6ES7135-4GB52-0AB0
ET200S, El-Mod., 2AO I, +/-20mA, 4-20mA

From SIEMENS

SIMATIC DP, Electronics module for ET 200S, 2 AO I High Speed 15 mm width, +/-20mA; 16 bit, 4..20 mA; 16 bit, Cycle time 0.1 ms with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.150 mA; With load
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.2.4 W
Address area
Address space per module
Address space per module, max.4 byte
Analog outputs
Number of analog outputs2
Current output, no-load voltage, max.18 V
Cycle time (all channels) max.250 µs
Output ranges, current
-20 mA to +20 mAYes
4 mA to 20 mAYes
Connection of actuators
for current output two-wire connectionYes
for current output four-wire connectionNo
Load impedance (in rated range of output)
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH; for TWA 100µs
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA15 V; Max. 15 V / 5 hours (higher voltages not permissible even briefly)
Current, max.30 mA; DC
Cable length
shielded, max.200 m; Max. 20 m for TWA 100 µs
Analog value generation for the outputs
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Settling time
for resistive load0.05 ms
for capacitive load0.05 ms; at a load of up to 500 ohms/100 nF and a max. cable length of 20 m
for inductive load0.05 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.03 %; with resistive load
Temperature error (relative to output range), (+/-)0.01 %/K
Crosstalk between the outputs, min.-60 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.03 %
Operational error limit in overall temperature range
Current, relative to output range, (+/-)0.2 %; Specified value applies to loads from 200 to 350 Ohm, deviating operational limits for loads up to 200 Ohm and from 350 to 500 Ohm with up to 0.4%
Basic error limit (operational limit at 25 °C)
Current, relative to output range, (+/-)0.1 %; Specified value applies for loads from 200 to 350 ohms, deviating basic error limits for loads up to 200 ohms and from 350 to 500 ohms with up to 0.3%
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Substitute values connectableYes
Diagnostic messages
Diagnostic information readableYes
Wire-breakYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 byte
Diagnostics wire breakDisable / enable
Output type/rangedeactivated / ±20 mA / 4 to 20 mA
Group diagnosticsDisable / enable
Response to CPU/master STOPOutput current and de-energized/substitute a value/keep last value
Potential separation
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019