6ES7634-1DF02-0AE3
C7-634/P

From SIEMENS

*** SPARE PART*** SIMATIC C7-634/P, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU 315, OP17, IM 360 16DI, 16DO, 4AI, 4AO, 4 UI
Operator control and monitoring
Password protectionYes
Password levels9
Graphics object
Character graphicsYes; As part of the character set
Process images
Number of process images99
Number of variables in message text, max.8
Entries per process image99
Operating-/fault messages
Number of operating messages, max.999
Scroll operating messages, max.256
Number of entries in operational log, max.256
Number of fault message, max.999
Number of entries in fault message buffer, max.256
Number of symbol/character sets1
Recipes
Number, max.99
Data records per recipe, max.99
Entries per data record, max.99
Recipe data memory, max.20 kbyte
Display
Design of displayLCD backlit
dynamic objectsInput, output, input/output fields, date/time fields, symbolic input/output fields
Line display
Number of lines8; 4x 20 / 8x 40
Number of characters per line40; 4x 20 / 8x 40
Character size6 mm; 11/6 mm
Backlighting
MTBF backlighting (at 25 °C)100 000 h; about 11 years
Control elements
Keyboard fonts
Function keys
— Number of function keys16
— Number of softkeys8
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)30.2 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption, typ.550 mA
Current consumption, max.1 A
Power loss
Power loss, typ.12 W
Memory
Work memory
integrated48 kbyte; 16 K instructions RAM
Load memory
expandable FEPROMYes
expandable FEPROM, max.512 kbyte
integrated RAM, max.80 kbyte; for data
Backup
with batteryYes; all data
without batteryYes; 4736 Byte: parameterizable for memory bits, times, counters, data
CPU processing times
for bit operations, typ.0.3 µs
for bit operations, max.0.6 µs
for word operations, typ.1 µs
for fixed point arithmetic, typ.2 µs
for floating point arithmetic, typ.50 µs
for timer/counter operations, typ.12 µs
CPU-blocks
DB
Number, max.255; DB 0 reserved
FB
Number, max.192; see instruction list
FC
Number, max.192; see instruction list
OB
Number, max.see instruction list
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of cyclic interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of startup OBs1; OB 100
Number of asynchronous error OBs7; OB 80, 81, 82, 85, 87, 121, 122
Nesting depth
per priority class8
Counters, timers and their retentivity
S7 counter
Number64
Retentivity
— adjustableYes
— lower limit0
— upper limit63
Counting range
— lower limit0
— upper limit999
S7 times
Number128
Retentivity
— adjustableYes
— lower limit0
— upper limit127
Time range
— lower limit10 ms
— upper limit9 990 s
Data areas and their retentivity
Flag
Number, max.256 byte
Retentivity availableYes
of which retentive with battery0 to 2047
of which retentive without battery0 to 2047
Address area
I/O address area
Inputs1 kbyte
Outputs1 kbyte
Process image
Inputs128 byte
Outputs128 byte
Hardware configuration
connectable programming devices/PCsSIMATIC PG/PC, standard PC
Number of modules per system, max.8
Number of modules per DP slave interface, max.32; 122 byte address space per DP station
Interface modules
Interface module IM 360 integratedYes
Number of DP masters
via CP1; CP 342-5
Number of operable FMs and CPs (recommended)
FM8
CP, PtP4
CP, LAN2
Expansion modules
Analog inputs/outputs, max.192
Digital inputs/outputs, max.768
Number of expansion modules, max.24
Rack
Number of lines, max.3
Time of day
Clock
Hardware clock (real-time)Yes
Digital inputs
Number of digital inputs16
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+11 to +30V
Input current
for signal "1", typ.11.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.4.8 ms; typically 3 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs16
Short-circuit protectionYes; Clocked electronically
Limitation of inductive shutdown voltage to48 V
Switching capacity of the outputs
on lamp load, max.5 W
Output voltage
for signal "1", min.L+ (-0.8 V)
Output current
for signal "1" rated value0.5 A
for signal "1" minimum load current5 mA
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.5 Hz
Total current of the outputs (per group)
all mounting positions
— up to 20 °C, max.4 A
— up to 40 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Universal inputs
Number of universal inputs4
usable asUI4: Digital/alarm input 24 V DC; UI1, UI2: additional up/down counter; UI3: additional frequency/period duration counter
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+11 to +30V
Input current
for signal "1"typ. 11.5 mA
Cable length
shielded, max.1 000 m
Analog inputs
Number of analog inputs4
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.30 mA
Cycle time (all channels), typ.2 ms
Input ranges
VoltageYes
CurrentYes
Input ranges (rated values), voltages
-10 V to +10 VYes
Input resistance (-10 V to +10 V)50 kΩ
Input ranges (rated values), currents
-20 mA to +20 mAYes
Input resistance (-20 mA to +20 mA)105.5 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)105.5 kΩ
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.25 mA
Current output, no-load voltage, max.16 V; ±
Cycle time (all channels) max.4 ms; typ. 2 ms
Output ranges, voltage
-10 V to +10 VYes
Output ranges, current
-20 mA to +20 mAYes
4 mA to 20 mAYes
Load impedance (in rated range of output)
with voltage outputs, min.2 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.0.5 kΩ
with current outputs, inductive load, max.1 mH
Cable length
shielded, max.200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)0.5 ms
Settling time
for resistive load0.1 ms
for capacitive load3.3 ms
for inductive load0.5 ms
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.2 mA
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.8 %
Current, relative to input range, (+/-)0.8 %
Voltage, relative to output range, (+/-)0.8 %
Current, relative to output range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.6 %
Current, relative to input range, (+/-)0.6 %
Voltage, relative to output range, (+/-)0.5 %
Current, relative to output range, (+/-)0.6 %
Interfaces
Number of printer interfaces1; RS 232
MPI
Cable length, max.9 100 m; without repeaters 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with star hubs or OLMs)
1. Interface
Protocols
MPIYes; occupies 2 nodes per device (1 x CPU, 1 x OP)
MPI
Number of nodes, max.32; PG/PC, OP, C7, S7-300/400, M7
Transmission rate, max.187.5 kbit/s
Communication functions
S7 communication
S7 extended communicationYes; Server
S5 compatible communication
supportedYes
Standard communication (FMS)
supportedYes
Number of connections
overall
— of which dynamic8
— of which static4
Interrupts/diagnostics/status information
Diagnostics functionYes; C7-CPU
Substitute values connectableYes; Parameterizable
Alarms
Alarm cycleYes; Parameterizable
Diagnostic alarmYes; Measurement overrange, wire break detection at 4 to 20 mA by means of software; parameterizable for parameter errors
Counter
Number of counter inputs3; UE1, UE2, UE3
PrincipleCounting of edges
Counting range, descriptionUI1, UI2: up: 0 to 65535, down: 65535 to 0; UI3: up: 0 to 16777215, down: 16777215 to 0
Counter frequency, max.10 kHz
Counting alarm backward counteron reaching "0"
Counting alarm forward counteron reaching limit value
EnableIn the program
Limit value (setpoint) defaultone counter per value
External gate counters
Number of external gate counters3
PrincipleCounting of edges within a gate time via external pin
Counting rangeUE1, UE2: 0 to 65535; UE3: 0 to 16777215
Frequency counter
Number1; UI3
PrincipleCounting of pulses within a time period
Gate width, adjustableYes
Gate width0.1 / 1 / 10 s
Counting range0 to 16777215
Cycle duration counter
Number1; UI3
Cycle duration, max.8.38 s; or 0.12 Hz
PrincipleCounting of fixed time units between two positive edges
Counting range, lower limit0
Counting range, upper limit16 777 214
Potential separation
Potential separation digital inputs
Potential separation digital inputsYes; Optocoupler
between the channels, in groups of16
Potential separation digital outputs
Potential separation digital outputsYes; Optocoupler
between the channels, in groups of2
Potential separation analog inputs
Potential separation analog inputsYes; shared with AO
Potential separation analog outputs
Potential separation analog outputsYes; Shared with IO
Potential separation channels
Potential separation universal inputsNo
Isolation
Isolation tested with500 V DC
EMC
EMC interference immunityNoise immunity: IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-6, EN 50140
Emission of radio interference acc. to EN 55 022
Interference emission acc. to EN 55022, class AYes; Noise emission: Class A / EN 55022; conducted interference: IEC 1000-4-4, IEC 1000-4-5
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes; Housing
IP65Yes; Front
Standards, approvals, certificates
CSA approvalYes; to Standard C22.2 number 142
UL approvalYes; UL 508
FM approvalYes; FM-Standards No. 3611, 3600, 3810 Class I, Division 2, Group A, B, C, D
developed in accordance with IEC 61131Yes; EN 61131-2 (IEC 1131-2)
DIN/ISO 9001Yes
Ambient conditions
Ambient temperature during operation
45 degree installation, min.0 °C
45 degree installation, max.45 °C
vertical installation, min.0 °C
vertical installation, max.50 °C
Air pressure acc. to IEC 60068-2-13
permissible range, lower limit795 hPa
permissible range, upper limit1 080 hPa
Relative humidity
Operation, min.5 %
Operation, max.95 %; at 25 °C (no condensation), tested to DIN IEC 60068-2-3
Vibrations
Operation, tested according to IEC 60068-2-6Yes; IEC 60068-2-6; 10 Hz to 58 Hz; (constant amplitude 0.075 mm); 58 Hz to 500 Hz; (constant acceleration 9.8 m/s²)
Shock testing
tested according to IEC 60068-2-29Yes; IEC 68, Part 2-29 half-sine: 100 m/s² (10 g), 16 ms, 100 shocks
Configuration
Configuration software
STEP 7Yes
STEP 7 LiteYes
ProToolYes
ProTool/LiteYes
ProTool/ProYes
Programming
Command setsee instruction list
Nesting levels8
Program organizationLinear, structured
System functions (SFC)see instruction list
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Software libraries
— Process diagnosticsYes; C7-CPU
— Software controllerYes; 16 circles
Know-how protection
User program protection/password protectionYes
Cycle time monitoring
lower limit1 ms
upper limit6 000 ms
adjustableYes
preset150 ms
Languages
Online languages
Number of online/runtime languages3
Dimensions
Width240 mm
Height168 mm
Depth89.4 mm
Mounting cutout, width231 mm
Mounting cutout, height159 mm
Weights
Weight, approx.1 900 g
last modified:03/13/2019