6GK1161-2AA00
COMMUNICATION PROCESSOR CP 1612

From SIEMENS

Product type designationCP 1612
COMMUNICATION PROCESSOR CP 1612 PCI CARD (32BITS) F. CONNECTION (10/100MBIT/S)OF A PG/PC TO IE WITH RJ 45 PORT VIA SOFTNET-S7 AND SOFTNET-PG, SUPPORT FOR OPERATING SYSTEM SEE SIMATIC NET SW
Transmission rate
Transfer rate10 Mbit/s, 100 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet1
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage
1 / from backplane bus5 V
2 / from backplane bus12 V
Relative symmetrical tolerance / at DC
at 5 V5 %
at 12 V5 %
Permitted ambient conditions
Ambient temperature
during operation0 ... 50 °C
during storage-25 ... +55 °C
during transport-25 ... +55 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum90 %
Protection class IPIP00
Design, dimensions and weight
Module formatPCI
Width18 mm
Height50 mm
Depth120 mm
Net weight100 g
Number of plug-in cards of same design / plug-in / per PC station2
Number of units / Note-
Performance data
Performance data / open communication
Software / for open communication / by means of SEND/RECEIVE / requiredYes, SOFTNET-IE S7 / SOFTNET-IE S7 Lean
Number of possible connections / for open communication / by means of SEND/RECEIVE / maximum64
Performance data / S7 communication
Software / for S7 communication / requiredYes, SOFTNET-IE S7 / SOFTNET-IE S7 Lean
Number of possible connections / for S7/PG communication / maximum64
Performance data / multi-protocol mode
Number of active connections / with multi-protocol mode64
Number of configurable connections / per PC station207
Performance data / PROFINET communication / as PN IO-Controller
Software / for PROFINET IO communication / requiredYes, SOFTNET-IE PN IO
Number of PN IO devices / on PROFINET IO controller / usable / total64
Number of PN IO IRT devices / on PROFINET IO controller / usable0
Amount of data
as user data for input variables / as PROFINET IO controller / maximum4096 byte
as user data for input variables / as PROFINET IO controller / maximum4096 byte
as user data for input variables per PN IO device / as PROFINET IO controller / maximum1430 byte
as user data for output variables per PN IO device / as PROFINET IO controller / maximum1430 byte
Performance data / PROFINET CBA
Software / for PROFINET CBA communication / requiredYes, PN CBA OPC server
Number of remote connection partners / with PROFINET CBA228
Number of connections / with PROFINET CBA / total10000
Product functions / management, configuration
Product function / MIB supportYes
Protocol / is supported
SNMP v1Yes
DCPNo
LLDPNo
Configuration software / requiredIncluded in the scope of delivery of the required software product
Configuration software / for PROFINET CBA / requiredYes, SIMATIC iMAP
Standards, specifications, approvals
Standard
for EMC2004/108/EC
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1, UL 1950
for emitted interferenceEN 61000-6-3, EN 61000-6-4
for interference immunityEN 61000-6-1, EN 61000-6-2
Certificate of suitability
CE markingYes
C-TickYes

External links