6GK1160-4AT00
COMMUNICATIONS PROCESSOR CP 1604 TS.

From SIEMENS

Product type designationCP 1604 TS
Communications processor CP 1604 TS PC/104 plus card (32 bit; 33/66M Hz; 3.3/5V) with ASIC ERTEC 400 for connection to PROFINET IO with 4-port real-time switch train-compatible version
Transmission rate
Transfer rate100 Mbit/s
Interfaces
Number of electrical connections
at the 1st interface / acc. to Industrial Ethernet4
for power supply1
Type of electrical connection
at the 1st interface / acc. to Industrial EthernetRJ45 port via connection board
for power supply4-pole terminal block through power supply board
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage
1 / from backplane bus5 V
Relative symmetrical tolerance / at DC
at 5 V5 %
Consumed current
1 / from backplane bus / at DC / maximum0.8 A
from external supply voltage / at DC / at 24 V / maximum0.3 A
Power loss [W]4 W
Power loss [W] / in switch mode / maximum4.1 W
Design, dimensions and weight
Module formatPCI-104
Width90 mm
Height24 mm
Depth95 mm
Mounting typeScrew mounting
Number of plug-in cards of same design / plug-in / per PC station1
Number of units / Note-
Performance data
Performance data / PROFINET communication / as PN IO-Controller
Software / for PROFINET IO communication / requiredNo
Number of PN IO devices / on PROFINET IO controller / usable / total128
Number of PN IO IRT devices / on PROFINET IO controller / usable64
Amount of data
as user data for input variables / as PROFINET IO controller / maximum8192 byte
as user data for input variables / as PROFINET IO controller / maximum8192 byte
as user data for input variables per PN IO device / as PROFINET IO controller / maximum1430 byte
as user data for output variables per PN IO device / as PROFINET IO controller / maximum1430 byte
Performance data / PROFINET communication / as PN IO-Device
Amount of data
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / as PROFINET IO device / maximum1430 byte
as user data for input variables / for each sub-module as PROFINET IO device254 byte
as user data for input variables / for each sub-module as PROFINET IO device254 byte
as user data for the consistency area for each sub-module254 byte
Number of submodules / per PROFINET IO-Device64
Product functions / management, configuration
Product function / MIB supportYes
Protocol / is supported
SNMP v1Yes
DCPYes
LLDPYes
Configuration software / requiredIncluded in scope of supply
Product functions / Diagnosis
Product function
Web-based diagnosticsYes
Port diagnosticsYes
Product functions / switch
Product feature / SwitchYes
Product function / switch-managedNo
Product function / with IRT / PROFINET IO switchYes
Product functions / Redundancy
Software / for redundancy function / requiredNo
Product function
Ring redundancyYes
Redundancy managerYes
Protocol / is supported / Media Redundancy Protocol (MRP)Yes
Standards, specifications, approvals
Standard
for safety / from CSA and ULCAN/CSA C22.2 & UL 60950-1
for emitted interferenceEN 61000-6-3
for interference immunityEN 61000-6-3
Certificate of suitability
CE markingYes
C-TickYes

External links