6ES7322-5RD00-0AB0
SM322, 4DO, 15V DC,20MA, HAZARDOUS AREAS

From SIEMENS

SIMATIC S7, digital output SM 322, isolated, 4 DO, 15 V / 20 mA 1 x 20-pole, for signals from the hazardous area, diagnostics-capable, PTB tested
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.160 mA
from backplane bus 5 V DC, max.85 mA
Power loss
Power loss, typ.3 W
Digital outputs
Number of digital outputs4
Short-circuit protectionYes; Electronic
Response threshold, typ.Output current with short-circuit protection, min. 20.5 mA + 10 %
Load resistance range
upper limit200 Ω; Two-wire connection
Output voltage
Rated value (DC)15 V
Output current
for signal "1" permissible range for 0 to 60 °C, max.20 mA; ±10 %
Switching frequency
with resistive load, max.100 Hz
Cable length
unshielded, max.200 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnostic messages
Diagnostic information readableYes
Short-circuitYes
Diagnostics indication LED
Group error SF (red)Yes
Status indicator digital output (green)Yes
Channel fault indicator F (red)Yes
Ex(i) characteristics
Module for Ex(i) protectionYes
Maximum values of output circuits (per channel)
Co (permissible external capacity), max.500 nF
Io (short-circuit current), max.85 mA
Lo (permissible external inductivity), max.5 mH
Po (power of load), max.335 mW
Uo (output no-load voltage), max.15.75 V
Potential separation
Potential separation digital outputs
Potential separation digital outputsYes
between the channels, in groups of1
Standards, approvals, certificates
Use in hazardous areas
Type of protection acc. to EN 50020 (CENELEC)[EEx ib] IIC
Type of protection acc. to FMAIS CL.1, DIV 1, GP A, B, C, D; CL.I, DIV 2, GP A, B, C, D T4
Test number PTBEx-96.D.2102X
Ambient conditions
Ambient temperature during operation
max.60 °C
Connection method
required front connector20-pin
Weights
Weight, approx.230 g
last modified:03/13/2019