| *** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S |
General information |
Usable terminal block | TB8 |
Supply voltage |
Rated value (DC) | 24 V; Value at t < 0.5 s: 35 V |
permissible range, lower limit (DC) | 18.5 V |
permissible range, upper limit (DC) | 30.2 V |
Input current |
Current consumption, max. | 200 mA; Logic |
Power loss |
Power loss, typ. | 2.4 W |
Analog outputs |
Number of analog outputs | 4 |
Voltage output, short-circuit protection | Yes; Electronic; max. 1 output in parallel |
Voltage output, short-circuit current, max. | 25 mA |
Current output, no-load voltage, max. | 18 V |
Output ranges, voltage |
0 to 10 V | Yes |
-10 V to +10 V | Yes |
Output ranges, current |
0 to 20 mA | Yes |
4 mA to 20 mA | Yes |
Connection of actuators |
for voltage output two-wire connection | Yes |
for voltage output four-wire connection | Yes |
for current output two-wire connection | Yes |
Load impedance (in rated range of output) |
with voltage outputs, capacitive load, max. | 1 µF |
with current outputs, max. | 300 Ω |
with current outputs, inductive load, max. | 1 mH |
Cable length |
shielded, max. | 100 m |
Analog value generation for the outputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 11 bit; Two's complement |
Conversion time (per channel) | 1 ms |
Settling time |
for resistive load | 0.1 ms |
for capacitive load | 3.3 ms |
for inductive load | 0.5 ms |
Errors/accuracies |
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.05 % |
Linearity error (relative to output range), (+/-) | 0.05 % |
Temperature error (relative to output range), (+/-) | 0.02 %/K |
Crosstalk between the outputs, min. | 40 dB |
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Voltage, relative to output range, (+/-) | 0.05 % |
Current, relative to output range, (+/-) | 1 % |
Basic error limit (operational limit at 25 °C) |
Voltage, relative to output range, (+/-) | 0.2 % |
Current, relative to output range, (+/-) | 0.3 % |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 12 Mbit/s |
Protocols |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms |
Diagnostic alarm | Yes; Parameterizable |
Diagnostics indication LED |
RUN LED | Yes |
Bus fault BF (red) | Yes |
Potential separation |
between electronic block and PROFIBUS DP | Yes |
Potential separation analog outputs |
Potential separation analog outputs | No |
Degree and class of protection |
Degree of protection acc. to EN 60529 | IP20 |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C; 40°C for other mountings |
Air pressure acc. to IEC 60068-2-13 |
permissible range, lower limit | 795 hPa |
permissible range, upper limit | 1 080 hPa |
Relative humidity |
Operation, min. | 15 % |
Operation, max. | 95 %; RH class 2 in accordance with IEC 1131-2 |
Vibrations |
Operation, tested according to IEC 60068-2-6 | Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g) |
Shock testing |
tested according to IEC 60068-2-27 | Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms |
Connection method |
Design of electrical connection for the inputs and outputs | Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection |
Dimensions |
Width | 160 mm; EB and TB |
Height | 130 mm; EB and TB |
Depth | 60 mm; EB and TB |
Weights |
Weight, approx. | 550 g; EB and TB |
last modified: | 03/13/2019 |