| ***Spare part*** SIMATIC DP, distributed I/O ET200X: Basic module BM143/DESINA 8DE/DA parameterizable ADDITIONAL diagnostics, inputs, Hybrid, Field bus activation, (RS485), Identification plug IP67 |
General information |
Vendor identification (VendorID) | 809Ah |
Supply voltage |
Load voltage non-switched (NS) |
Rated value (DC) | 24 V |
Short-circuit protection | No |
Reverse polarity protection | No |
Load voltage switched (S) |
Rated value (DC) | 24 V |
Reverse polarity protection | No |
Input current |
from load voltage, unswitched (NS) |
up to 40 °C, max. | 10 A |
up to 55 °C, max. | 8 A |
from load voltage, switched (S) |
up to 40 °C, max. | 10 A |
up to 55 °C, max. | 8 A |
Encoder supply |
Number of outputs | 8 |
Short-circuit protection | Yes; Electronic |
Output current |
up to 40 °C, max. | 1 A |
up to 55 °C, max. | 0.8 A |
Power loss |
Power loss, typ. | 3.5 W |
Hardware configuration |
Expansion modules |
Number of expansion modules, max. | 7 |
— of which motor starters/frequency converters, max. | 6 |
— of which pneumatic interfaces, max. | 6 |
Digital inputs |
Number of digital inputs | 8; 8 process channels, parameterization as DI/DO; 8 function channels, parameter assignment as diagnostics/NC input |
Input characteristic curve in accordance with IEC 61131, type 2 | Yes |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 55 °C, max. | 8 |
Input voltage |
Rated value (DC) | 24 V; Input voltage for parameterized DI (Pin 4): Rated value 24 VDC, for signal "1": 13 to 30 V, for signal "0": -30 to +5 V: Input voltage for input functionality (Pin 2): Rated value 24 VDC, for signal "1": 13 to 30 VDC, for signal "0": -30 to +2 V |
for signal "0" | -3 to +5V |
for signal "1" | 13 to 30V |
Input current |
for signal "1", typ. | 5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", min. | 1.2 ms |
— at "0" to "1", max. | 4.8 ms |
— at "1" to "0", min. | 1.2 ms |
— at "1" to "0", max. | 4.8 ms |
Cable length |
unshielded, max. | 30 m; for signal lines |
Digital outputs |
Number of digital outputs | 8; 8 process channels, parameterization as DI/DO; 8 function channels, parameter assignment as diagnostics/NC input |
Short-circuit protection | Yes; Electronic |
Response threshold, typ. | 1.8 A |
Switching capacity of the outputs |
on lamp load, max. | 10 W |
Output current |
for signal "1" rated value | 1.2 A |
for signal "0" residual current, max. | 0.5 mA |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load (acc. to IEC 60947-5-1, DC13), max. | 2 Hz |
on lamp load, max. | 1 Hz |
Total current of the outputs (per module) |
all mounting positions |
— up to 20 °C, max. | 10 A |
— up to 55 °C, max. | 5 A |
Cable length |
unshielded, max. | 30 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interfaces |
PROFIBUS DP |
SYNC capability | Yes |
FREEZE capability | Yes |
1. Interface |
Protocols |
PROFIBUS DP slave | Yes |
PROFIBUS DP slave |
Transmission rate, max. | 12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 12 Mbit/s |
Services |
— Direct data exchange (slave-to-slave communication) | Yes; Sender |
Protocols |
PROFIBUS DP | Yes |
Interrupts/diagnostics/status information |
Diagnostics function | Parameterizable |
Alarms |
Diagnostic alarm | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Diagnostics indication LED |
RUN LED | Yes |
Group error SF (red) | Yes |
Status indicator per channel (yellow) | Yes |
Indicator function input per channel (yellow/red) | Yes |
Monitoring the unswitched load voltage DC 24 V-NS (green) | Yes |
Monitoring the switched load voltage DC 24 V-S (green) | Yes |
Potential separation |
between the load voltages | No |
between load voltage and all other switching components | No |
between PROFIBUS DP and all other circuit components | Yes |
Potential separation digital inputs |
between the channels | No |
between the channels and backplane bus | No |
Potential separation digital outputs |
between the channels | No |
between the channels and backplane bus | No |
Dimensions |
Width | 175 mm; 180 when screw mounted |
Height | 180 mm; 174 when screw mounted |
Depth | 110 mm; 90 when screw mounted |
Weights |
Weight, approx. | 650 g |
last modified: | 03/25/2019 |