6ES7145-6HD00-0AB0
ET200eco PN, 4AO U/I 4xM12

From SIEMENS

SIMATIC DP, ET 200ECO PN, 4 AO U/I; 4xM12, Degree of protection IP67
General information
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0306H
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
Current consumption, typ.280 mA
Actuator supply
Number of outputs4
Short-circuit protectionYes; Electronic at 1.4 A
Output current
Rated value1 A; Maximum
Power loss
Power loss, typ.5.5 W
Analog outputs
Number of analog outputs4
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.30 mA
Current output, no-load voltage, max.20 V
Output ranges, voltage
0 to 10 VYes
1 V to 5 VYes
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
for current output two-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.600 Ω
with current outputs, inductive load, max.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA28.8 V permanent, 35 V for max. 500 ms
Cable length
shielded, max.30 m
Analog value generation for the outputs
Analog value displaySIMATIC S7 format
Conversion principleResistor network
Integration and conversion time/resolution per channel
Resolution (incl. overrange)15 bit + sign
Conversion time (per channel)1 ms
Settling time
for resistive load2 ms
for capacitive load1.8 ms
for inductive load2 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)U: ±0.6 mVrms; I: ±0.4 nArms
Linearity error (relative to output range), (+/-)0.02 %
Temperature error (relative to output range), (+/-)U: 0.001%/°C; I: 0.0025%/°C
Crosstalk between the outputs, min.70 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.008 %
Interfaces
Transmission procedure100BASE-TX
Number of PROFINET interfaces1
1. Interface
Interface types
integrated switchYes
M12 portYes
Interface types
M12 port
Transmission procedure100BASE-TX
AutonegotiationYes
AutocrossingYes
Transmission rate, max.100 Mbit/s
Protocols
Supports protocol for PROFINET IOYes
PROFINET CBANo
PROFIsafeNo
PROFINET IO Device
Services
— IRT with the option "high flexibility"Yes
— Prioritized startupYes
Open IE communication
TCP/IPNo
SNMPYes
DCPYes
LLDPYes
pingYes
ARPYes
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Monitoring the supply voltageYes; Green "ON" LED
Wire-breakYes; Channel-by-channel with current output
Short-circuitYes; Channel-by-channel with voltage output
Group errorYes; Red/yellow "SF/MT" LED
Potential separation
between the load voltagesYes
between load voltage and all other switching componentsNo
between Ethernet and electronicsYes
Potential separation channels
between the channelsNo
Permissible potential difference
between M internally and the outputs10 Vpp AC
Isolation
tested with
24 V DC circuits707 V DC (type test)
Test voltage for interface, rms value [Vrms]1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protectionIP65/67
Connection method
Design of electrical connection4/5-pin M12 circular connectors
Dimensions
Width60 mm
Height175 mm
Depth49 mm
Weights
Weight, approx.930 g
last modified:03/13/2019