Product type designation | CP 1604 TS |
| Communications processor CP 1604 TS PC/104 plus card (32 bit; 33/66M Hz; 3.3/5V) with ASIC ERTEC 400 for connection to PROFINET IO with 4-port real-time switch train-compatible version |
Transmission rate |
Transfer rate | 100 Mbit/s |
Interfaces |
Number of electrical connections | |
at the 1st interface / acc. to Industrial Ethernet | 4 |
for power supply | 1 |
Type of electrical connection | |
at the 1st interface / acc. to Industrial Ethernet | RJ45 port via connection board |
for power supply | 4-pole terminal block through power supply board |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage | DC |
Supply voltage | |
1 / from backplane bus | 5 V |
Relative symmetrical tolerance / at DC | |
at 5 V | 5 % |
Consumed current | |
1 / from backplane bus / at DC / maximum | 0.8 A |
from external supply voltage / at DC / at 24 V / maximum | 0.3 A |
Power loss [W] | 4 W |
Power loss [W] / in switch mode / maximum | 4.1 W |
Design, dimensions and weight |
Module format | PCI-104 |
Width | 90 mm |
Height | 24 mm |
Depth | 95 mm |
Mounting type | Screw mounting |
Number of plug-in cards of same design / plug-in / per PC station | 1 |
Number of units / Note | - |
Performance data |
Performance data / PROFINET communication / as PN IO-Controller |
Software / for PROFINET IO communication / required | No |
Number of PN IO devices / on PROFINET IO controller / usable / total | 128 |
Number of PN IO IRT devices / on PROFINET IO controller / usable | 64 |
Amount of data | |
as user data for input variables / as PROFINET IO controller / maximum | 8192 byte |
as user data for input variables / as PROFINET IO controller / maximum | 8192 byte |
as user data for input variables per PN IO device / as PROFINET IO controller / maximum | 1430 byte |
as user data for output variables per PN IO device / as PROFINET IO controller / maximum | 1430 byte |
Performance data / PROFINET communication / as PN IO-Device |
Amount of data | |
as user data for input variables / as PROFINET IO device / maximum | 1430 byte |
as user data for input variables / as PROFINET IO device / maximum | 1430 byte |
as user data for input variables / for each sub-module as PROFINET IO device | 254 byte |
as user data for input variables / for each sub-module as PROFINET IO device | 254 byte |
as user data for the consistency area for each sub-module | 254 byte |
Number of submodules / per PROFINET IO-Device | 64 |
Product functions / management, configuration |
Product function / MIB support | Yes |
Protocol / is supported | |
SNMP v1 | Yes |
DCP | Yes |
LLDP | Yes |
Configuration software / required | Included in scope of supply |
Product functions / Diagnosis |
Product function | |
Web-based diagnostics | Yes |
Port diagnostics | Yes |
Product functions / switch |
Product feature / Switch | Yes |
Product function / switch-managed | No |
Product function / with IRT / PROFINET IO switch | Yes |
Product functions / Redundancy |
Software / for redundancy function / required | No |
Product function | |
Ring redundancy | Yes |
Redundancy manager | Yes |
Protocol / is supported / Media Redundancy Protocol (MRP) | Yes |
Standards, specifications, approvals |
Standard | |
for safety / from CSA and UL | CAN/CSA C22.2 & UL 60950-1 |
for emitted interference | EN 61000-6-3 |
for interference immunity | EN 61000-6-3 |
Certificate of suitability | |
CE marking | Yes |
C-Tick | Yes |