6ES7317-6TJ10-0AB0
SIMATIC S7-300, CPU 317T-2 DP,

From SIEMENS

SIMATIC S7-300, CPU 317T-2 DP, CENTRAL PROCESSING UNIT FOR PLC AND TECHNOLOGY 512 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S 2. INTERFACE DP(DRIVE), INTEGRATED I/O FOR TECHNOLOGY FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD MIN. 4MB NECESSARY
General information
HW functional status02
Firmware versionCPU: V2.1.0, integrated technology: V3.0.1
Engineering with
Programming packageSTEP 7 V 5.2 SP1 or higher with HF1 and S7-Technology option package
Supply voltage
Rated value (DC)
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
external protection for power supply lines (recommendation)2 A min.
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionNo
Input current
Current consumption (in no-load operation), typ.200 mA
Inrush current, typ.2.5 A
I²t1 A²·s
Power loss
Power loss, typ.6 W
Memory
Work memory
integrated512 kbyte
expandableNo
Load memory
Plug-in (MMC)Yes; min. 4 MB required
Plug-in (MMC), max.8 Mbyte
Backup
presentYes; Guaranteed by MMC (maintenance-free)
Battery
Backup battery
Backup time, max.10 y; Data retention on the MMC (after last programming)
CPU processing times
for bit operations, typ.0.05 µs
for word operations, typ.0.2 µs
for fixed point arithmetic, typ.0.2 µs
for floating point arithmetic, typ.1 µs
CPU-blocks
DB
Number, max.2 047; DB 0 reserved
Size, max.64 kbyte
FB
Number, max.2 048; see instruction list
Size, max.64 kbyte
FC
Number, max.2 048; see instruction list
Size, max.64 kbyte
OB
Number, max.see instruction list
Size, max.64 kbyte
Nesting depth
per priority class16
additional within an error OB4
Counters, timers and their retentivity
S7 counter
Number512
Retentivity
— adjustableYes
— presetZ 0 to Z 7
Counting range
— adjustableYes
— lower limit0
— upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 times
Number512
Retentivity
— adjustableYes
— presetNo retentivity
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total2048 (DBs, FCs, FBs). The maximum number of loadable blocks can be reduced by the MMC that you use.
Flag
Number, max.4 096 byte
Retentivity availableYes; From MB 0 to MB 4 095
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Data blocks
Retentivity adjustableYes
Local data
per priority class, max.1 024 byte
Address area
I/O address area
Inputs8 kbyte
Outputs8 kbyte
of which distributed
— Inputs8 kbyte
— Outputs8 kbyte
Process image
Inputs256 byte
Outputs256 byte
Digital channels
Inputs65 636
— of which central256
Outputs65 636
— of which central256
Analog channels
Inputs4 096
— of which central64
Outputs4 096
— of which central64
Hardware configuration
Number of DP masters
integrated2
via CP2
Number of operable FMs and CPs (recommended)
FM8
CP, PtP8
CP, LAN10
Rack
Racks, max.1
Modules per rack, max.8
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Backup time6 wk; At 40 °C ambient temperature
Deviation per day, max.10 s
Operating hours counter
Number4
Number/Number range0 to 3
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 h
retentiveYes; Must be restarted at each restart
Clock synchronization
supportedYes
to MPI, masterYes
to MPI, slaveYes
in AS, masterYes
in AS, slaveYes
Digital inputs
Number of digital inputs4
Functionstechnological functions, e.g. reference point detection (BERO); digital inputs can also be used (with restrictions) in STEP 7 user program.
Input characteristic curve in accordance with IEC 61131, type 1Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.4
— up to 60 °C, max.4
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+15 to +30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for technological functions
— at "0" to "1", max.10 µs; Typical
— at "1" to "0", max.10 µs; Typical
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs8
FunctionsFor technology functions, e.g. high-speed cam switch signals
Short-circuit protectionYes
Response threshold, typ.1 A
Limitation of inductive shutdown voltage to2L+ (-48 V)
Controlling a digital inputNo
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit4 kΩ
Output voltage
for signal "0", max.3 V
for signal "1", min.2L+ (-2,5 V)
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range for 0 to 60 °C, min.5 mA
for signal "1" permissible range for 0 to 60 °C, max.0.6 A
for signal "0" residual current, max.0.3 mA
Parallel switching of two outputs
for upratingNo
for redundant control of a loadNo
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.2 Hz; According to IEC 60947-5-1, DC-13
on lamp load, max.100 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.4 A
— up to 60 °C, max.3 mA
all other mounting positions
— up to 40 °C, max.3 mA
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorNo
1. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Protocols
MPIYes
PROFIBUS DP masterYes
PROFIBUS DP slaveYes
Point-to-point connectionNo
MPI
Transmission rate, max.12 Mbit/s
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationYes
— S7 basic communicationYes
— S7 communicationYes
— S7 communication, as clientYes; Via CP and loadable FB
— S7 communication, as serverYes
PROFIBUS DP master
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.124
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationNo
— EquidistanceYes
— SYNC/FREEZEYes
— DPV1Yes
Address area
— Inputs, max.244 kbyte
— Outputs, max.244 kbyte
PROFIBUS DP slave
Transmission rate, max.12 Mbit/s
automatic baud rate searchNo
Address area, max.32
User data per address area, max.32 byte
Services
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationNo
— Direct data exchange (slave-to-slave communication)Yes
— DPV1No
Transfer memory
— Inputs244 byte
— Outputs244 byte
2. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Protocols
MPINo
PROFIBUS DP masterYes; DP(DRIVE)-Master
PROFIBUS DP slaveNo
Point-to-point connectionNo
PROFIBUS DP master
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.32
Services
— PG/OP communicationNo
— RoutingNo
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationNo
— EquidistanceYes
— SYNC/FREEZENo
— Activation/deactivation of DP slavesNo
— DPV1No
Address area
— Inputs, max.244 kbyte
— Outputs, max.244 kbyte
Communication functions
PG/OP communicationYes
Global data communication
supportedYes
Number of GD loops, max.8
Number of GD packets, max.8
Number of GD packets, transmitter, max.8
Number of GD packets, receiver, max.8
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supportedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supportedYes
as serverYes
as clientYes; Via CP and loadable FB
User data per job, max.180 byte; With PUT/GET
User data per job (of which consistent), max.160 byte; as server
S5 compatible communication
supportedYes; via CP and loadable FC
Number of connections
overall32
usable for PG communication31
— reserved for PG communication1
— adjustable for PG communication, min.1
— adjustable for PG communication, max.31
usable for OP communication31
— reserved for OP communication1
— adjustable for OP communication, min.1
— adjustable for OP communication, max.31
usable for S7 basic communication30
— reserved for S7 basic communication0
— adjustable for S7 basic communication, min.0
— adjustable for S7 basic communication, max.30
S7 message functions
Number of login stations for message functions, max.32; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.60
Test commissioning functions
Status blockYes
Single stepYes
Number of breakpoints2
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.30
— of which status variables, max.30
— of which control variables, max.14
Forcing
ForcingYes
Forcing, variablesInputs, outputs
Number of variables, max.10
Diagnostic buffer
presentYes
Number of entries, max.100
— adjustableNo
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Potential separation
Potential separation digital inputs
between the channels and backplane busYes
Potential separation digital outputs
between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Configuration
Configuration software
STEP 7Yes; V5.2 SP1 or higher and S7 Technology option package
Programming
Command setsee instruction list
Nesting levels8
System functions (SFC)see instruction list
System function blocks (SFB)see instruction list
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Know-how protection
User program protection/password protectionYes
Dimensions
Width160 mm
Height125 mm
Depth130 mm
Weights
Weight, approx.750 g
last modified:03/13/2019