| SIMATIC S7-200, Analog input EM 231, only for S7-22X CPU, 8 AI, 0-10V DC, max 2 AI 0..20 mA 12/11-bit converter |
Input current |
from load voltage L+ (without load), max. | 60 mA |
from backplane bus 5 V DC, max. | 20 mA |
Power loss |
Power loss, typ. | 2 W |
Analog inputs |
Number of analog inputs | 8; Difference |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
permissible input current for current input (destruction limit), max. | 40 mA |
Input ranges |
Voltage | Yes |
Current | Yes; for channels 6 and 7 only |
Thermocouple | No |
Resistance thermometer | No |
Resistance | No |
Input ranges (rated values), voltages |
0 to +5 V | Yes |
Input resistance (0 to 5 V) | 10 MΩ |
0 to +10 V | Yes |
Input resistance (0 to 10 V) | 10 MΩ |
-2.5 V to +2.5 V | Yes |
Input resistance (-2.5 V to +2.5 V) | 10 MΩ |
-5 V to +5 V | Yes |
Input resistance (-5 V to +5 V) | 10 MΩ |
-80 mV to +80 mV | No |
Input ranges (rated values), currents |
0 to 20 mA | Yes; for channels 6 and 7 only |
Input resistance (0 to 20 mA) | 10 MΩ |
Input ranges (rated values), thermocouples |
Type E | No |
Type J | No |
Type K | No |
Type N | No |
Type R | No |
Type S | No |
Type T | No |
Input ranges (rated values), resistance thermometer |
Cu 10 | No |
Ni 10 | No |
Ni 1000 | No |
Ni 120 | No |
Pt 100 | No |
Pt 1000 | No |
Pt 10000 | No |
Pt 200 | No |
Pt 500 | No |
Input ranges (rated values), resistors |
0 to 150 ohms | No |
0 to 300 ohms | No |
0 to 600 ohms | No |
Thermocouple (TC) |
Temperature compensation |
— parameterizable | No |
Cable length |
shielded, max. | 100 m; to the sensor |
Analog value generation for the inputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit |
Interference voltage suppression for interference frequency f1 in Hz | 40 dB, DC up to 60 V for interference frequency |
Conversion time (per channel) | 250 µs |
Displayable conversion value range |
bipolar signals | -32 000 to +32 000 |
unipolar signals | 0 to 32 000 |
Errors/accuracies |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Common mode voltage, max. | 12 V |
Interrupts/diagnostics/status information |
Diagnostics indication LED |
external fault EXTF (red) | Yes |
Potential separation |
Potential separation analog inputs |
Potential separation analog inputs | No |
Connection method |
Plug-in I/O terminals | No |
Dimensions |
Width | 71.2 mm |
Height | 80 mm |
Depth | 62 mm |
Weights |
Weight, approx. | 190 g |
last modified: | 03/13/2019 |