6ES7138-4CB10-0AB0
ET200S, POWERMOD.PM-E;DC24-48V/AC24-230V

From SIEMENS

SIMATIC DP, POWER MODULE PM-E FOR ET200S; DC 24 - 48V, AC 24 - 230V, WITH DIAGNOSTICS AND BACKUP
Supply voltage
Load voltage L+
Rated value (DC)24 to 56.7 V DC, 24 to 48 V / 120 V / 230 V AC
Short-circuit protectionYes; IEC 127-2/1, internal with fuse (5x 20 mm), 250 V, 10 A, quick-response, replaceable
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.9 mA
from backplane bus 24 V DC, max.9.5 mA
Output voltage
Overvoltage protectionYes
Current carrying capacity
up to 30 °C, max.10 A; 10 A (24 to 56.7 V DC), 8 A (24 to 48 V AC / 120 V / 230 V)
up to 40 °C, max.9 A; 9 A (24 to 56.7 V DC); 7 A (24 to 48 V AC / 120 V / 130 V)
up to 60 °C, max.7 A; 7 A (24 to 56.7 V DC); 5 A (24 to 48 V AC / 120 V / 230 V)
Power loss
Power loss, max.5 W
Interrupts/diagnostics/status information
Diagnostics functionYes
Diagnostic messages
Diagnostic information readableYes
Fuse blownYes
missing load voltageYes
Diagnostics indication LED
Rated load voltage PWR (green)Yes
Fuse OK FSG (green)Yes
Group error SF (red)Yes
Parameter
Remark3 byte
Diagnostics, fuse blownDisable / enable
missing load voltageDisable / enable
Load voltageDC/AC
Potential separation
primary/secondaryYes; between rated load voltage and backplane bus, between power modules
Isolation
Isolation tested with1500 V AC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.34 g
last modified:03/13/2019

External links