6ES7673-6CC20-0YX0
SIMATIC WINAC SLOT 416 V3.2,

From SIEMENS

SIMATIC WINAC SLOT 416 V3.2, SINGLE LICENSE F. 1 INSTALL., INCL R-SW, SW AND DOCU. ON CD, CLASS A, 3 LANGUAGES (G,E,F), EXECUTABLE UNDER WIN NT/2000, REFERENCE-HW: SIMATIC PC
General information
HW functional status1
Firmware versionV3.0
Input current
Current consumption, max.1.5 A; from PCI bus without PS Extension Board; 0.3 A with PS Extension Board; current consumption 12 V/24 V via PS Extension Board 1.2 A
Power
Active power input, typ.12 W
Memory
Work memory
integrated16 Mbyte; 16 MB code + 16 MB data
Load memory
expandable FEPROMYes; Memory Card (FLASH) up to 64 MB
expandable FEPROM, max.64 Mbyte
integrated RAM, max.256 kbyte
expandable RAMYes; Memory Card (FLASH) up to 64 MB
expandable RAM, max.16 Mbyte
Battery
Backup battery
Backup current, typ.130 µA
Backup current, max.500 µA; Backup battery voltage: 3.6 V Lithium
CPU processing times
for bit operations, typ.0.08 µs
for fixed point arithmetic, typ.0.08 µs
for floating point arithmetic, typ.0.48 µs
CPU-blocks
DB
Number, max.4 095
Size, max.64 kbyte
FB
Number, max.2 048
Size, max.64 kbyte
FC
Number, max.2 048
Size, max.64 kbyte
OB
Size, max.64 kbyte
Number of time alarm OBs8
Number of delay alarm OBs4
Number of cyclic interrupt OBs9
Number of process alarm OBs8
Nesting depth
per priority class24
additional within an error OB2
Counters, timers and their retentivity
S7 counter
Number512
Retentivity
— adjustableYes
— lower limit0
— upper limit511
— presetZ 0 to Z 7
Counting range
— adjustableYes
— lower limit1
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number512
Retentivity
— lower limit0
— upper limit511
— presetNo retentivity
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
Retentivity without UPS and PS Extension Boardnone
Retentivity with UPSnone
Retentivity with PS extension board and batteryall data
Flag
Number, max.16 kbyte
of which retentiveMB 0 to MB 16383
Retentivity presetMB 0 to MB 15
Number of clock memories8
Address area
I/O address area
Inputs16 kbyte
Outputs16 kbyte
Process image
Inputs, adjustable16 kbyte
Outputs, adjustable16 kbyte
Inputs, default512 byte
Outputs, default512 byte
Subprocess images
Number of subprocess images, max.8
Digital channels
Inputs81 920
Outputs81 920
Analog channels
Inputs5 120
Outputs5 120
Hardware configuration
Number of DP masters
integrated2
Number of operable FMs and CPs (recommended)
FMFM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2
CP, LANOver PC CP
Slots
Number of single-width slots, max.1; 2 with PC extension board; PCI format 3/4
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Clock synchronization
supportedYes; to PC-CP: Slave
to MPI, masterYes
to MPI, slaveYes
1. Interface
PhysicsRS 485 / PROFIBUS
IsolatedYes
Protocols
MPIYes
PROFIBUS DP masterYes
PROFIBUS DP slaveYes
MPI
Number of connections44
Transmission rate, max.12 Mbit/s
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationYes
— S7 basic communicationYes
— S7 communicationYes
PROFIBUS DP master
Number of connections, max.32
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.32
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationYes
— S7 communicationYes
— EquidistanceYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.2 kbyte
— Outputs, max.2 kbyte
User data per DP slave
— User data per DP slave, max.244 byte; 244 byte / 244 byte
PROFIBUS DP slave
Services
— RoutingYes
2. Interface
PhysicsRS 485 / PROFIBUS
IsolatedYes
Protocols
MPINo
PROFIBUS DP masterYes
PROFIBUS DP slaveYes
PROFIBUS DP master
Number of connections, max.32
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.125
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationYes
— S7 communicationYes
— EquidistanceYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.8 kbyte
— Outputs, max.8 kbyte
User data per DP slave
— User data per DP slave, max.244 byte; 244 byte / 244 byte
PROFIBUS DP slave
Services
— PG/OP communicationYes
— RoutingYes
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
S7 basic communication
supportedYes
S7 communication
as serverYes
as clientYes
Number of connections
overall64
usable for PG communication
— reserved for PG communication1
usable for OP communication
— reserved for OP communication1
S7 message functions
Number of login stations for message functions, max.12
SCAN procedureYes
Process diagnostic messagesYes; Alarm_S
Alarm 8-blocksYes
Process control messagesYes
Test commissioning functions
Status blockYes
Single stepYes
Status/control
Status/control variableYes
Forcing
ForcingYes
Diagnostic buffer
presentYes
Number of entries, max.3 200
— preset120
Hardware requirement
Hardware requiredAccessories: color monitor, keyboard, mouse or pointer for Windows
Processor
ProcessorIntel Pentium 300 MHz
Memory
Main memory, min.128 Mbyte
Required memory on hard disk60 Mbyte
Operating systems
pre-installed operating system
Windows NT 4.0Yes; WS, ≥ SP6
Windows 2000Yes; Professional, SP3 or higher
Configuration
Software interfaceC/C++ with WinAC Slot T-Kit
Configuration software
STEP 7Yes
Programming
Nesting levels8
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Software libraries
— Easy Motion ControlYes
Know-how protection
User program protection/password protectionYes
Open Development interfaces
SMX (Shared Memory Extension)
— Inputs4 kbyte
— Outputs4 kbyte
Dimensions
Width98 mm
Height288 mm
Weights
Weight, approx.250 g; 450 g with PC extension board
last modified:03/13/2019