| ***Spare part*** SIMATIC S7-300, CPU 317T-2 DP, Central processing unit for PLC and Technology tasks, 1024 KB work memory, 1st interface MPI/DP 12 Mbit/s, 2nd interface DP (drive), Integr. I/O for technology Front connector (1x 40-pole) and Micro Memory Card min. 8 MB required |
General information |
HW functional status | 01 |
Firmware version | CPU: V2.7, integrated technology: V4.1.5 |
Engineering with |
Programming package | STEP 7 V5.4 + SP5 (and higher) and Optional package S7-Technology V4.2 |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | 2 A min. |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Digital outputs |
— Rated value (DC) | 24 V; (2L+) |
— Reverse polarity protection | No; (2L+) |
Input current |
Current consumption (in no-load operation), typ. | 200 mA |
Inrush current, typ. | 2.5 A |
I²t | 1 A²·s |
Power loss |
Power loss, typ. | 6 W |
Memory |
Work memory |
integrated | 1 024 kbyte |
expandable | No |
Load memory |
Plug-in (MMC) | Yes |
Plug-in (MMC), max. | 8 Mbyte |
Data management on MMC (after last programming), min. | 10 y |
Backup |
present | Yes; Guaranteed by MMC (maintenance-free) |
without battery | Yes; Program and data |
CPU processing times |
for bit operations, typ. | 0.05 µs |
for bit operations, max. | 0.05 µs |
for word operations, typ. | 0.2 µs |
for fixed point arithmetic, typ. | 0.2 µs |
for floating point arithmetic, typ. | 1 µs |
CPU-blocks |
Number of blocks (total) | 2 048; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
Number, max. | 2 047; Number band: 1 to 2047 |
Size, max. | 64 kbyte |
FB |
Number, max. | 2 048; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
FC |
Number, max. | 2 048; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
OB |
Description | see instruction list |
Size, max. | 64 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of delay alarm OBs | 2; OB 20, 21 |
Number of cyclic interrupt OBs | 4; OB 32, 33, 34, 35 |
Number of process alarm OBs | 1; OB 40 |
Number of DPV1 alarm OBs | 3; OB 55, 56, 57 |
Number of isochronous mode OBs | 1; OB 61 |
Number of technology synchronous alarm OBs | 1; OB 65 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 5; OB 80, 82, 85, 86, 87 |
Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth |
per priority class | 16 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 512; Number range: 0 to 511 |
Retentivity |
— adjustable | Yes |
— preset | 8 |
Counting range |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 512; Number range: 0 to 511 |
Retentivity |
— adjustable | Yes |
— preset | No retentivity |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
retentive data area in total | All DBs, max. 256 KB |
Flag |
Number, max. | 4 096 byte |
Retentivity available | Yes; From MB 0 to MB 4 095 |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; 1 memory byte |
Data blocks |
Retentivity adjustable | Yes; via non-retain property on DB |
Retentivity preset | Yes |
Local data |
per priority class, max. | 1 024 byte |
Address area |
I/O address area |
Inputs | 8 192 byte |
Outputs | 8 192 byte |
of which distributed |
— Inputs | 8 192 byte |
— Outputs | 8 192 byte |
Process image |
Inputs, adjustable | 2 048 byte |
Outputs, adjustable | 2 048 byte |
Inputs, default | 256 byte |
Outputs, default | 256 byte |
Default addresses of the integrated channels |
— Digital inputs | 66 |
— Digital outputs | 66 |
Subprocess images |
Number of subprocess images, max. | 1 |
Digital channels |
Inputs | 65 536 |
— of which central | 512 |
Outputs | 65 536 |
— of which central | 512 |
Analog channels |
Inputs | 4 096 |
— of which central | 64 |
Outputs | 4 096 |
— of which central | 64 |
Hardware configuration |
Number of expansion units, max. | 0 |
Number of DP masters |
integrated | 2; 1 DP and 1 DP (drive) |
via CP | 2; for DP |
Number of operable FMs and CPs (recommended) |
FM | 8 |
CP, PtP | 8 |
CP, LAN | 10 |
Rack |
Racks, max. | 1 |
Modules per rack, max. | 8 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Backup time | 6 wk; At 40 °C ambient temperature |
Deviation per day, max. | 10 s |
Operating hours counter |
Number | 4 |
Number/Number range | 0 to 3 |
Range of values | 0 to 2^31 hours (when using SFC 101) |
Granularity | 1 h |
retentive | Yes; Must be restarted at each restart |
Clock synchronization |
supported | Yes |
to MPI, master | Yes |
to MPI, slave | Yes |
to DP, master | Yes |
to DP, slave | Yes |
in AS, master | Yes |
in AS, slave | Yes |
Digital inputs |
Number of digital inputs | 4 |
of which inputs usable for technological functions | 4 |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Number of simultaneously controllable inputs |
horizontal installation |
— up to 40 °C, max. | 4 |
— up to 60 °C, max. | 4 |
vertical installation |
— up to 40 °C, max. | 4 |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -3 to +5V |
for signal "1" | +15 to +30V |
Input current |
for signal "1", typ. | 7 mA |
Input delay (for rated value of input voltage) |
for technological functions |
— at "0" to "1", max. | 10 µs; Typical |
— at "1" to "0", max. | 10 µs; Typical |
Cable length |
shielded, max. | 1 000 m |
Digital outputs |
Number of digital outputs | 8 |
of which high-speed outputs | 8 |
Functions | For technology functions, e.g. high-speed cam switch signals |
Short-circuit protection | Yes |
Response threshold, typ. | 1 A |
Limitation of inductive shutdown voltage to | 48 V |
Controlling a digital input | No |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 4 kΩ |
Output voltage |
for signal "0", max. | 3 V; (2L+) |
for signal "1", min. | Rated voltage -2.5 V |
Output current |
for signal "1" rated value | 0.5 A |
for signal "1" permissible range for 0 to 60 °C, min. | 5 mA |
for signal "1" permissible range for 0 to 60 °C, max. | 0.6 A |
for signal "0" residual current, max. | 0.3 mA |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 0.2 Hz; According to IEC 60947-5-1, DC-13 |
on lamp load, max. | 100 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. | 4 A |
— up to 60 °C, max. | 3 A |
all other mounting positions |
— up to 40 °C, max. | 3 A |
Cable length |
shielded, max. | 1 000 m |
Analog inputs |
Number of analog inputs | 0 |
Analog outputs |
Number of analog outputs | 0 |
Encoder |
Connectable encoders |
2-wire sensor | No |
Interfaces |
Number of industrial Ethernet interfaces | 0 |
Number of PROFINET interfaces | 0 |
Number of RS 485 interfaces | 2 |
Number of RS 422 interfaces | 0 |
1. Interface |
Interface type | Integrated RS 485 interface |
Physics | RS 485 |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | 200 mA |
Protocols |
MPI | Yes |
PROFIBUS DP master | Yes |
PROFIBUS DP slave | Yes |
Point-to-point connection | No |
MPI |
Number of connections | 32 |
Transmission rate, max. | 12 Mbit/s |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
— S7 communication, as client | No; but via CP and loadable FB |
— S7 communication, as server | Yes; Connection configured on one side only |
PROFIBUS DP master |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 124 |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | Yes; I blocks only |
— S7 communication | Yes |
— S7 communication, as client | No; but via CP and loadable FB |
— S7 communication, as server | Yes; Connection configured on one side only |
— Equidistance | Yes |
— Isochronous mode | Yes; OB 61 |
— SYNC/FREEZE | Yes |
— Activation/deactivation of DP slaves | Yes |
— DPV1 | Yes |
Address area |
— Inputs, max. | 8 192 byte |
— Outputs, max. | 8 192 byte |
User data per DP slave |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
PROFIBUS DP slave |
Transmission rate, max. | 12 Mbit/s |
automatic baud rate search | No |
Address area, max. | 32 |
User data per address area, max. | 32 byte |
Services |
— PG/OP communication | Yes |
— Routing | Yes; Only with active interface |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | Yes |
— S7 communication, as client | No; but via CP and loadable FB |
— S7 communication, as server | Yes; Connection configured on one side only |
— Direct data exchange (slave-to-slave communication) | Yes |
— DPV1 | No |
Transfer memory |
— Inputs | 244 byte |
— Outputs | 244 byte |
2. Interface |
Interface type | Integrated RS 485 interface |
Physics | RS 485 |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | 200 mA |
Protocols |
MPI | No |
PROFIBUS DP master | Yes; DP(DRIVE)-Master |
PROFIBUS DP slave | No |
Point-to-point connection | No |
PROFIBUS DP master |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 64 |
Services |
— PG/OP communication | No |
— Routing | No |
— Global data communication | No |
— S7 basic communication | No |
— S7 communication | No |
— Equidistance | Yes |
— Isochronous mode | Yes |
— SYNC/FREEZE | No |
— Activation/deactivation of DP slaves | Yes |
— DPV1 | No |
Address area |
— Inputs, max. | 1 024 byte |
— Outputs, max. | 1 024 byte |
User data per DP slave |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
PROFIBUS DP slave |
GSD file | |
Transmission rate, max. | 12 Mbit/s |
Communication functions |
PG/OP communication | Yes |
Global data communication |
supported | Yes |
Number of GD loops, max. | 8 |
Number of GD packets, max. | 8 |
Number of GD packets, transmitter, max. | 8 |
Number of GD packets, receiver, max. | 8 |
Size of GD packets, max. | 22 byte |
Size of GD packet (of which consistent), max. | 22 byte |
S7 basic communication |
supported | Yes |
User data per job, max. | 76 byte |
User data per job (of which consistent), max. | 76 byte; 76 bytes (with X_SEND or X_RCV), 76 bytes (with X_PUT or X_GET as server) |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes; Via CP and loadable FB |
User data per job, max. | See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication) |
S5 compatible communication |
supported | Yes; via CP and loadable FC |
Number of connections |
overall | 32 |
usable for PG communication | 31 |
— reserved for PG communication | 1 |
— adjustable for PG communication, min. | 1 |
— adjustable for PG communication, max. | 31 |
usable for OP communication | 31 |
— reserved for OP communication | 1 |
— adjustable for OP communication, min. | 1 |
— adjustable for OP communication, max. | 31 |
usable for S7 basic communication | 30 |
— reserved for S7 basic communication | 0 |
— adjustable for S7 basic communication, min. | 0 |
— adjustable for S7 basic communication, max. | 30 |
usable for routing | 8; additional |
S7 message functions |
Number of login stations for message functions, max. | 32; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes |
simultaneously active Alarm-S blocks, max. | 60 |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 2 |
Status/control |
Status/control variable | Yes |
Variables | Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. | 30 |
— of which status variables, max. | 30 |
— of which control variables, max. | 14 |
Forcing |
Forcing | Yes |
Forcing, variables | Inputs, outputs |
Number of variables, max. | 10 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 100 |
— adjustable | No |
Interrupts/diagnostics/status information |
Alarms | No |
Diagnostics function | No |
Diagnostics indication LED |
Status indicator digital input (green) | Yes |
Status indicator digital output (green) | Yes |
Potential separation |
Potential separation digital inputs |
between the channels and backplane bus | Yes |
Potential separation digital outputs |
between the channels and backplane bus | Yes |
Permissible potential difference |
between different circuits | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C |
max. | 60 °C |
Configuration |
Configuration software |
STEP 7 | Yes |
Programming |
Command set | see instruction list |
Nesting levels | 8 |
System functions (SFC) | see instruction list |
System function blocks (SFB) | see instruction list |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— CFC | Yes |
— GRAPH | Yes |
— HiGraph® | Yes |
Know-how protection |
User program protection/password protection | Yes |
Cycle time monitoring |
lower limit | 1 ms |
upper limit | 6 000 ms |
adjustable | Yes |
preset | 150 ms |
Dimensions |
Width | 160 mm |
Height | 125 mm |
Depth | 130 mm |
Weights |
Weight, approx. | 750 g |