6ES7216-2AD23-0XB0
CPU 226, DC PS, 24DI DC/16DO DC

From SIEMENS

***Spare part*** SIMATIC S7-200, CPU 226 Compact unit, DC power supply 24 DI DC/16 DO DC, 16/24 KB progr./10 KB data, 2 PPI/user-programmable interface
Supply voltage
Rated value (DC)
24 V DCYes
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Input current
Inrush current, max.10 A; at 28.8 V
from supply voltage L+, max.1 050 mA; 150 mA to 1 050 mA output current for expansion modules (5 V DC) 1 000 mA
Encoder supply
24 V encoder supply
24 VYes; permissible range: 15.4 to 28.8 V
Short-circuit protectionYes; electronic at 400 mA
Output current, max.400 mA
Power loss
Power loss, typ.11 W
Memory
Number of memory modules (optional)1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files
Work memory
integrated (for program)24 kbyte; 16 KB with active run-time edit
integrated (for data)10 kbyte
Backup
presentYes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering
Battery
Backup battery
Backup time, max.100 h; (min. 70 h at 40 °C); 200 days (typ.) with optional battery module
CPU processing times
for bit operations, max.0.22 µs
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
— adjustableYes; via high-performance capacitor or battery
— lower limit1
— upper limit256
Counting range
— lower limit0
— upper limit32 767
S7 times
Number256
Retentivity
— adjustableYes; via high-performance capacitor or battery
— upper limit64
Time range
— lower limit1 ms
— upper limit54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min
Data areas and their retentivity
Flag
Number, max.32 byte
Retentivity availableYes; M 0.0 to M 31.7
of which retentive with battery0 to 255, via high-performance capacitor or battery, adjustable
of which retentive without battery0 to 112 in EEPROM, adjustable
Hardware configuration
Number of expansion units, max.7; Only expansion modules of the S7-22x series can be used. Due to the limited output current, the use of expansion modules may be limited.
connectable programming devices/PCsSIMATIC PG/PC, standard PC
Expansion modules
Analog inputs/outputs, max.35; max. 28 inputs and 7 outputs (EM) or max. 0 inputs and 14 outputs (EM)
Digital inputs/outputs, max.148; max. 128 inputs and 120 outputs (CPU+EM)
AS-Interface inputs/outputs, max.62; AS-Interface A/B slaves (CP 243-2)
Digital inputs
Number of digital inputs24
Source/sink inputYes; optionally, per group
Input voltage
Rated value (DC)24 V
for signal "0"0 to 5 V
for signal "1"min. 15 V
Input current
for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; all
— at "0" to "1", min.0.2 ms
— at "0" to "1", max.12.8 ms
for interrupt inputs
— parameterizableYes; I 0.0 to I 0.3
for technological functions
— parameterizableYes; (E 0.0 to E 1.5) 30 kHz
Cable length
shielded, max.500 m; Standard input: 500 m, high-speed counters: 50 m
unshielded, max.300 m; not for high-speed signals
Digital outputs
Number of digital outputs16; Transistor
Short-circuit protectionNo; to be provided externally
Limitation of inductive shutdown voltage to1 W
Switching capacity of the outputs
with resistive load, max.0.75 A
on lamp load, max.5 W
Output voltage
for signal "1", min.20 V DC
Output current
for signal "1" rated value750 mA
for signal "0" residual current, max.10 µA
Output delay with resistive load
"0" to "1", max.15 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 2 µs; of the pulse outputs, max. (Q 0.0 to Q 0.1) 2 µs
"1" to "0", max.130 µs; of the standard outputs, max. (Q 0.2 to Q 1.1) 10 µs; of the pulse outputs, max. (Q 0.0 to Q 0.1) 10 µs
Parallel switching of two outputs
for upratingYes
Switching frequency
of the pulse outputs, with resistive load, max.20 kHz; Q0.0 to Q0.1
Total current of the outputs (per group)
all mounting positions
— up to 40 °C, max.6 A
horizontal installation
— up to 55 °C, max.6 A
Relay outputs
Number of relay outputs0
Number of relay outputs, integrated0
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog inputs
Number of analog potentiometers2; Analog potentiometer; resolution 8 bit
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1 mA
1. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
Protocols
MPIYes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s
PPIYes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s
serial data exchangeYes; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter
MPI
Transmission rate, min.19.2 kbit/s
Transmission rate, max.187.5 kbit/s
2. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
Protocols
MPIYes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s
PPIYes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s
serial data exchangeYes; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter
Integrated Functions
Number of counters6; High-speed counters (30 kHz each), 32 bit (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc.
Counting frequency (counter) max.30 kHz
Number of alarm inputs4; 4 rising edges and/or 4 falling edges
Number of pulse outputs2; High-speed outputs, 20 kHz, with interrupt option; pulse-width and frequency modulation option
Limit frequency (pulse)20 kHz
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of13 and 11
Potential separation digital outputs
between the channelsYes; Optocoupler
between the channels, in groups of8 and 8
Permissible potential difference
between different circuits500 V DC between 24 V DC and 5 V DC
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
Air pressure acc. to IEC 60068-2-13
permissible range, lower limit860 hPa
permissible range, upper limit1 080 hPa
Relative humidity
Operation, min.5 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Configuration
Programming
Command setBit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions
Program processingfree cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms)
Program organization1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer
Number of subroutines, max.64
Programming language
— LADYes
— FBDYes
— STLYes
Know-how protection
User program protection/password protectionYes; 3-stage password protection
Connection method
Plug-in I/O terminalsYes
Dimensions
Width196 mm
Height80 mm
Depth62 mm
Weights
Weight, approx.550 g
last modified:03/13/2019

External links