| ***Spare part*** SIMATIC DP, IM151-8 PN/DP CPU f. ET200S, 128 KB work memory int. PROFINET interface (with three RJ45 ports) as IO controller,without battery MMC required |
General information |
HW functional status | 01 |
Firmware version | V2.7 |
Engineering with |
Programming package | STEP 7 V5.4 SP4 or higher |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes; against destruction |
external protection for power supply lines (recommendation) | 24 V DC/16 A miniature circuit breaker with type B and C tripping characteristics. Note: The 24 V DC/16 A miniature circuit breaker with type B tripping characteristics trips before the device protection fuse. The 24 V DC/16 A miniature circuit breaker with type C tripping characteristics trips |
Mains buffering |
Mains/voltage failure stored energy time | 5 ms |
Input current |
Inrush current, max. | 1.8 A; Typical |
I²t | 0.21 A²·s |
from supply voltage 1L+, max. | 380 mA; 460 mA with DP master module |
Output current |
for backplane bus (5 V DC), max. | 700 mA |
Power loss |
Power loss, typ. | 5.5 W |
Memory |
Work memory |
integrated | 128 kbyte; For program and data |
expandable | No |
Size of retentive memory for retentive data blocks | 64 kbyte |
Load memory |
Plug-in (MMC) | Yes |
Plug-in (MMC), max. | 8 Mbyte |
Data management on MMC (after last programming), min. | 10 y |
Backup |
present | Yes; Ensured by SIMATIC Micro Memory Card (maintenance-free) |
CPU processing times |
for bit operations, typ. | 0.1 µs |
for word operations, typ. | 0.2 µs |
for fixed point arithmetic, typ. | 2 µs |
for floating point arithmetic, typ. | 3 µs |
CPU-blocks |
Number of blocks (total) | 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. |
DB |
Number, max. | 511; Number range: 1 to 511 |
Size, max. | 64 kbyte |
FB |
Number, max. | 1 024; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
FC |
Number, max. | 1 024; Number range: 0 to 2047 |
Size, max. | 64 kbyte |
OB |
Description | See S7-300 operation list |
Size, max. | 64 kbyte |
Number of free cycle OBs | 1; OB 1 |
Number of time alarm OBs | 1; OB 10 |
Number of delay alarm OBs | 1; OB 20 |
Number of cyclic interrupt OBs | 1; OB 35 |
Number of process alarm OBs | 1; OB 40 |
Number of DPV1 alarm OBs | 3; OB 55, 56, 57 |
Number of startup OBs | 1; OB 100 |
Number of asynchronous error OBs | 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for centralized I/O and PROFINET IO) |
Number of synchronous error OBs | 2; OB 121, 122 |
Nesting depth |
per priority class | 16 |
additional within an error OB | 4 |
Counters, timers and their retentivity |
S7 counter |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 255 |
— preset | Z 0 to Z 7 |
Counting range |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 999 |
IEC counter |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
S7 times |
Number | 256 |
Retentivity |
— adjustable | Yes |
— lower limit | 0 |
— upper limit | 255 |
— preset | No retentivity |
Time range |
— lower limit | 10 ms |
— upper limit | 9 990 s |
IEC timer |
present | Yes |
Type | SFB |
Number | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity |
Flag |
Number, max. | 256 byte |
Retentivity available | Yes |
Retentivity preset | MB 0 to MB 15 |
Number of clock memories | 8; 1 memory byte |
Data blocks |
Retentivity adjustable | Yes; via non-retain property on DB |
Retentivity preset | Yes |
Local data |
per priority class, max. | 510 byte; per priority class |
Address area |
I/O address area |
Inputs | 2 048 byte |
Outputs | 2 048 byte |
of which distributed |
— Inputs | 2 048 byte |
— Outputs | 2 048 byte |
Process image |
Inputs, adjustable | 2 048 byte |
Outputs, adjustable | 2 048 byte |
Inputs, default | 128 byte |
Outputs, default | 128 byte |
Subprocess images |
Number of subprocess images, max. | none |
Digital channels |
Inputs | 16 336 |
— of which central | 496 |
Outputs | 16 336 |
— of which central | 496 |
Analog channels |
Inputs | 1 021 |
— of which central | 124 |
Outputs | 1 021 |
— of which central | 124 |
Hardware configuration |
Number of modules per system, max. | 63; Centralized |
Mounting rail |
Number of mounting rails that can be used | 1 |
Length of mounting rail, max. | Station width: ≤ 1 m or < 2 m |
Time of day |
Clock |
Hardware clock (real-time) | Yes |
retentive and synchronizable | Yes |
Backup time | 6 wk; At 40 °C ambient temperature, typically |
Deviation per day, max. | 10 s |
Behavior of the clock following expiry of backup period | Clock continues to run with the time at which the power failure occurred |
Operating hours counter |
Number | 1 |
Number/Number range | 0 |
Range of values | 0 to 2^31 hours (when using SFC 101) |
Granularity | 1 h |
retentive | Yes; Must be restarted at each restart |
Clock synchronization |
supported | Yes |
to MPI, master | No |
to MPI, slave | No |
to DP, master | Yes; With DP master module |
to DP, slave | Yes; With DP master module |
in AS, master | No |
in AS, slave | No |
on Ethernet via NTP | Yes; As client |
Interfaces |
Number of industrial Ethernet interfaces | 1 |
Number of PROFINET interfaces | 1 |
Number of wireless interfaces | 0 |
1. Interface |
Interface type | PROFINET |
Physics | Ethernet |
Isolated | Yes |
automatic detection of transmission rate | Yes |
Autonegotiation | Yes |
Autocrossing | Yes |
Interface types |
Number of ports | 3; RJ45 |
integrated switch | Yes |
Protocols |
MPI | No |
PROFINET IO Controller | Yes |
PROFINET IO Device | No |
PROFINET CBA | Yes |
PROFIBUS DP master | No |
PROFIBUS DP slave | No |
Open IE communication | Yes; Via TCP/IP, ISO on TCP, and UDP |
Web server | Yes |
Point-to-point connection | No |
PROFINET IO Controller |
Transmission rate, max. | 100 Mbit/s; full duplex |
Services |
— PG/OP communication | Yes |
— Routing | Yes; With DP master module |
— S7 communication | Yes; with loadable FBs |
— Isochronous mode | No |
— Open IE communication | Yes; Via TCP/IP, ISO on TCP, and UDP |
— IRT | Yes |
— Prioritized startup | Yes |
— Number of IO devices with prioritized startup, max. | 32 |
— Number of connectable IO Devices, max. | 128 |
— Number of IO Devices with IRT and the option "high flexibility" | 128 |
— of which in line, max. | 61 |
— Number of connectable IO Devices for RT, max. | 128 |
— of which in line, max. | 128 |
— Activation/deactivation of IO Devices | Yes |
— Number of IO Devices that can be simultaneously activated/deactivated, max. | 8 |
— IO Devices changing during operation (partner ports), supported | Yes |
— Number of IO Devices per tool, max. | 8 |
— Device replacement without swap medium | Yes |
— Send cycles | Adjustable: 250 µs, 500 µs and 1 ms |
— Updating time | Minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the number of configured user data items. |
— Updating times | 250 µs - 128 ms (with signal cycle 250 µs); 500 µs - 256 ms (with signal cycle 500 µs); 1 ms - 512 ms (with signal cycle 1 ms) |
Address area |
— Inputs, max. | 2 kbyte |
— Outputs, max. | 2 kbyte |
— User data consistency, max. | 254 byte; with PROFINET I/O |
PROFINET CBA |
acyclic transmission | Yes |
cyclic transmission | Yes |
Open IE communication |
Number of connections, max. | 8 |
Local port numbers used at the system end | 0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
2. Interface |
Interface type | External interface via master module 6ES7138-4HA00-0AB0 |
Physics | RS 485 |
Isolated | Yes |
Power supply to interface (15 to 30 V DC), max. | No |
Protocols |
MPI | No |
PROFINET IO Controller | No |
PROFINET IO Device | No |
PROFINET CBA | No |
PROFIBUS DP master | Yes |
PROFIBUS DP slave | No |
Open IE communication | No |
Web server | No |
Point-to-point connection | No |
PROFIBUS DP master |
Number of connections, max. | 12; Notice: 12 connections per CPU, not per interface |
Transmission rate, max. | 12 Mbit/s |
Number of DP slaves, max. | 32; Per station |
Services |
— PG/OP communication | Yes |
— Routing | Yes |
— Global data communication | No |
— S7 basic communication | Yes; I blocks only |
— S7 communication | Yes |
— S7 communication, as client | No |
— S7 communication, as server | Yes |
— Equidistance | Yes |
— Isochronous mode | No |
— SYNC/FREEZE | Yes |
— Activation/deactivation of DP slaves | Yes |
— Number of DP slaves that can be simultaneously activated/deactivated, max. | 8 |
— Direct data exchange (slave-to-slave communication) | Yes |
— DPV1 | Yes |
Address area |
— Inputs, max. | 2 048 byte |
— Outputs, max. | 2 048 byte |
User data per DP slave |
— Inputs, max. | 244 byte |
— Outputs, max. | 244 byte |
Protocols |
Open IE communication |
TCP/IP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 8 |
— Data length for connection type 01H, max. | 1 460 byte |
— Data length for connection type 11H, max. | 8 192 byte |
ISO-on-TCP (RFC1006) | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 8 |
— Data length, max. | 8 192 byte |
UDP | Yes; via integrated PROFINET interface and loadable FBs |
— Number of connections, max. | 8 |
— Data length, max. | 1 472 byte |
Web server |
supported | Yes |
Number of HTTP clients | 5 |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Communication functions |
PG/OP communication | Yes |
Data record routing | Yes; With DP master module |
Global data communication |
supported | No |
S7 basic communication |
supported | Yes; I blocks |
User data per job, max. | 76 byte |
User data per job (of which consistent), max. | 76 byte |
S7 communication |
supported | Yes |
as server | Yes |
as client | Yes; via integrated PROFINET interface and loadable FBs |
User data per job, max. | 180 byte |
User data per job (of which consistent), max. | 64 byte |
S5 compatible communication |
supported | No |
Standard communication (FMS) |
supported | No |
PROFINET CBA (at set setpoint communication load) |
Setpoint for the CPU communication load | 50 % |
Number of remote interconnection partners | 32 |
Number of functions, master/slave | 30 |
Total of all master/slave connections | 1 000 |
Data length of all incoming connections master/slave, max. | 4 000 byte |
Data length of all outgoing connections master/slave, max. | 4 000 byte |
Number of device-internal and PROFIBUS interconnections | 500 |
Data length of device-internal und PROFIBUS interconnections, max. | 4 000 byte |
Data length per connection, max. | 1 400 byte |
Remote interconnections with acyclic transmission |
— Sampling frequency: Sampling time, min. | 500 ms |
— Number of incoming interconnections | 100 |
— Number of outgoing interconnections | 100 |
— Data length of all incoming interconnections, max. | 2 000 byte |
— Data length of all outgoing interconnections, max. | 2 000 byte |
— Data length per connection, max. | 1 400 byte |
Remote interconnections with cyclic transmission |
— Transmission frequency: Transmission interval, min. | 1 ms |
— Number of incoming interconnections | 200 |
— Number of outgoing interconnections | 200 |
— Data length of all incoming interconnections, max. | 2 000 byte |
— Data length of all outgoing interconnections, max. | 2 000 byte |
— Data length per connection, max. | 250 byte |
HMI variables via PROFINET (acyclic) |
— Number of stations that can log on for HMI variables (PN OPC/iMap) | 3; 2x PN OPC/1x iMap |
— HMI variable updating | 500 ms |
— Number of HMI variables | 200 |
— Data length of all HMI variables, max. | 2 000 byte |
PROFIBUS proxy functionality |
— supported | Yes |
— Number of linked PROFIBUS devices | 16 |
— Data length per connection, max. | 240 byte; Slave-dependent |
Number of connections |
overall | 12 |
usable for PG communication | 11 |
— reserved for PG communication | 1 |
— adjustable for PG communication, min. | 1 |
— adjustable for PG communication, max. | 11 |
usable for OP communication | 11 |
— reserved for OP communication | 1 |
— adjustable for OP communication, min. | 1 |
— adjustable for OP communication, max. | 11 |
usable for S7 basic communication | 10 |
— reserved for S7 basic communication | 0 |
— adjustable for S7 basic communication, min. | 0 |
— adjustable for S7 basic communication, max. | 10 |
usable for S7 communication | 10; with loadable FBs |
— adjustable for S7 communication, max. | 10 |
total number of instances, max. | 32 |
usable for routing | 4; With DP master module |
S7 message functions |
Number of login stations for message functions, max. | 12; Depending on the configured connections for PG/OP and S7 basic communication |
Process diagnostic messages | Yes; ALARM_S, ALARM_SC, ALARM_SQ, ALARM_D, ALARM_DQ |
simultaneously active Alarm-S blocks, max. | 300 |
Test commissioning functions |
Status block | Yes |
Single step | Yes |
Number of breakpoints | 2 |
Status/control |
Status/control variable | Yes |
Variables | Inputs, outputs, memory bits, DB, times, counters |
Number of variables, max. | 30 |
— of which status variables, max. | 30 |
— of which control variables, max. | 14 |
Forcing |
Forcing | Yes |
Forcing, variables | Inputs, outputs |
Number of variables, max. | 10 |
Diagnostic buffer |
present | Yes |
Number of entries, max. | 500 |
— adjustable | No |
— of which powerfail-proof | 100; Only the last 100 entries are retained |
Interrupts/diagnostics/status information |
Alarms | Yes |
Diagnostics function | Yes |
Diagnostics indication LED |
for maintenance | Yes; MT |
Bus fault BF (red) | Yes; BF-PN |
Group error SF (red) | Yes |
Monitoring 24 V voltage supply ON (green) | Yes |
Bus activity PROFINET (green) | Yes; P1-/P2-/P3-Link |
Potential separation |
between load voltage and all other switching components | Yes |
between PROFIBUS DP and all other circuit components | Yes |
Permissible potential difference |
between different circuits | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Degree and class of protection |
IP degree of protection | IP20 |
Configuration |
Configuration software |
STEP 7 | Yes; V5.4 SP4 |
Programming |
Command set | see instruction list |
Nesting levels | 8 |
System functions (SFC) | see instruction list |
System function blocks (SFB) | see instruction list |
Programming language |
— LAD | Yes |
— FBD | Yes |
— STL | Yes |
— SCL | Yes; Optional |
— CFC | Yes; Optional |
— GRAPH | Yes; Optional |
— HiGraph® | Yes; Optional |
Know-how protection |
User program protection/password protection | Yes |
Cycle time monitoring |
lower limit | 1 ms |
upper limit | 6 000 ms |
adjustable | Yes |
preset | 150 ms |
Dimensions |
Width | 120 mm; DP master module: 35 mm |
Height | 119.5 mm |
Depth | 75 mm |
Weights |
Weight, approx. | 320 g; DP master module: Approx. 100 g |
last modified: | 03/13/2019 |