6ES7134-4FB50-0AB0
ET200S, EL-MOD., 2AI HS U, +/-10V,

From SIEMENS

*** SPARE PART*** SIMATIC DP, ELECTRONIC MODULE 2 AI HIGH SPEED U FOR ET 200S, 15 MM WIDE, +/-10V; 11 BIT + SIGN, CYCLE TIME OF THE MODULE: 1MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Input current
from load voltage L+ (without load), max.35 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.8 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.35 V; 35 V continuous; 75 V for max. 1 ms
Cycle time (all channels) max.1 ms
Input ranges (rated values), voltages
-10 V to +10 VYes
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleActual value encryption
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.12 bit
Conversion time (per channel)0.1 ms
Smoothing of measured values
parameterizableYes
Step: NoneYes
Step: lowYes
Step: MediumYes
Step: HighYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.01 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.15 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)1 %; ±0.3% available soon
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Interrupts/diagnostics/status information
Diagnostic messages
Wire-breakNo
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 byte
Measurement type/rangedeactivated / ±10 V
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
Between the inputs and MANA (UCM)2 V AC PP
between MANA and M internally (UISO)75 V DC/60 V AC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019