6ES7134-4FB00-0AB0
SIMATIC DP, ELECTRONIC MODULE

From SIEMENS

SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AI STANDARD 15 MM WIDE +/-10 V; 13 BIT + SIGN +/-5 V; 12 BIT+ SIGN, 1..5V; 12BIT, CYCLE TIME 65 MS/CHANNEL WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.30 mA
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.6 W
Address area
Address space per module
Address space per module, max.4 byte
Analog inputs
Number of analog inputs2
permissible input voltage for voltage input (destruction limit), max.35 V; 35 V continuous; 75 V for max. 1 ms (mark to space ratio 1:20)
Cycle time (all channels) max.Number of active channels per module x basic conversion time
Input ranges (rated values), voltages
1 V to 5 VYes
-10 V to +10 VYes
-5 V to +5 VYes
Cable length
shielded, max.200 m
Analog value generation for the inputs
Measurement principleintegrating
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.14 bit; ±10 V: 13 bit + sign, ±5 V: 13 bit + sign; 1 to 5 V: 13 bit
Integration time, parameterizableYes
Integration time (ms)16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Conversion time (per channel)65 ms; 55 / 65 ms
Smoothing of measured values
parameterizableYes; In four stages by means of digital filtering
Step: NoneYes; 1x cycle time
Step: lowYes; 4x cycle time
Step: MediumYes; 32x cycle time
Step: HighYes; 64x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.01 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode interference (USS < 2.5 V) , min.90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostic messages
Wire-breakYes; Measuring range 1 to 5 V only
Group errorYes
Overflow/underflowYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark4 byte
Diagnostics wire breakDisable / enable (only in measuring range 1 to 5 V)
Measurement type/rangedeactivated / ±5 V / 1 to 5 V / ±10 V
Group diagnosticsDisable / enable
Overflow/underflowDisable / enable
Potential separation
Potential separation analog inputs
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Permissible potential difference
Between the inputs and MANA (UCM)2 V AC PP
between MANA and M internally (UISO)75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g
last modified:03/13/2019