6ES7133-1JH00-0XB0
ET200L, EL-BLOCK, 8DI/8DO, AC 120V

From SIEMENS

*** SPARE PART*** SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 8 DI/8 DO, 120V AC CAN BE PLUGGED INTO TB16L AC
General information
Vendor identification (VendorID)0027h
Usable terminal blockTB 16L AC
Supply voltage
Rated value (AC)120 V
Line frequency
permissible range, lower limit47 Hz
permissible range, upper limit63 Hz
Mains buffering
Mains/voltage failure stored energy time20 ms
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)4.5 V
permissible range, upper limit (DC)30 V
Load voltage L1
Rated value (AC)120 V
permissible range, lower limit (AC)6 V
permissible range, upper limit (AC)132 V
permissible frequency range, lower limit47 Hz
permissible frequency range, upper limit63 Hz
Input current
from supply voltage L1, max.160 mA
Power loss
Power loss, typ.15.1 W
Digital inputs
Number of digital inputs8
Input characteristic curve in accordance with IEC 61131, type 2Yes
Input voltage
Rated value (AC)120 V
for signal "0"0V AC to 20V AC
for signal "1"74V AC to 132V AC
Input current
for signal "0", max. (permissible quiescent current)4 mA; 0 to 4 mA
for signal "1", typ.9 mA; 9 to 27 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", min.2 ms
— at "0" to "1", max.14 ms
— at "1" to "0", min.6 ms
— at "1" to "0", max.25 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Number of digital outputs8
Controlling a digital inputYes
Size of motor starters according to NEMA, max.Size 5 to NEMA (up to 40 °C); size 4 to NEMA (up to 60 °C)
Switching capacity of the outputs
on lamp load, max.50 W
Output voltage
Rated value (AC)120 V
for signal "1", min.L+ (-1 V)
Output current
for signal "1" permissible range, min.10 mA
for signal "1" permissible range, max.2 A
for signal "0" residual current, max.0 mA
Output delay with resistive load
"0" to "1", max.10 ms
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.10 Hz
with inductive load, max.0.5 Hz
on lamp load, max.1 Hz
Total current of the outputs (per group)
horizontal installation
— up to 40 °C, max.2 000 mA
— up to 60 °C, max.1 000 mA
all other mounting positions
— up to 40 °C, max.1 000 mA
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Encoder
Connectable encoders
2-wire sensorYes
Interfaces
PROFIBUS DP
Transmission rate, max.6 000 kbit/s
SYNC capabilityYes
FREEZE capabilityYes
Direct data exchange (slave-to-slave communication)Yes
Protocols
Bus protocol/transmission protocolPROFIBUS DP
Interrupts/diagnostics/status information
AlarmsNo
Diagnostics functionYes
Diagnostics indication LED
Bus fault BF (red)Yes
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Monitoring 24 V voltage supply ON (green)Yes
Potential separation
between PROFIBUS DP and all other circuit componentsYes
Potential separation digital inputs
between the channelsYes
between the channels and PROFIBUS DPYes
Potential separation digital outputs
between the channelsYes
between the channels and PROFIBUS DPYes
Isolation
Isolation tested with1500 V AC
Degree and class of protection
IP degree of protectionIP20
Ambient conditions
Ambient temperature during operation
horizontal installation, min.0 °C
horizontal installation, max.60 °C
Air pressure acc. to IEC 60068-2-13
permissible range, lower limit795 hPa
permissible range, upper limit1 080 hPa
Relative humidity
Operation, min.5 %
Operation, max.95 %
Vibrations
Operation, tested according to IEC 60068-2-6Yes
Shock testing
tested according to IEC 60068-2-27Yes
Connection method
Design of electrical connection for the inputs and outputsScrew-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection
Dimensions
Width145 mm
Height61 mm
Depth85.5 mm
Weights
Weight, approx.322 g
last modified:03/13/2019