| SIMATIC DP, POWER M. F-PM-E PPM PROFIsafe, for ET 200SP; 24 V DC safe shutdown of DQ and F-DQ up to PL D/SIL2 or PL E/SIL3 2 for safe dig. inputs 1 for safe dig. output PPM |
General information |
Product type designation | F-PM-E 24 V DC/8 A PPM ST |
usable BaseUnits | BU type C0 |
Color code for module-specific color identification plate | CC52 |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V12 |
STEP 7 configurable/integrated as of version | V5.5 SP3 / - |
PROFIBUS as of GSD version/GSD revision | V2.3 |
PROFINET as of GSD version/GSD revision | V2.31 |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption (rated value) | 75 mA; without load |
Current consumption, max. | 21 mA; From the backplane bus |
Output voltage |
Rated value (DC) | 24 V |
Encoder supply |
Number of outputs | 2 |
Short-circuit protection | Yes; Electronic (response threshold 0.7 A to 2.1 A) |
Output current |
up to 60 °C, max. | 0.3 A |
24 V encoder supply |
24 V | Yes; min. L+ (-1.5 V) |
Short-circuit protection | Yes |
Output current, max. | 600 mA; Total current of all encoders |
Power |
Power available from the backplane bus | 70 mW |
Power loss |
Power loss, typ. | 5 W |
Address area |
Address space per module |
Inputs | 7 byte |
Outputs | 5 byte |
Hardware configuration |
Automatic encoding | Yes |
Electronic coding element type F | Yes |
Digital inputs |
Number of digital inputs | 2 |
Source/sink input | Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input voltage |
Type of input voltage | DC |
Rated value (DC) | 24 V |
for signal "0" | -30 to +5V |
for signal "1" | +15 to +30V |
Input current |
for signal "1", typ. | 3.7 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | Yes |
— at "0" to "1", min. | 0.4 ms |
— at "0" to "1", max. | 20 ms |
— at "1" to "0", min. | 0.4 ms |
— at "1" to "0", max. | 20 ms |
for technological functions |
— parameterizable | No |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 500 m |
Digital outputs |
Number of digital outputs | 1 |
Short-circuit protection | Yes |
Response threshold, typ. | > 14.8 A |
Open-circuit detection | Yes |
Response threshold, typ. | 8 mA |
Overload protection | Yes |
Response threshold, typ. | 8.8 A |
Limitation of inductive shutdown voltage to | Max. -1.5 V |
Switching capacity of the outputs |
with resistive load, max. | 8 A |
on lamp load, max. | 100 W |
Load resistance range |
lower limit | 3 Ω |
upper limit | 2 000 Ω |
Output voltage |
for signal "1", min. | 24 V; L+ (-0.5 V) |
Output current |
for signal "1" rated value | 8 A |
for signal "0" residual current, max. | 1.5 mA; PP-switching: max. 1.5 mA; PM-switching: max. 1 mA |
Switching frequency |
with resistive load, max. | 10 Hz; Symmetrical |
with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
on lamp load, max. | 4 Hz; Symmetrical |
Total current of the outputs |
Current per channel, max. | 8 A; Note derating data in the manual |
Current per module, max. | 8 A; Note derating data in the manual |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 500 m |
Interrupts/diagnostics/status information |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual |
Substitute values connectable | No |
Alarms |
Diagnostic alarm | Yes |
Hardware interrupt | No |
Diagnostics indication LED |
RUN LED | Yes; Green LED |
ERROR LED | Yes; Red LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | Yes; Red LED |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | No |
Isolation |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
Performance level according to ISO 13849-1 | PLe |
SIL acc. to IEC 61508 | SIL 3 |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C |
vertical installation, min. | 0 °C |
vertical installation, max. | 50 °C |
Dimensions |
Width | 20 mm |
Height | 73 mm |
Depth | 55 mm |
Weights |
Weight, approx. | 70 g |
last modified: | 03/13/2019 |