6ES7144-1GB31-0XB0
ET200X, EM144, 2AI, +/-20mA, 12 bit+Sign

From SIEMENS

***Spare part*** SIMATIC DP, Expansion module EM 144 for ET 200X, IP66/67 2 AI, +/-20 mA, 12 bit+sign diagnostics via channels for 4 wire measuring transducer
Input current
from supply voltage L+, max.40 mA
Encoder supply
Number of outputs2
Short-circuit protectionYes; Electronic
Output current
up to 40 °C, max.0.9 A
up to 55 °C, max.0.7 A
Power loss
Power loss, typ.0.9 W
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.40 mA
Cycle time (all channels) max.134 / 160
Input ranges
CurrentYes
Input ranges (rated values), currents
-20 mA to +20 mAYes
Input resistance (-20 mA to +20 mA)25 Ω
4 mA to 20 mAYes
Input resistance (4 mA to 20 mA)25 Ω
Cable length
shielded, max.30 m
Analog value generation for the inputs
Analog value displayS7 Format / S5 Format
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit; + sign; overrange 17.5%
Integration time, parameterizableYes
Integration time (ms)16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Encoder
Connection of signal encoders
for current measurement as 2-wire transducerNo
for current measurement as 4-wire transducerYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.05 %
Temperature error (relative to input range), (+/-)0.01 %/K
Crosstalk between the inputs, min.45 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)1.2 %
Current, relative to input range, (+/-)1.2 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)1 %
Current, relative to input range, (+/-)1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes
Limit value alarmYes; upper limit, channel by channel/ lower limit channel by channel
Hardware interruptYes
Diagnostic messages
Wire-breakYes; channel by channel
Short-circuitYes; channel by channel
Overflow/underflowYes; channel by channel
Diagnostics indication LED
Group error SF (red)Yes
Potential separation
Potential separation analog inputs
Potential separation analog inputsNo
Connection method
Design of electrical connection for the inputs and outputs4/5-pin M12 circular connectors
Dimensions
Width87 mm; Width module 60 mm
Height110 mm
Depth55 mm
Weights
Weight, approx.250 g
last modified:03/13/2019