| SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AI STAND. I-2DMU 15 MM WIDE, 4 .. 20MA; 13 BIT FOR 2-WIRE TRANSDUCER CYCLE TIME 65 MS/CHANNEL WITH LED SF (GROUP FAULT) |
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 80 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Output voltage |
Power supply to the transmitters |
present | Yes |
short-circuit proof | Yes; Destruction limit 35 mA per channel |
Power loss |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
Address space per module, max. | 4 byte |
Analog inputs |
Number of analog inputs | 2 |
permissible input current for current input (destruction limit), max. | 40 mA |
Cycle time (all channels) max. | Number of active channels per module x basic conversion time |
Input ranges (rated values), currents |
4 mA to 20 mA | Yes; on 50 ohms |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. | 13 bit; 4 to 20 mA: 13 bit |
Integration time, parameterizable | Yes |
Integration time (ms) | 16,7 / 20 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Conversion time (per channel) | 65 ms; 55 / 65 ms |
Smoothing of measured values |
parameterizable | Yes; In four stages by means of digital filtering |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 4x cycle time |
Step: Medium | Yes; 32x cycle time |
Step: High | Yes; 64x cycle time |
Encoder |
Connection of signal encoders |
for current measurement as 2-wire transducer | |
— Burden of 2-wire transmitter, max. | 750 Ω |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.01 % |
Temperature error (relative to input range), (+/-) | 0.005 %/K |
Crosstalk between the inputs, min. | -50 dB |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 0.6 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.4 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Diagnostic messages |
Wire-break | Yes |
Group error | Yes |
Overflow/underflow | Yes |
Diagnostics indication LED |
Group error SF (red) | Yes |
Parameter |
Remark | 4 byte |
Diagnostics wire break | Disable / enable (only in measuring range 4 to 20 mA) |
Measurement type/range | deactivated / 4 to 20 mA |
Group diagnostics | Disable / enable |
Overflow/underflow | Disable / enable |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | Yes |
Between the channels and load voltage L+ | No |
Isolation |
Isolation tested with | 500 V DC |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weights |
Weight, approx. | 40 g |
last modified: | 03/13/2019 |