| SIMATIC DP, Electronics module ET 200S: 2AI High Speed I-4WIRE 4-20 mA; 16 bit, 15 mm width, for 4-wire transmitter, Cycle time of module: 0.1 ms, with SF LED (group fault) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V |
Short-circuit protection | Yes |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 80 mA; without load |
from backplane bus 3.3 V DC, max. | 10 mA |
Output voltage |
Power supply to the transmitters |
present | Yes |
short-circuit proof | Yes |
Encoder supply |
Number of outputs | 2 |
Type of output voltage | 24 V |
Short-circuit protection | Yes |
Output current |
Rated value | 80 mA; Per channel |
permissible range, lower limit | 0 mA |
permissible range, upper limit | 90 mA |
Power loss |
Power loss, typ. | 1.9 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog inputs |
Number of analog inputs | 2 |
permissible input current for current input (destruction limit), max. | 30 mA |
Cycle time (all channels) max. | 250 µs |
Input ranges (rated values), currents |
0 to 20 mA | Yes |
Input resistance (0 to 20 mA) | 106 Ω |
-20 mA to +20 mA | Yes |
4 mA to 20 mA | Yes |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 16 bit |
Smoothing of measured values |
parameterizable | Yes |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 16x cycle time |
Step: High | Yes; 32x cycle time |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | No |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.03 % |
Temperature error (relative to input range), (+/-) | 0.01 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.1 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 0.3 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.2 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | Yes |
Interrupts/diagnostics/status information |
Alarms |
Hardware interrupt | Yes |
Diagnostic messages |
Diagnostic information readable | Yes |
Wire-break | Yes; Measuring range 4 to 20 mA only |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Diagnostics wire break | At 4 to 20 mA |
Measurement type/range | 4 to 20 mA, 0 to 20 mA, ±20 mA |
Group diagnostics | Yes |
Overflow/underflow | Yes |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | Yes |
Permissible potential difference |
between MANA and M internally (UISO) | 75 V DC/60 V AC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 45 g |
last modified: | 03/13/2019 |