6ES7211-0BA23-0XB0
CPU 221, AC PS, 6DI DC/4DO Relay

From SIEMENS

SIMATIC S7-200, CPU 221 Compact unit, AC power supply 6 DI DC/4 DO Relay outputs, 4 KB progr./2 KB data
Supply voltage
Rated value (AC)
120 V ACYes
230 V ACYes
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)5 V
permissible range, upper limit (DC)30 V
Load voltage L1
Rated value (AC)100 V; 100 V AC to 230 V AC
permissible range, lower limit (AC)5 V
permissible range, upper limit (AC)250 V
permissible frequency range, lower limit47 Hz
permissible frequency range, upper limit63 Hz
Input current
Inrush current, max.20 A; at 264 V
from supply voltage L1, max.120 mA; 15 to 60 mA (240 V); 30 to 120 mA (120 V); output current for expansion modules (5 V DC) 340 mA
Encoder supply
24 V encoder supply
24 VYes; Permissible range: 20.4V to 28.8V
Short-circuit protectionYes; electronic at 600 mA
Output current, max.180 mA
Power loss
Power loss, typ.6 W
Memory
Number of memory modules (optional)1; pluggable memory module, content identical with integral EEPROM; can additionally store recipes, data logs and other files
Work memory
integrated (for program)4 kbyte
integrated (for data)2 kbyte
Backup
presentYes; Program: Entire program maintenance-free on integral EEPROM, programmable via CPU; data: Entire DB 1 loaded from PG/PC maintenance-free on integral EEPROM, current values of DB 1 in RAM, retentive memory bits, timers, counters, etc. maintenance-free via high-performance capacitor; optional battery for long-term buffering
Battery
Backup battery
Backup time, max.50 h; (min. 8 h at 40 °C); 200 days (typ.) with optional battery module
CPU processing times
for bit operations, max.0.22 µs
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
— adjustableYes; via high-performance capacitor or battery
— lower limit1
— upper limit256
Counting range
— lower limit0
— upper limit32 767
S7 times
Number256
Retentivity
— adjustableYes; via high-performance capacitor or battery
— upper limit64
Time range
— lower limit1 ms
— upper limit54 min; 4 timers: 1 ms to 30 s; 16 timers: 10 ms to 5 min; 236 timers: 100 ms to 54 min
Data areas and their retentivity
Flag
Number, max.32 byte
Retentivity availableYes; M 0.0 to M 31.7
of which retentive with battery0 to 255, via high-performance capacitor or battery, adjustable
of which retentive without battery0 to 112 in EEPROM, adjustable
Hardware configuration
connectable programming devices/PCsSIMATIC PG/PC, standard PC
Digital inputs
Number of digital inputs6; Integrated
Source/sink inputYes; optionally, per group
Input voltage
Rated value (DC)24 V
for signal "0"0 to 5 V
for signal "1"min. 15 V
Input current
for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; all
— at "0" to "1", min.0.2 ms
— at "0" to "1", max.12.8 ms
for interrupt inputs
— parameterizableYes; I 0.0 to I 0.3
for technological functions
— parameterizableYes; (E 0.0 to E 0.5) 30 kHz
Cable length
shielded, max.500 m; Standard input: 500 m, high-speed counters: 50 m
unshielded, max.300 m; not for high-speed signals
Digital outputs
Number of digital outputs4; Relays
Short-circuit protectionNo; to be provided externally
Switching capacity of the outputs
with resistive load, max.2 A
on lamp load, max.30 W with DC, 200 W with AC
Output voltage
for signal "1", min.L+/L1
Output current
for signal "1" rated value2 A
for signal "0" residual current, max.0 mA
Output delay with resistive load
"0" to "1", max.10 ms; all outputs
"1" to "0", max.10 ms; all outputs
Parallel switching of two outputs
for upratingNo
Total current of the outputs (per group)
all mounting positions
— up to 40 °C, max.6 A
horizontal installation
— up to 55 °C, max.6 A
Relay outputs
Number of relay outputs4
Number of relay outputs, integrated4
Number of operating cycles, max.10 000 000; mechanically 10 million, at rated load voltage 100 000
Cable length
shielded, max.500 m
unshielded, max.150 m
Analog inputs
Number of analog potentiometers1; Analog potentiometer; resolution 8 bit
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1 mA
1. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
Protocols
MPIYes; As MPI slave for data exchange with MPI masters (S7-300/S7-400 CPUs, OPs, TDs, Push Button Panels); S7-200-internal CPU/CPU communication is possible in the MPI network with restrictions; transmission rates: 19.2/187.5 kbit/s
PPIYes; with PPI protocol for program functions, HMI functions (TD 200, OP), S7-200-internal CPU/CPU communication ; transmission rates 9.6/19.2/187.5 kbit/s
serial data exchangeYes; As freely programmable interface with interrupt facility for serial data exchange with third-party devices with ASCII protocol transfer rates: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 115.2 kbps; the PC/PPI cable can also be used as RS 232/RS 485 converter
MPI
Transmission rate, min.19.2 kbit/s
Transmission rate, max.187.5 kbit/s
Integrated Functions
Number of counters4; High-speed counters (30 kHz each), 32 bit (incl. sign), can be used as up/down counters or for connecting 2 incremental encoders with 2 pulse trains offset by 90° (max. 20 kHz (A/B counters)); parameterizable enable and reset input; interrupt facilities (incl. call of subroutine with any content) when the setpoint is reached; reversal in counting direction, etc.
Counting frequency (counter) max.30 kHz
Number of alarm inputs4; 4 rising edges and/or 4 falling edges
Potential separation
Potential separation digital inputs
between the channelsYes
between the channels, in groups of2 and 4
Potential separation digital outputs
between the channelsYes; Relays
between the channels, in groups of1 and 3
Permissible potential difference
between different circuits500 V DC between 24 V DC and 5 V DC; 1500 V AC between 24 V DC and 230 V AC
Degree and class of protection
Degree of protection acc. to EN 60529
IP20Yes
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.55 °C
vertical installation, min.0 °C
vertical installation, max.45 °C
Air pressure acc. to IEC 60068-2-13
permissible range, lower limit860 hPa
permissible range, upper limit1 080 hPa
Relative humidity
Operation, min.5 %
Operation, max.95 %; RH class 2 in accordance with IEC 1131-2
Configuration
Programming
Command setBit logic instructions, compare instructions, timer instructions, counter instructions, clock instructions, transmissions instructions, table instructions, logic instructions, shift and rotate instructions, conversion instructions, program control instructions, interrupt and communications instructions, logic stack instructions, integer maths, floating-point math instructions, numerical functions
Program processingfree cycle (OB 1), interrupt-controller, time-controlled (1 to 255 ms)
Program organization1 OB, 1 DB, 1 SDB subroutines with/without parameter transfer
Number of subroutines, max.64
Programming language
— LADYes
— FBDYes
— STLYes
Know-how protection
User program protection/password protectionYes; 3-stage password protection
Connection method
Plug-in I/O terminalsNo
Dimensions
Width90 mm
Height80 mm
Depth62 mm
Weights
Weight, approx.310 g
last modified:03/13/2019