6ES7134-4GB60-0AB0
ET200S, EL-MOD., 2AI HS I-4DMU, 0-20MA

From SIEMENS

*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE 2AI HIGH SPEED I-4WIRE FOR ET 200S, 15 MM WIDE, 4 .. 20MA; 12 BIT, FOR 4-WIRE TRANSDUCER, CYCLE TIME OF THE MODULE: 1MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Input current
from load voltage L+ (without load), max.35 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.8 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input current for current input (destruction limit), max.35 mA
Cycle time (all channels) max.1 ms
Input ranges (rated values), currents
4 mA to 20 mAYes
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleActual value encryption
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)0.1 ms
Smoothing of measured values
parameterizableYes
Step: NoneYes
Step: lowYes
Step: MediumYes
Step: HighYes
Encoder
Connection of signal encoders
for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max.750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.01 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.1 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Interrupts/diagnostics/status information
Diagnostic messages
Wire-breakYes
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 byte
Diagnostics wire breakDisable / enable
Measurement type/rangedeactivated / 4 to 20 mA
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Permissible potential difference
between MANA and M internally (UISO)75 V DC/60 V AC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019

External links