024 byte
Number of submodules / per PROFINET IO-Device512
Product functions / management, configuration
Product function / MIB supportYes
Protocol / is supported
SNMP v1Yes
DCPYes
LLDPYes
Configuration software / requiredIncluded in scope of supply
Identification & maintenance function
I&M0 - device-specific informationYes
I&M1 – higher-level designation/location designationYes
I&M2 - installation dateYes
I&M3 - commentYes
I&M4 - signatureYes
I&M4 - OEM dataYes
Product functions / Diagnosis
Product function
Web-based diagnosticsYes
Port diagnosticsYes
Product functions / switch
Product feature / SwitchYes
Product function / switch-managedNo
Product function / with IRT / PROFINET IO switchYes
Product functions / Redundancy
Software / for redundancy function / requiredNo
Product function
Ring redundancyYes
Redundancy managerYes
Protocol / is supported / Media Redundancy Protocol (MRP)Yes
Standards, specifications, approvals
Standard
for EMC2004/108/EC
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1
for emitted interferenceEN 61000-6-3, EN 61000-6-4
for interference immunityEN 61000-6-1, EN 61000-6-2
Certificate of suitability
CE markingYes
C-TickYes