| SIMATIC WINAC SLOT 416 V3.2, SINGLE LICENSE F. 1 INSTALL., INCL R-SW, SW AND DOCU. ON CD, CLASS A, 3 LANGUAGES (G,E,F), EXECUTABLE UNDER WIN NT/2000, REFERENCE-HW: SIMATIC PC |
General information |
HW functional status | 1 |
Firmware version | V3.0 |
Input current |
Current consumption, max. | 1.5 A; from PCI bus without PS Extension Board; 0.3 A with PS Extension Board; current consumption 12 V/24 V via PS Extension Board 1.2 A |
Power |
Active power input, typ. | 12 W |
Memory |
Work memory |
integrated | 16 Mbyte; 16 MB code + 16 MB data |
Load memory |
expandable FEPROM | Yes; Memory Card (FLASH) up to 64 MB |
expandable FEPROM, max. | 64 Mbyte |
integrated RAM, max. | 256 kbyte |
expandable RAM | Yes; Memory Card (FLASH) up to 64 MB |
expandable RAM, max. | 16 Mbyte |
Battery |
Backup battery |
Backup current, typ. | 130 µA |
Backup current, max. | 500 µA; Backup battery voltage: 3.6 V Lithium |
CPU processing times |
for bit operations, typ. | 0.08 µs |
for fixed point arithmetic, typ. | 0.08 µs |
for floating point arithmetic, typ. | 0.48 µs |
CPU-blocks |
DB |
Number, max. | 4 095 |
Size, max. | 64 kbyte |
FB |
Number, max. | 2 048 |
Size, max. | 64 kbyte |
FC |
Number, max. | 2 048 |
Size, max. | 64 kbyte |
OB |
Size, max. | 64 kbyte |
Number of time alarm OBs | 8 |
Number of delay alarm OBs | 4 |
Number of cyclic interrupt OBs | 9 |
Number of process alarm OBs | 8 |
Nesting depth |
per priority class | 24 |
additional within an error OB | 2 |
Counters, timers and their retentivity |
S7 counter |
Number | 512 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 511 |
— preset | Z 0 to Z 7 |
Counting range |
— adjustable | Yes |
— lower limit | 1 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
S7 times |
Number | 512 |
Retentivity |
— lower limit | 0 |
— upper limit | 511 |
— preset | No retentivity |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Data areas and their retentivity |
Retentivity without UPS and PS Extension Board | none |
Retentivity with UPS | none |
Retentivity with PS extension board and battery | all data |
Flag |
Number, max. | 16 kbyte |
of which retentive | MB 0 to MB 16383 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8 |
Address area |
I/O address area |
Inputs | 16 kbyte |
Outputs | 16 kbyte |
Process image |
Inputs, adjustable | 16 kbyte |
Outputs, adjustable | 16 kbyte |
Inputs, default | 512 byte |
Outputs, default | 512 byte |
Subprocess images |
Number of subprocess images, max. | 8 |
Digital channels |
Inputs | 81 920 |
Outputs | 81 920 |
Analog channels |
Inputs | 5 120 |
Outputs | 5 120 |
Hardware configuration |
Number of DP masters |
integrated | 2 |
Number of operable FMs and CPs (recommended) |
FM | FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2 |
CP, LAN | Over PC CP |
Slots |
Number of single-width slots, max. | 1; 2 with PC extension board; PCI format 3/4 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Clock synchronization |
supported | Yes; to PC-CP: Slave |
to MPI, master | Yes |
to MPI, slave | Yes |
1. Interface |
Physics | RS 485 / PROFIBUS |
Isolated | Yes |
Protocols |
MPI | Yes |
PROFIBUS DP master | Yes |
PROFIBUS DP slave | Yes |
MPI |
Number of connections | 44 |
Transmission rate, max. | 12 Mbit/s |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
PROFIBUS DP master |
Number of connections, max. | 32 |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 32 |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | Yes |
— S7 communication | Yes |
— Equidistance | Yes |
— SYNC/FREEZE | Yes |
— Activation/deactivation of DP slaves | Yes |
— Direct data exchange (slave-to-slave communication) | Yes |
— DPV0 | Yes |
— DPV1 | Yes |
Address area |
— Inputs, max. | 2 kbyte |
— Outputs, max. | 2 kbyte |
User data per DP slave |
— User data per DP slave, max. | 244 byte; 244 byte / 244 byte |
PROFIBUS DP slave |
Services |
— Routing | Yes |
2. Interface |
Physics | RS 485 / PROFIBUS |
Isolated | Yes |
Protocols |
MPI | No |
PROFIBUS DP master | Yes |
PROFIBUS DP slave | Yes |
PROFIBUS DP master |
Number of connections, max. | 32 |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 125 |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | Yes |
— S7 communication | Yes |
— Equidistance | Yes |
— SYNC/FREEZE | Yes |
— Activation/deactivation of DP slaves | Yes |
— Direct data exchange (slave-to-slave communication) | Yes |
— DPV0 | Yes |
— DPV1 | Yes |
Address area |
— Inputs, max. | 8 kbyte |
— Outputs, max. | 8 kbyte |
User data per DP slave |
— User data per DP slave, max. | 244 byte; 244 byte / 244 byte |
PROFIBUS DP slave |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Communication functions |
PG/OP communication | Yes |
Global data communication |
supported | Yes |
S7 basic communication |
supported | Yes |
S7 communication |
as server | Yes |
as client | Yes |
Number of connections |
overall | 64 |
usable for PG communication | |
— reserved for PG communication | 1 |
usable for OP communication | |
— reserved for OP communication | 1 |
S7 message functions |
Number of login stations for message functions, max. | 12 |
SCAN procedure | Yes |
Process diagnostic messages | Yes; Alarm_S |
Alarm 8-blocks | Yes |
Process control messages | Yes |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Status/control |
Status/control variable | Yes |
Forcing |
Forcing | Yes |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 3 200 |
— preset | 120 |
Hardware requirement |
Hardware required | Accessories: color monitor, keyboard, mouse or pointer for Windows |
Processor |
Processor | Intel Pentium 300 MHz |
Memory |
Main memory, min. | 128 Mbyte |
Required memory on hard disk | 60 Mbyte |
Operating systems |
pre-installed operating system |
Windows NT 4.0 | Yes; WS, ≥ SP6 |
Windows 2000 | Yes; Professional, SP3 or higher |
Configuration |
Software interface | C/C++ with WinAC Slot T-Kit |
Configuration software |
STEP 7 | Yes |
Programming |
Nesting levels | 8 |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Software libraries |
— Easy Motion Control | Yes |
Know-how protection |
User program protection/password protection | Yes |
Open Development interfaces |
SMX (Shared Memory Extension) | |
— Inputs | 4 kbyte |
— Outputs | 4 kbyte |
Dimensions |
Width | 98 mm |
Height | 288 mm |
Weights |
Weight, approx. | 250 g; 450 g with PC extension board |
last modified: | 03/13/2019 |