| SIMATIC WINAC RTX 2005, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON FD, CLASS A, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN 2000/XP AND ARDENCE RTX, REFERENCE-HW: SIMATIC PC |
| General information |
| Product type designation | SIMATIC WinAC RTX 2005 incl. SP2 |
| Firmware version | 4,3 |
| Memory |
| Work memory |
| integrated | PC RAM can be used (non-paged memory) |
| Load memory |
| integrated RAM, max. | PC RAM can be used (non-paged memory) |
| CPU processing times |
| for bit operations, typ. | 0.004 µs; Typical |
| for fixed point arithmetic, typ. | 0.003 µs; Typical |
| for floating point arithmetic, typ. | 0.004 µs; Typical |
| Reference platform | Pentium 4, 2.4 GHz |
| CPU-blocks |
| DB |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| FB |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| FC |
| Number, max. | Limited only by available PC work memory |
| Size, max. | 64 kbyte |
| OB |
| Size, max. | 64 kbyte |
| Number of time alarm OBs | 1 |
| Number of delay alarm OBs | 1 |
| Number of cyclic interrupt OBs | 9 |
| Number of process alarm OBs | 1 |
| Nesting depth |
| per priority class | 24 |
| additional within an error OB | 24 |
| Counters, timers and their retentivity |
| S7 counter |
| Number | 2 048 |
| Retentivity |
| — adjustable | Yes |
| — lower limit | 0 |
| — upper limit | 2 047 |
| — preset | 8 |
| Counting range |
| — adjustable | Yes |
| — lower limit | 0 |
| — upper limit | 999 |
| IEC counter |
| present | Yes |
| Type | SFB |
| S7 times |
| Number | 2 048 |
| Retentivity |
| — lower limit | 0 |
| — upper limit | 2 047 |
| — preset | 0 |
| Time range |
| — lower limit | 10 ms |
| — upper limit | 9 990 s |
| IEC timer |
| present | Yes |
| Type | SFB |
| Data areas and their retentivity |
| Retentivity without UPS and PS Extension Board | 128 KB with SIMATIC Microbox PC 427B and Panel PC 477B; other SIMATIC PCs on request |
| Retentivity with UPS | all data |
| Flag |
| Number, max. | 16 kbyte |
| of which retentive | MB 0 to MB 16383 |
| Retentivity preset | MB 0 to MB 15 |
| Number of clock memories | 8 |
| Address area |
| I/O address area |
| Inputs | 16 kbyte |
| Outputs | 16 kbyte |
| Process image |
| Inputs, adjustable | 8 kbyte |
| Outputs, adjustable | 8 kbyte |
| Inputs, default | 512 byte |
| Outputs, default | 512 byte |
| Subprocess images |
| Number of subprocess images, max. | 15 |
| Digital channels |
| Inputs | 128 000 |
| Outputs | 128 000 |
| Analog channels |
| Inputs | 8 000 |
| Outputs | 8 000 |
| Hardware configuration |
| Number of operable FMs and CPs (recommended) |
| FM | FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2 |
| CP, PtP | CP 340, CP 341 distributed |
| CP, LAN | Over PC CP |
| Submodules |
| Number of submodules, max | 4 |
| — of which PROFIBUS, max. | 4; CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC, CP 5613 CP, 5613-A2 |
| Time of day |
| Clock |
| Hardware clock (real-time) | Yes |
| retentive and synchronizable | Yes |
| Clock synchronization |
| supported | Yes |
| to PC-CP, slave | Yes |
| 1. Interface |
| Interface type | CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC |
| Physics | RS 485 / PROFIBUS |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 1 |
| Protocols |
| MPI | No |
| PROFIBUS DP master | Yes |
| PROFIBUS DP slave | No |
| PROFIBUS DP master |
| Number of connections, max. | 8 |
| Transmission rate, max. | 12 Mbit/s |
| Number of DP slaves, max. | 64 |
| Services |
| — PG/OP communication | Yes |
| — Routing | Yes |
| — Global data communication | No |
| — S7 basic communication | No |
| — S7 communication | Yes |
| — Equidistance | Yes; Only in conjunction with isochronous mode |
| — Isochronous mode | Yes |
| — SYNC/FREEZE | Yes |
| — Activation/deactivation of DP slaves | Yes |
| — Direct data exchange (slave-to-slave communication) | Yes |
| — DPV0 | Yes |
| — DPV1 | Yes |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| User data per DP slave |
| — Inputs, max. | 244 byte |
| — Outputs, max. | 244 byte |
| 2. Interface |
| Interface type | CP 5613, CP 5613-A2 |
| Physics | RS 485 / PROFIBUS |
| Isolated | Yes |
| Number of simultaneously operable CPs, max. | 4 |
| Protocols |
| MPI | No |
| PROFIBUS DP master | Yes |
| PROFIBUS DP slave | No |
| PROFIBUS DP master |
| Number of connections, max. | 50 |
| Transmission rate, max. | 12 Mbit/s |
| Number of DP slaves, max. | 125 |
| Services |
| — PG/OP communication | Yes |
| — Routing | Yes |
| — Global data communication | No |
| — S7 basic communication | No |
| — S7 communication | Yes |
| — Equidistance | Yes; Only in conjunction with isochronous mode |
| — Isochronous mode | Yes |
| — SYNC/FREEZE | Yes |
| — Activation/deactivation of DP slaves | Yes |
| — Direct data exchange (slave-to-slave communication) | Yes |
| — DPV0 | Yes |
| — DPV1 | Yes |
| Address area |
| — Inputs, max. | 16 kbyte |
| — Outputs, max. | 16 kbyte |
| User data per DP slave |
| — Inputs, max. | 244 byte |
| — Outputs, max. | 244 byte |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) | Yes |
| Equidistance | Yes |
| Number of DP masters with isochronous mode | 2 |
| User data per isochronous slave, max. | 128 byte |
| shortest clock pulse | 2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image |
| Communication functions |
| PG/OP communication | Yes |
| Global data communication |
| supported | No |
| S7 basic communication |
| supported | No |
| S7 communication |
| as server | Yes |
| as client | Yes |
| Number of connections |
| overall | 64 |
| usable for PG communication | |
| — reserved for PG communication | 1 |
| usable for OP communication | |
| — reserved for OP communication | 1 |
| S7 message functions |
| Number of login stations for message functions, max. | 62 |
| SCAN procedure | No |
| Process diagnostic messages | Yes; Alarm_S |
| Alarm 8-blocks | Yes |
| Process control messages | No |
| Test commissioning functions |
| Status block | Yes |
| Single step | Yes |
| Status/control |
| Status/control variable | Yes |
| Forcing |
| Forcing | No |
| Diagnostic buffer |
| present | Yes |
| Number of entries, max. | |
| — preset | 120 |
| Hardware requirement |
| Hardware required | PC with color monitor, keyboard, mouse or pointing device for Windows |
| Processor |
| Processor | Intel Pentium 400 MHz |
| — Multi-processor system | Yes; Dual Pentium, CoreDuo, Core2Duo |
| — Hyper-threading | Yes |
| Memory |
| Main memory, min. | 256 Mbyte |
| Required memory on hard disk | 100 Mbyte |
| Operating systems |
| pre-installed operating system |
| Windows NT 4.0 | No |
| Windows 2000 | Yes; Professional, SP3 or higher |
| Windows XP | Yes; Professional, SP1 and SP2 |
| Windows XP Embedded | Yes; With the delivery image of the SIMATIC PC |
| — supported HAL types under Windows XP | PC with single core processor without Hyper-Threading: ACPI-PC, ACPI uniprocessor PC; PC with multicore processors or Hyper-Threading: ACPI multiprocessor PC |
| Configuration |
| Configuration software |
| STEP 7 | Yes; V5.3 SP3 or higher, Engineering Tools (optional) |
| Programming |
| Nesting levels | 8 |
| Programming language |
| — LAD | Yes |
| — FBD | Yes |
| — STL | Yes |
| — SCL | Yes |
| — CFC | Yes |
| — GRAPH | Yes |
| — HiGraph® | Yes |
| Software libraries |
| — Easy Motion Control | Yes |
| Know-how protection |
| User program protection/password protection | Yes |
| Open Development interfaces |
| CCX (Custom Code Extension) | Yes; With WinAC ODK V4.1 |
| CMI (Controller Management Interface) | Yes; With WinAC ODK V4.1 |
| SMX (Shared Memory Extension) | Yes; With WinAC ODK V4.1 |
| — Inputs | 4 kbyte |
| — Outputs | 4 kbyte |
| last modified: | 03/13/2019 |