| ***Spare part*** SIMATIC S7-300, CPU 314 for extended. temperature range additional power supply 24V DC Work memory 24 KB |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Input current |
Current consumption (rated value) | 1 000 mA |
Inrush current, typ. | 8 A |
Power loss |
Power loss, typ. | 8 W |
Memory |
Work memory |
integrated | 24 kbyte; 24 KB/8 K instructions RAM (integrated); 1 instruction means 3 bytes on average |
Load memory |
expandable FEPROM | Yes; Flash-EPROM |
expandable FEPROM, max. | 4 Mbyte |
integrated RAM, max. | 40 kbyte |
Backup |
present | Yes |
with battery | Yes; all blocks |
without battery | Yes; 4 KB: bit memory, counter, times and data |
CPU processing times |
for bit operations, typ. | 0.3 µs |
for bit operations, max. | 0.6 µs |
for word operations, typ. | 1 µs |
for fixed point arithmetic, typ. | 2 µs |
for floating point arithmetic, typ. | 50 µs |
for timer/counter operations, typ. | 12 µs |
CPU-blocks |
DB |
Number, max. | 127 |
Size, max. | 8 kbyte |
FB |
Number, max. | 128 |
Size, max. | 8 kbyte |
FC |
Number, max. | 128 |
Size, max. | 8 kbyte |
OB |
Description | see instruction list |
Size, max. | 8 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of cyclic interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of startup OBs | 1; OB 100 |
Nesting depth |
per priority class | 8 |
Counters, timers and their retentivity |
S7 counter |
Number | 64 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 63 |
Counting range |
— lower limit | 1 |
— upper limit | 999 |
S7 times |
Number | 128 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 127 |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
Data areas and their retentivity |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes; MB 0 to MB 255 |
of which retentive with battery | 0 to 2 047 (M 0.0 to M 255.7, adjustable) |
of which retentive without battery | 0 to 2 047 (M 0.0 to M 255.7, adjustable) |
Address area |
I/O address area |
Inputs | 512 byte |
Outputs | 512 byte |
Process image |
Inputs | 128 byte |
Outputs | 128 byte |
Digital channels |
Inputs | 1 024 |
Outputs | 1 024 |
Analog channels |
Inputs | 256 |
Outputs | 128 |
Addressing volume |
Inputs | 122 byte |
Outputs | 122 byte |
Hardware configuration |
Number of expansion units, max. | 3 |
connectable programming devices/PCs | PGs/PCs with STEP 7 connectable via MPI interface |
Number of modules per DP slave interface, max. | 16 |
Number of DP masters |
integrated | 0 |
via CP | 1; CP 342-5 |
Number of operable FMs and CPs (recommended) |
FM | 4 |
CP, PtP | 2 |
CP, LAN | 1 |
Rack |
Modules per rack, max. | 32 |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
Interfaces |
MPI |
Cable length, max. | 9 100 m; without repeaters: 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with 16 star hubs or OLMs) |
1. Interface |
Protocols |
MPI | Yes |
MPI |
Number of nodes, max. | 32; 32 nodes on MPI bus; PG/PC, OP, additional S7-300/400, C7; per CPU max. 4 static and 4 dynamic connections |
Transmission rate, max. | 187.5 kbit/s |
Services |
— PG/OP communication | Yes |
— Global data communication | Yes |
— S7 basic communication | Yes |
— S7 communication | Yes |
Communication functions |
PG/OP communication | Yes |
Global data communication |
supported | Yes |
S7 basic communication |
supported | Yes |
S7 communication |
supported | Yes |
as server | Yes |
S5 compatible communication |
supported | Yes; via loadable blocks |
Standard communication (FMS) |
supported | Yes; via loadable blocks |
Number of connections |
overall | |
— of which dynamic | 8 |
— of which static | 4 |
Configuration |
Configuration software |
STEP 7 | Yes; V5.0, V5.0 SP1 |
Programming |
Command set | Binary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions |
Nesting levels | 8 |
Program organization | Linear, structured |
System functions (SFC) | Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions |
System function blocks (SFB) | 1 |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes |
— GRAPH | Yes |
Software libraries |
— Process diagnostics | Yes |
— Software controller | Yes; depending on the required memory space and the resulting execution time |
Know-how protection |
User program protection/password protection | Yes |
Cycle time monitoring |
lower limit | 1 ms |
upper limit | 6 000 ms |
adjustable | Yes |
preset | 150 ms |
Dimensions |
Width | 80 mm |
Height | 125 mm |
Depth | 130 mm |
Weights |
Weight, approx. | 530 g; Memory card 16 g |