| SIMATIC DP, Electronics module for ET 200S, 2 AO U High Speed, 15 mm width, +/-10 V, +/-5 V, 1.. 5V; 16 bit, Cycle time: 0.1ms with SF LED (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 130 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power loss |
Power loss, typ. | 2.2 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog outputs |
Number of analog outputs | 2 |
Voltage output, short-circuit protection | Yes |
Voltage output, short-circuit current, max. | 25 mA |
Cycle time (all channels) max. | 0.25 ms |
Output ranges, voltage |
1 V to 5 V | Yes |
-5 V to +5 V | Yes |
-10 V to +10 V | Yes |
Connection of actuators |
for voltage output two-wire connection | Yes; Without compensation of the line resistances |
for voltage output four-wire connection | Yes |
Load impedance (in rated range of output) |
with voltage outputs, min. | 1 kΩ |
with voltage outputs, capacitive load, max. | 1 µF; 0.1 µF for Twa=0.1 ms |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA | 15 V; Max. 15 V for max. 5 hours, 75 V for max. 1 s |
Current, max. | 30 mA; DC |
Cable length |
shielded, max. | 200 m; Max. 20 m for TWA 100 µs |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit; 1 to 5 V: 14 bit, ±10 V: 15 bit + sign, ±5 V: 14 bit + sign |
Settling time |
for resistive load | 0.05 ms |
for capacitive load | 0.05 ms |
for inductive load | 0.05 ms |
Errors/accuracies |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
Linearity error (relative to output range), (+/-) | 0.03 % |
Temperature error (relative to output range), (+/-) | 0.01 %/K |
Crosstalk between the outputs, min. | 60 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.03 % |
Operational error limit in overall temperature range |
Voltage, relative to output range, (+/-) | 0.2 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to output range, (+/-) | 0.01 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes; 0 to 65535 (range of values must be within the rated range) |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire-break | No |
Short-circuit | Yes |
Group error | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 7 byte |
Diagnostics short-circuit | Disable / enable |
Output type/range | deactivated / 1 to 5 V / ±10 V / ±5 V |
Group diagnostics | Disable / enable |
Response to CPU/master STOP | Output current and de-energized/substitute a value/keep last value |
Potential separation |
Potential separation analog outputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/08/2019 |