| ***Spare part*** SIMATIC DP, Expansion module EM 144 for ET 200X, IP66/67 2 AI, +/-20 mA, 12 bit+sign diagnostics via channels for 4 wire measuring transducer |
Input current |
from supply voltage L+, max. | 40 mA |
Encoder supply |
Number of outputs | 2 |
Short-circuit protection | Yes; Electronic |
Output current |
up to 40 °C, max. | 0.9 A |
up to 55 °C, max. | 0.7 A |
Power loss |
Power loss, typ. | 0.9 W |
Analog inputs |
Number of analog inputs | 2 |
permissible input current for current input (destruction limit), max. | 40 mA |
Cycle time (all channels) max. | 134 / 160 |
Input ranges |
Current | Yes |
Input ranges (rated values), currents |
-20 mA to +20 mA | Yes |
Input resistance (-20 mA to +20 mA) | 25 Ω |
4 mA to 20 mA | Yes |
Input resistance (4 mA to 20 mA) | 25 Ω |
Cable length |
shielded, max. | 30 m |
Analog value generation for the inputs |
Analog value display | S7 Format / S5 Format |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 12 bit; + sign; overrange 17.5% |
Integration time, parameterizable | Yes |
Integration time (ms) | 16,7 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | No |
for current measurement as 4-wire transducer | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.05 % |
Temperature error (relative to input range), (+/-) | 0.01 %/K |
Crosstalk between the inputs, min. | 45 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Voltage, relative to input range, (+/-) | 1.2 % |
Current, relative to input range, (+/-) | 1.2 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to input range, (+/-) | 1 % |
Current, relative to input range, (+/-) | 1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 40 dB |
Common mode interference, min. | 60 dB |
Interrupts/diagnostics/status information |
Diagnostics function | Yes; Parameterizable |
Alarms |
Diagnostic alarm | Yes |
Limit value alarm | Yes; upper limit, channel by channel/ lower limit channel by channel |
Hardware interrupt | Yes |
Diagnostic messages |
Wire-break | Yes; channel by channel |
Short-circuit | Yes; channel by channel |
Overflow/underflow | Yes; channel by channel |
Diagnostics indication LED |
Group error SF (red) | Yes |
Potential separation |
Potential separation analog inputs |
Potential separation analog inputs | No |
Connection method |
Design of electrical connection for the inputs and outputs | 4/5-pin M12 circular connectors |
Dimensions |
Width | 87 mm; Width module 60 mm |
Height | 110 mm |
Depth | 55 mm |
Weights |
Weight, approx. | 250 g |
last modified: | 03/13/2019 |