6ES7145-1FB31-0XB0
ET200X, EM145, 2AO, +/-10V, 11 bit+Sign

From SIEMENS

***Spare part*** SIMATIC DP, Expansion module EM 145 for ET 200X, IP66/67 2 AO, +/-10 V, 11 bit + sign with diagnostics via channels 2/4 wire connection
Input current
from supply voltage L+, max.75 mA
Power loss
Power loss, typ.1.5 W
Analog outputs
Number of analog outputs2
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.30 mA
Cycle time (all channels) max.1 ms
Output ranges, voltage
-10 V to +10 VYes
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionYes
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ
with voltage outputs, capacitive load, max.0.1 µF
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA15 V
Cable length
shielded, max.30 m
Analog value generation for the outputs
Analog value displayS7 Format / S5 Format
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.11 bit; + sign
Settling time
for resistive load0.6 ms
for capacitive load6 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.05 %
Linearity error (relative to output range), (+/-)0.08 %
Temperature error (relative to output range), (+/-)0.01 %/K
Crosstalk between the outputs, min.45 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)1 %
Current, relative to output range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.9 %
Current, relative to output range, (+/-)0.9 %
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Substitute values connectableNo; channel by channel
Alarms
Diagnostic alarmYes
Diagnostic messages
Short-circuitYes; channel by channel
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog outputs
Potential separation analog outputsNo
Permissible potential difference
between MANA and M internally (UISO)0V AC; DC
Connection method
Design of electrical connection for the inputs and outputs4/5-pin M12 circular connectors
Dimensions
Width87 mm; Width module 60 mm
Height110 mm
Depth55 mm
Weights
Weight, approx.250 g
last modified:02/22/2020