6GK1161-6AA00
Communication processor CP 1616

From SIEMENS

Product type designationCP 1616
Communications processor CP 1616 PCI card (32 bit; 33/66M Hz; 3.3/5 V) with ASIC ERTEC 400 for connection to PROFINET IO with 4-port real-time switch (RJ45) via development kit DK-16XX PN IO; NCM PC
Transmission rate
Transfer rate100 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet4
for power supply1
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port
for power supplyLow-voltage socket for hollow plug 3.5 mm (-) / 1.3 mm (+)
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage
1 / from backplane bus5 V
external6 ... 9 V
Relative symmetrical tolerance / at DC
at 5 V5 %
at 12 V5 %
Consumed current
1 / from backplane bus / at DC / maximum0.8 A
from external supply voltage / at DC / at 6 V / maximum0.65 A
from external supply voltage / at DC / at 9 V / maximum0.45 A
Power loss [W]4 W
Power loss [W] / in switch mode / maximum4.1 W
Permitted ambient conditions
Ambient temperature
during operation5 ... 55 °C
during storage-20 ... +60 °C
during transport-20 ... +60 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP00
Design, dimensions and weight
Module formatPCI
Width18 mm
Height107 mm
Depth167 mm
Net weight110 g
Number of plug-in cards of same design / plug-in / per PC station1
Number of units / Note-
Performance data
Performance data / PROFINET communication / as PN IO-Controller
Software / for PROFINET IO communication / requiredNo
Number of PN IO devices / on PROFINET IO controller / usable / total128
Number of PN IO IRT devices / on PROFINET IO controller / usable64
Amount of data
as user data for input variables / as PROFINET IO controller / maximum8192 byte
as user data for input variables / as PROFINET IO controller / maximum8192 byte
as user data for input variables per PN IO device / as PROFINET IO controller / maximum1430 byte
as user data for output variables per PN IO device / as PROFINET IO controller / maximum1430 byte
Performance data / PROFINET communication / as PN IO-Device
Amount of data
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / for each sub-module as PROFINET IO device254 byte
as user data for input variables / for each sub-module as PROFINET IO device254 byte
as user data for the consistency area for each sub-module254 byte
Number of submodules / per PROFINET IO-Device64
Product functions / management, configuration
Product function / MIB supportYes
Protocol / is supported
SNMP v1Yes
DCPYes
LLDPYes
Configuration software / requiredIncluded in scope of supply
Identification & maintenance function
I&M0 - device-specific informationYes
I&M1 – higher-level designation/location designationYes
I&M2 - installation dateYes
I&M3 - commentYes
I&M4 - signatureYes
I&M4 - OEM dataYes
Product functions / Diagnosis
Product function
Web-based diagnosticsYes
Port diagnosticsYes
Product functions / switch
Product feature / SwitchYes
Product function / switch-managedNo
Product function / with IRT / PROFINET IO switchYes
Product functions / Redundancy
Software / for redundancy function / requiredNo
Product function
Ring redundancyYes
Redundancy managerYes
Protocol / is supported / Media Redundancy Protocol (MRP)Yes
Standards, specifications, approvals
Standard
for EMC89/336/EEC
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1
for emitted interferenceEN 61000-6-3, EN 61000-6-4
for interference immunityEN 61000-6-1, EN 61000-6-2
Certificate of suitability
CE markingYes
C-TickYes