| *** SPARE PART*** SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 8 DI/8 DO, 120V AC CAN BE PLUGGED INTO TB16L AC |
General information |
Vendor identification (VendorID) | 0027h |
Usable terminal block | TB 16L AC |
Supply voltage |
Rated value (AC) | 120 V |
Line frequency |
permissible range, lower limit | 47 Hz |
permissible range, upper limit | 63 Hz |
Mains buffering |
Mains/voltage failure stored energy time | 20 ms |
Load voltage L+ |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 4.5 V |
permissible range, upper limit (DC) | 30 V |
Load voltage L1 |
Rated value (AC) | 120 V |
permissible range, lower limit (AC) | 6 V |
permissible range, upper limit (AC) | 132 V |
permissible frequency range, lower limit | 47 Hz |
permissible frequency range, upper limit | 63 Hz |
Input current |
from supply voltage L1, max. | 160 mA |
Power loss |
Power loss, typ. | 15.1 W |
Digital inputs |
Number of digital inputs | 8 |
Input characteristic curve in accordance with IEC 61131, type 2 | Yes |
Input voltage |
Rated value (AC) | 120 V |
for signal "0" | 0V AC to 20V AC |
for signal "1" | 74V AC to 132V AC |
Input current |
for signal "0", max. (permissible quiescent current) | 4 mA; 0 to 4 mA |
for signal "1", typ. | 9 mA; 9 to 27 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", min. | 2 ms |
— at "0" to "1", max. | 14 ms |
— at "1" to "0", min. | 6 ms |
— at "1" to "0", max. | 25 ms |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Digital outputs |
Number of digital outputs | 8 |
Controlling a digital input | Yes |
Size of motor starters according to NEMA, max. | Size 5 to NEMA (up to 40 °C); size 4 to NEMA (up to 60 °C) |
Switching capacity of the outputs |
on lamp load, max. | 50 W |
Output voltage |
Rated value (AC) | 120 V |
for signal "1", min. | L+ (-1 V) |
Output current |
for signal "1" permissible range, min. | 10 mA |
for signal "1" permissible range, max. | 2 A |
for signal "0" residual current, max. | 0 mA |
Output delay with resistive load |
"0" to "1", max. | 10 ms |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | Yes |
Switching frequency |
with resistive load, max. | 10 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 1 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. | 2 000 mA |
— up to 60 °C, max. | 1 000 mA |
all other mounting positions |
— up to 40 °C, max. | 1 000 mA |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
Interfaces |
PROFIBUS DP |
Transmission rate, max. | 6 000 kbit/s |
SYNC capability | Yes |
FREEZE capability | Yes |
Direct data exchange (slave-to-slave communication) | Yes |
Protocols |
Bus protocol/transmission protocol | PROFIBUS DP |
Interrupts/diagnostics/status information |
Alarms | No |
Diagnostics function | Yes |
Diagnostics indication LED |
Bus fault BF (red) | Yes |
Status indicator digital input (green) | Yes |
Status indicator digital output (green) | Yes |
Monitoring 24 V voltage supply ON (green) | Yes |
Potential separation |
between PROFIBUS DP and all other circuit components | Yes |
Potential separation digital inputs |
between the channels | Yes |
between the channels and PROFIBUS DP | Yes |
Potential separation digital outputs |
between the channels | Yes |
between the channels and PROFIBUS DP | Yes |
Isolation |
Isolation tested with | 1500 V AC |
Degree and class of protection |
IP degree of protection | IP20 |
Ambient conditions |
Ambient temperature during operation |
horizontal installation, min. | 0 °C |
horizontal installation, max. | 60 °C |
Air pressure acc. to IEC 60068-2-13 |
permissible range, lower limit | 795 hPa |
permissible range, upper limit | 1 080 hPa |
Relative humidity |
Operation, min. | 5 % |
Operation, max. | 95 % |
Vibrations |
Operation, tested according to IEC 60068-2-6 | Yes |
Shock testing |
tested according to IEC 60068-2-27 | Yes |
Connection method |
Design of electrical connection for the inputs and outputs | Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection |
Dimensions |
Width | 145 mm |
Height | 61 mm |
Depth | 85.5 mm |
Weights |
Weight, approx. | 322 g |