| ***Spare part*** SIMATIC DP, Connection ET 200M IM 153-2 FO High Feature for max. 8 S7-300 modules, with redundancy capability, With integr. LWL interface for addition of an optical line |
General information |
Vendor identification (VendorID) | 8071h |
Supply voltage |
Rated value (DC) | |
24 V DC | Yes |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
external protection for power supply lines (recommendation) | not necessary |
Mains buffering |
Mains/voltage failure stored energy time | 5 ms |
Input current |
Current consumption, max. | 500 mA; at 24 V DC |
Inrush current, typ. | 3.5 A |
I²t | 0.1 A²·s |
Output voltage |
Rated value (DC) | 5 V |
Output current |
for backplane bus (5 V DC), max. | 1 A |
Power loss |
Power loss, typ. | 4.5 W |
Address area |
Addressing volume |
Inputs | 128 byte |
Outputs | 128 byte |
Hardware configuration |
Number of modules per DP slave interface, max. | 8 |
Time stamping |
Accuracy | 10 ms; 10 ms / 3 ms |
Number of message buffers | 15 |
Messages per message buffer | 20 |
Number of stampable digital inputs, max. | 128 |
Time format | RFC 1119 Internet (ISP) |
Time resolution | 1 ms |
Time interval for transmitting the message buffer if a message is present | 1 000 ms |
Time stamp on signal change | rising / falling edge as signal entering or exiting |
Interfaces |
Transmission procedure | FOC, wavelength 660 nm |
PROFIBUS DP |
Node addresses | 1 to 125 permitted |
automatic detection of transmission rate | Yes |
Transmission rate, max. | 12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 12 Mbit/s |
SYNC capability | Yes |
FREEZE capability | Yes |
Direct data exchange (slave-to-slave communication) | Yes; Sender |
Design of electrical connection of PROFIBUS interface | Optical, 2 x duplex sockets |
1. Interface |
PROFIBUS DP slave |
GSD file | (for DPV1) SIEM8071.GSD; SI018071.GSG (for IM 153-2AB0x); SI028071.GSG (for IM 153-2BB0x) |
automatic baud rate search | Yes |
Protocols |
Bus protocol/transmission protocol | PROFIBUS DP to EN 50170 |
Protocols (Ethernet) |
TCP/IP | No |
Potential separation |
Potential separation exists | Yes |
Isolation |
Isolation tested with | Isolation voltage 500 V |
Degree and class of protection |
IP degree of protection | IP20 |
Ambient conditions |
Ambient temperature during operation |
min. | 0 °C |
max. | 60 °C |
Altitude during operation relating to sea level |
Installation altitude above sea level, max. | 3 000 m |
Configuration |
Configuration software |
STEP 7 | Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
Dimensions |
Width | 40 mm |
Height | 125 mm |
Depth | 117 mm |
Weights |
Weight, approx. | 360 g |
last modified: | 03/29/2019 |