6ES7132-4BD00-0AA0
ET200S, EL-MOD., 4DO ST,DC24V, 0.5A,5PCS

From SIEMENS

SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO STANDARD DC 24V/0.5A, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT
Supply voltage
Reverse voltage protectionYes; when using the same load voltage as on the power module
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.5 mA; Per channel
from backplane bus 3.3 V DC, max.10 mA
Power loss
Power loss, typ.0.8 W
Address area
Address space per module
Address space per module, max.1 byte
with packing2 bit
Digital outputs
Number of digital outputs4
Short-circuit protection
Response threshold, typ.0.7 to 1.5 A
Limitation of inductive shutdown voltage to-55 to -60 V
Controlling a digital inputYes
Switching capacity of the outputs
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit3 400 Ω
Output voltage
for signal "1", min.L+ (-1 V)
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.3 mA
Output delay with resistive load
"0" to "1", max.100 µs
"1" to "0", max.300 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes; per module
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal)No
Interrupts/diagnostics/status information
Diagnostics functionNo
Diagnostics indication LED
Status indicator digital output (green)Yes
Parameter
Remark1 byte
Potential separation
Potential separation digital outputs
between the channelsNo
between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC
Isolation
Isolation tested with500 V DC
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weights
Weight, approx.40 g