6ES7143-1BF30-0XB0
ET 200X, BM143/DESINA, 8DI/DO

From SIEMENS

***Spare part*** SIMATIC DP, distributed I/O ET200X: Extended module BM143/DESINA 8DE/DA parameterizable additional diagnostics inputs, IP67
Input current
from backplane bus 5 V DC, max.40 mA
Encoder supply
Number of outputs8
Short-circuit protectionYes; Electronic
Output current
up to 40 °C, max.1 A
up to 55 °C, max.0.8 A
Power loss
Power loss, typ.1.5 W
Digital inputs
Number of digital inputs8; 8 function inputs (diagnostic inputs or inputs with opener function)
Input characteristic curve in accordance with IEC 61131, type 2Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 55 °C, max.8
Input voltage
Rated value (DC)24 V; Input voltage for parameterized DI (Pin 4) / Input voltage for function input (Pin 2)
for signal "0"-30 to +5V
for signal "1"13 to 30V
Input current
for signal "1", typ.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", min.1.2 ms
— at "0" to "1", max.4.8 ms
— at "1" to "0", min.1.2 ms
— at "1" to "0", max.4.8 µs
Cable length
unshielded, max.30 m; for signal lines
Digital outputs
Number of digital outputs8; 8 process channels, parameterization as DI/DO; 8 function channels, parameter assignment as diagnostics/NC input
Short-circuit protectionYes; Electronic
Response threshold, typ.1.8 A
Switching capacity of the outputs
on lamp load, max.10 W
Output current
for signal "1" rated value1.2 A
for signal "0" residual current, max.0.5 mA
Switching frequency
with resistive load, max.100 Hz
with inductive load (acc. to IEC 60947-5-1, DC13), max.2 Hz
on lamp load, max.1 Hz
Total current of the outputs (per module)
all mounting positions
— up to 20 °C, max.10 A
Cable length
unshielded, max.30 m; for signal lines
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Diagnostics indication LED
Status indicator per channel (yellow)Yes
Indicator function input per channel (yellow/red)Yes
Potential separation
between the load voltagesNo
between load voltage and all other switching componentsNo
Potential separation digital inputs
between the channelsNo
between the channels and backplane busNo
Potential separation digital outputs
between the channelsNo
between the channels and backplane busNo
Dimensions
Width87 mm; Width module 60 mm
Height180 mm
Depth55 mm
Weights
Weight, approx.350 g
last modified:03/25/2019