6ES7141-6BF00-0AB0
ET200eco PN, 8DI, DC24V, 4xM12

From SIEMENS

SIMATIC DP, ET 200ECO PN, 8 DI 24 V DC; 4xM12, Duplicate assignment, Degree of protection IP67
General information
Vendor identification (VendorID)002AH
Device identifier (DeviceID)0306H
Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
Current consumption, typ.100 mA
Encoder supply
Number of outputs4
24 V encoder supply
Short-circuit protectionYes; Electronic
Output current, max.100 mA; per output
Power loss
Power loss, typ.5.5 W
Digital inputs
Number of digital inputs8
in groups of2
Input characteristic curve in accordance with IEC 61131, type 3Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 60 °C, max.8
Input voltage
Rated value (DC)24 V
for signal "0"-3 to +5V
for signal "1"+11 to +30V
Input current
for signal "1", typ.7 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.typically 3 ms
— at "1" to "0", max.typically 3 ms
Cable length
unshielded, max.30 m
Encoder
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Interfaces
Transmission procedure100BASE-TX
Number of PROFINET interfaces1
1. Interface
Interface types
integrated switchYes
M12 portYes
Interface types
M12 port
Transmission procedure100BASE-TX
AutonegotiationYes
AutocrossingYes
Transmission rate, max.100 Mbit/s
Protocols
Supports protocol for PROFINET IOYes
PROFINET CBANo
PROFIsafeNo
PROFINET IO Device
Services
— IRT with the option "high flexibility"Yes
— Prioritized startupYes
Open IE communication
TCP/IPNo
SNMPYes
DCPYes
LLDPYes
pingYes
ARPYes
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Diagnostic messages
Diagnostic information readableYes
Monitoring the supply voltageYes; Green "ON" LED
Wire-break in signal transmitter cableYes
Short-circuit encoder supplyYes; Per channel group
Group errorYes; Red/yellow "SF/MT" LED
Potential separation
between the load voltagesYes
between load voltage and all other switching componentsNo
between Ethernet and electronicsYes
Potential separation channels
between the channelsNo
Isolation
tested with
24 V DC circuits707 V DC (type test)
Test voltage for interface, rms value [Vrms]1 500 V; According to IEEE 802.3
Degree and class of protection
IP degree of protectionIP65/67
Connection method
Design of electrical connection4/5-pin M12 circular connectors
Dimensions
Width30 mm
Height200 mm
Depth49 mm
Weights
Weight, approx.550 g