6ES7151-7AA00-0AB0
ET200S, IM151-7 CPU, 24KB

From SIEMENS

SIMATIC DP, IM151-7 CPU FOR ET200S, 24 KB WORKING MEMORY INTEGR. PROFIBUS-DP INTERFACE (9 PIN SUB-D, FEMALE) AS DP SLAVE, W/O BATTERY
General information
HW functional status02
Firmware versionV1.0.0
Engineering with
Programming packageSTEP 7 V5.1 or higher
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Inrush current, max.3.5 A
from supply voltage L+, max.250 mA
from supply voltage 1L+, max.250 mA; approx.
Output current
for backplane bus (5 V DC), max.700 mA
Power loss
Power loss, typ.3.3 W
Power loss, max.4.5 W
Memory
Work memory
integrated24 kbyte
expandableNo
Load memory
Plug-in (MMC), max.64 kbyte; RAM, integrated
expandable FEPROMYes
expandable FEPROM, max.64 kbyte; MMC, 2 MB MMC
Backup
presentNo
CPU processing times
for bit operations, typ.0.3 µs
for word operations, typ.1 µs
for fixed point arithmetic, typ.2 µs
for floating point arithmetic, typ.50 µs
for timer/counter operations, typ.12 µs
CPU-blocks
DB
Number, max.127; DB 0 reserved
Size, max.8 kbyte
FB
Number, max.128
Size, max.8 kbyte
FC
Number, max.128
Size, max.8 kbyte
OB
DescriptionSee Appendix B
Size, max.8 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of cyclic interrupt OBs1; OB 35
Number of process alarm OBs1; OB 40
Number of startup OBs1; OB 100
Number of asynchronous error OBs4; OB 80, 82, 85, 86
Nesting depth
per priority class8
Counters, timers and their retentivity
S7 counter
Number64
Retentivity
— adjustableYes
— lower limit0
— upper limit63
— presetZ 0 to Z 7
Counting range
— adjustableYes
— lower limit0
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number128
Retentivity
— adjustableYes
— lower limit0
— upper limit127
— presetNo times retentive
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max.4 736 byte
Flag
Number, max.256 byte
Retentivity availableYes
of which retentiveMB 0 to MB 255
Retentivity presetMB 0 to MB 15
Number of clock memories8; 1 memory byte
Local data
per priority class, max.256 byte; Local data max.: 1536 byte
Address area
I/O address area
Inputs1 536 byte
Outputs1 536 byte
Process image
Inputs128 byte; Not adjustable
Outputs128 byte; Not adjustable
Digital channels
Inputs248; max.
Outputs248; max.
Analog channels
Inputs124; max.
Outputs124; max.
Addressing volume
Inputs244 byte
Outputs244 byte
Hardware configuration
connectable programming devices/PCsPGs/OPs with STEP 7 connectable via PROFIBUS interface
Number of modules per system, max.63
Time of day
Clock
Software clockYes
Operating hours counter
NumberNo
Interfaces
PROFIBUS DP
Node addresses1 to 125
Cable length, max.1 000 m; 100 to 1 000 m (depending on transmission speed), without repeaters
1. Interface
Interface typeIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.80 mA
Protocols
MPINo
PROFIBUS DP slaveYes
Point-to-point connectionNo
PROFIBUS DP slave
Number of connections11
GSD file
Transmission rate, max.12 Mbit/s
Address area, max.32
User data per address area, max.32 byte; Up to max. size of the transfer memory
Services
— RoutingNo
— S7 communication, as clientYes
— S7 communication, as serverYes
— Direct data exchange (slave-to-slave communication)Yes
Transfer memory
— Inputs64 byte
— Outputs64 byte
Communication functions
PG/OP communicationYes
Global data communication
supportedNo
S7 basic communication
supportedYes; as server
User data per job, max.76 byte
User data per job (of which consistent), max.32 byte; with I_PUT/I_GET
S7 communication
supportedYes
as serverYes
User data per job, max.160 kbyte
User data per job (of which consistent), max.32 byte
S5 compatible communication
supportedNo
Standard communication (FMS)
supportedNo
S7 message functions
Process diagnostic messagesYes; ALARM_S, ALARM_SQ
Test commissioning functions
Status blockYes
Single stepYes
Number of breakpoints2
Status/control
Status/control variableYes
VariablesInputs, outputs, memory bits, DB, times, counters
Number of variables, max.
— of which status variables, max.30
— of which control variables, max.14
Forcing
ForcingYes
Forcing, variablesInputs, outputs
Number of variables, max.10
Diagnostic buffer
presentYes
Number of entries, max.100; does not exist
Isolation
Isolation tested with500 V DC
Ambient conditions
Ambient temperature during operation
min.0 °C
max.60 °C
Configuration
Configuration software
STEP 7Yes
Programming
Command setBinary logic operations, bracketed operations, result allocation, saving, counting, loading, transferring, comparing, shifting, rotating, complementation, calling blocks, fixed point arithmetic, floating point arithmetic, jump functions
Nesting levels8
Program organizationLinear, structured
System functions (SFC)Interrupt and error processing, copy data, clock functions, diagnostic functions, module parameterization, operating mode transitions
System function blocks (SFB)see Appendix C
Programming language
— SCLYes
Software libraries
— Process diagnosticsYes
— Software controllerYes; depending on the required memory space and the resulting execution time
Know-how protection
User program protection/password protectionYes
Cycle time monitoring
lower limit1 ms
upper limit6 000 ms
adjustableYes
preset150 ms
Dimensions
Width60 mm
Height119.5 mm
Depth75 mm
Weights
Weight, approx.200 g
last modified:03/13/2019