| SIMATIC DP, Electronics module for ET 200S, 2 AO I High Speed 15 mm width, +/-20mA; 16 bit, 4..20 mA; 16 bit, Cycle time 0.1 ms with SF LED (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 150 mA; With load |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 2.4 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog outputs |
Number of analog outputs | 2 |
Current output, no-load voltage, max. | 18 V |
Cycle time (all channels) max. | 250 µs |
Output ranges, current |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Connection of actuators |
for current output two-wire connection | Yes |
for current output four-wire connection | No |
Load impedance (in rated range of output) |
with current outputs, max. | 500 Ω |
with current outputs, inductive load, max. | 1 mH; for TWA 100µs |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA | 15 V; Max. 15 V / 5 hours (higher voltages not permissible even briefly) |
Current, max. | 30 mA; DC |
Cable length |
shielded, max. | 200 m; Max. 20 m for TWA 100 µs |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Settling time |
for resistive load | 0.05 ms |
for capacitive load | 0.05 ms; at a load of up to 500 ohms/100 nF and a max. cable length of 20 m |
for inductive load | 0.05 ms |
Errors/accuracies |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.03 %; with resistive load |
Temperature error (relative to output range), (+/-) | 0.01 %/K |
Crosstalk between the outputs, min. | -60 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.03 % |
Operational error limit in overall temperature range |
Current, relative to output range, (+/-) | 0.2 %; Specified value applies to loads from 200 to 350 Ohm, deviating operational limits for loads up to 200 Ohm and from 350 to 500 Ohm with up to 0.4% |
Basic error limit (operational limit at 25 °C) |
Current, relative to output range, (+/-) | 0.1 %; Specified value applies for loads from 200 to 350 ohms, deviating basic error limits for loads up to 200 ohms and from 350 to 500 ohms with up to 0.3% |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire-break | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 byte |
Diagnostics wire break | Disable / enable |
Output type/range | deactivated / ±20 mA / 4 to 20 mA |
Group diagnostics | Disable / enable |
Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value |
Potential separation |
Potential separation analog outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/13/2019 |