6ES7138-4CB10-0AB0 ET200S, POWERMOD.PM-E;DC24-48V/AC24-230V
From SIEMENS
SIMATIC DP, POWER MODULE PM-E FOR ET200S; DC 24 - 48V, AC 24 - 230V, WITH DIAGNOSTICS AND BACKUP | ||
Supply voltage | ||
Load voltage L+ | ||
Rated value (DC) | 24 to 56.7 V DC, 24 to 48 V / 120 V / 230 V AC | |
Short-circuit protection | Yes; IEC 127-2/1, internal with fuse (5x 20 mm), 250 V, 10 A, quick-response, replaceable | |
Reverse polarity protection | Yes | |
Input current | ||
from load voltage L+ (without load), max. | 9 mA | |
from backplane bus 24 V DC, max. | 9.5 mA | |
Output voltage | ||
Overvoltage protection | Yes | |
Current carrying capacity | ||
up to 30 °C, max. | 10 A; 10 A (24 to 56.7 V DC), 8 A (24 to 48 V AC / 120 V / 230 V) | |
up to 40 °C, max. | 9 A; 9 A (24 to 56.7 V DC); 7 A (24 to 48 V AC / 120 V / 130 V) | |
up to 60 °C, max. | 7 A; 7 A (24 to 56.7 V DC); 5 A (24 to 48 V AC / 120 V / 230 V) | |
Power loss | ||
Power loss, max. | 5 W | |
Interrupts/diagnostics/status information | ||
Diagnostics function | Yes | |
Diagnostic messages | ||
Diagnostic information readable | Yes | |
Fuse blown | Yes | |
missing load voltage | Yes | |
Diagnostics indication LED | ||
Rated load voltage PWR (green) | Yes | |
Fuse OK FSG (green) | Yes | |
Group error SF (red) | Yes | |
Parameter | ||
Remark | 3 byte | |
Diagnostics, fuse blown | Disable / enable | |
missing load voltage | Disable / enable | |
Load voltage | DC/AC | |
Potential separation | ||
primary/secondary | Yes; between rated load voltage and backplane bus, between power modules | |
Isolation | ||
Isolation tested with | 1500 V AC | |
Dimensions | ||
Width | 15 mm | |
Height | 81 mm | |
Depth | 52 mm | |
Weights | ||
Weight, approx. | 34 g | |
last modified: | 03/13/2019 |