6ES7134-4MB02-0AB0
ET200S, El-Mod., 2AI HF I, +/-20mA

From SIEMENS

SIMATIC DP, Electronics module 2 AI I High Feature for ET 200S, 15 mm width, Cycle time per module: 0.5 ms, +/-20mA; 15 bit+sign, 4.. 20mA; 15 bit, Operational limit +/-0.1% with SF LED (group fault)
Supply voltage
Load voltage L+
Rated value (DC)24 V
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.48 mA
from backplane bus 3.3 V DC, max.10 mA
Output voltage
Power supply to the transmitters
presentYes
short-circuit proofYes
Power loss
Power loss, typ.1.2 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels) max.0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression
Input ranges (rated values), currents
-20 mA to +20 mAYes
4 mA to 20 mAYes
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Conversion time (per channel)0.04 ms; Without noise suppression 17/20 ms per channel with error
Smoothing of measured values
parameterizableYes; In 4 stages: 1x, 4x, 16x, 32x cycle time
Step: NoneYes; 1x
Step: lowYes; 4x
Step: MediumYes; 16x
Step: HighYes; 32x
Encoder
Connection of signal encoders
for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max.750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.03 %
Temperature error (relative to input range), (+/-)0.003 %/K
Crosstalk between the inputs, min.-100 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)0.1 %; 0.2% without interference frequency suppression
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.05 %; 0.1% without interference frequency suppression
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.90 dB
Common mode interference (USS < 2.5 V) , min.100 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
Interrupts/diagnostics/status information
Alarms
Hardware interruptYes
Diagnostic messages
Wire-breakYes; Measuring range 4 to 20 mA only
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark12 bytes, 4 bytes in compatibility mode
Diagnostics wire breakDisable / enable
Measurement type/rangedeactivated / ±20 mA / 4 to 20 mA
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo; however, increased permissible potential difference between the inputs.
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.45 g
last modified:03/01/2019

External links