| *** SPARE PART*** SIMATIC SC,ELECTRONIC SUBMODULE 2 AI, 4..20MA, +/-20MA |
General information |
Usable terminal block | TB 16SC |
Supply voltage |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Input current |
from supply voltage L+, max. | 30 mA |
Power loss |
Power loss, typ. | 0.6 W |
Hardware configuration |
Slots |
required slots | 1; from 8 |
Analog inputs |
Number of analog inputs | 2 |
permissible input current for current input (destruction limit), max. | 40 mA; Permanent |
Input ranges |
Current | Yes |
Input ranges (rated values), currents |
-20 mA to +20 mA | Yes |
Input resistance (-20 mA to +20 mA) | 50 Ω |
4 mA to 20 mA | Yes |
Input resistance (4 mA to 20 mA) | 50 Ω |
Thermocouple (TC) |
Temperature compensation |
— parameterizable | No |
Characteristic linearization |
parameterizable | No |
Cable length |
shielded, max. | 200 m |
Analog value generation for the inputs |
Measurement principle | integrating |
Integration and conversion time/resolution per channel |
Resolution (incl. overrange) | ±20 mA: 13 bit, 4 to 20 mA: 12 bit |
Resolution with overrange (bit including sign), max. | 13 bit |
Integration time, parameterizable | Yes |
Basic conversion time (ms) | 55 / 65 ms |
Integration time (ms) | 50 / 60 ms |
Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz |
Smoothing of measured values |
parameterizable | Yes; parameterizable in 4 stages by means of digital filtering |
Step: None | Yes; 1x cycle time |
Step: low | Yes; 8x cycle time |
Step: Medium | Yes; 64x cycle time |
Step: High | Yes; 128x cycle time |
Encoder |
Connection of signal encoders |
for voltage measurement as 2-wire transducer | Yes; 4-wire transformer with external transmitter feed |
for current measurement as 2-wire transducer | Yes; with external transmitter supply |
for current measurement as 4-wire transducer | Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) | 0.05 % |
Temperature error (relative to input range), (+/-) | 0.01 %/K |
Crosstalk between the inputs, min. | 50 dB; At 50/60 Hz |
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.1 % |
Operational error limit in overall temperature range |
Current, relative to input range, (+/-) | 1 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to input range, (+/-) | 0.8 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
Series mode interference (peak value of interference < rated value of input range), min. | 70 dB |
Common mode interference (USS < 2.5 V) , min. | 90 dB |
Interrupts/diagnostics/status information |
Alarms | No |
Diagnostics function | No |
Potential separation |
Potential separation analog inputs |
between the channels | No |
between the channels and backplane bus | No; Optocoupler |
between the channels and the power supply of the electronics | No |
Permissible potential difference |
Between the inputs and MANA (UCM) | 2 V DC / 2 Vpp AC |
Isolation |
Isolation tested with | 1500 V AC |
Dimensions |
Width | 10 mm |
Height | 64 mm |
Depth | 51 mm |
Weights |
Weight, approx. | 20 g |
last modified: | 03/13/2019 |