| SIMATIC DP, Electronics module for ET 200SP, F-DQ 4X24 V DC/2A, 15 mm width, up to PL E (ISO 13849) up to SIL 3 (IEC 61508) |
General information |
Product type designation | F-DQ 4x24 V DC/2 A PM HF |
Product function |
I&M data | Yes; I&M0 to I&M3 |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | V12 |
STEP 7 configurable/integrated as of version | V5.5 SP3 / - |
PROFINET as of GSD version/GSD revision | V2.31 |
Supply voltage |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 20.4 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Input current |
Current consumption (rated value) | 75 mA; without load |
Current consumption, max. | 21 mA; From the backplane bus |
Output voltage |
Rated value (DC) | 24 V |
Power |
Power available from the backplane bus | 70 mW |
Power loss |
Power loss, typ. | 4 W |
Address area |
Address space per module |
Inputs | 5 byte |
Outputs | 5 byte |
Digital outputs |
Number of digital outputs | 4 |
Digital outputs, parameterizable | Yes |
Short-circuit protection | Yes |
Response threshold, typ. | > 3.3 A |
Open-circuit detection | Yes |
Response threshold, typ. | 8 mA |
Overload protection | Yes |
Response threshold, typ. | 2.9 A |
Limitation of inductive shutdown voltage to | Typ. -2x 47 V |
Switching capacity of the outputs |
with resistive load, max. | 2 A |
on lamp load, max. | 10 W |
Load resistance range |
lower limit | 12 Ω |
upper limit | 2 000 Ω |
Output voltage |
for signal "1", min. | 24 V; L+ (-0.5 V) |
Output current |
for signal "1" rated value | 2 A |
for signal "0" residual current, max. | 0.5 mA |
Switching frequency |
with resistive load, max. | 30 Hz; Symmetrical |
with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
on lamp load, max. | 10 Hz; Symmetrical |
Total current of the outputs |
Current per channel, max. | 2 A; Note derating data in the manual |
Current per module, max. | 6 A; Note derating data in the manual |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 500 m |
Interrupts/diagnostics/status information |
Diagnostics function | Yes, "Alarms/diagnostic messages" section in the manual |
Substitute values connectable | No |
Alarms |
Diagnostic alarm | Yes |
Diagnostics indication LED |
RUN LED | Yes; Green LED |
ERROR LED | Yes; Red LED |
Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
Channel status display | Yes; Green LED |
for channel diagnostics | Yes; Red LED |
for module diagnostics | Yes; green/red DIAG LED |
Potential separation |
Potential separation channels |
between the channels | No |
between the channels and backplane bus | Yes |
between the channels and the power supply of the electronics | No |
Isolation |
Isolation tested with | 707 V DC (type test) |
Standards, approvals, certificates |
Suitable for safety functions | Yes |
Highest safety class achievable in safety mode |
Performance level according to ISO 13849-1 | PLe |
SIL acc. to IEC 61508 | SIL 3 |
Probability of failure (for service life of 20 years and repair time of 100 hours) |
— Low demand mode: PFDavg in accordance with SIL3 | < 2.00E-05 |
— High demand/continuous mode: PFH in accordance with SIL3 | < 1.00E-09 1/h |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C |
vertical installation, min. | 0 °C |
vertical installation, max. | 50 °C |
Dimensions |
Width | 15 mm |
Height | 73 mm |
Depth | 58 mm |
Weights |
Weight, approx. | 57 g |
last modified: | 03/13/2019 |