6EP4145-8GB00-0XY0
SITOP BAT8600 PB 380WH

From SIEMENS

SITOP BAT8600 PB 380WH
SITOP BAT8600 Pb battery module for UPS8600 DC 48 V/380 Wh energy storage: mainten.-free lead batteries
Output
Rated current value Iout rated20 A
Rated voltage Vout DC48 V
Safety
Short-circuit protectionBlade-type fuse 40 A, 58 V DC
Design of the overload protectionValve control
Safety
Protection classClass III
Degree of protection (EN 60529)IP20
Approvals
CE markYes
UL/cUL (CSA) approvalcURus-Recognized (UL 1778, CSA C22.2 No. 107.1), File E219627; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protectionIECEx Ex nA IIC T5 Gc; ATEX (EX) II 3G Ex nA IIC T5 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T5
Marine approvalDNV GL and ABS in process
environmental conditions
Operating data noteFor storage, mounting and operation of batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed.
Ambient temperature
during operation-10 ... +50 °C
during transport-40 ... +60 °C
during storage-15 ... +40 °C
Service life
Service life of energy storage
typical Notecapacity falls to 80 % of original capacity (according to EUROBAT)
at 20 °C typical4 y
at 30 °C typical2 y
at 40 °C typical1 y
at 50 °C typical0.5 y
Ambient temperature during storage NoteIn addition to the storage temperature, additional factors, such as storage duration and charging status during storage, have a major impact on the potential service life. This means batteries should preferably be stored fully charged for short periods of time in a dry, cool and frost-proof (temperature range 0 to +20 °C) location.
Mechanics
Connection technologyPlug-in terminals with screwed connection
Connection for power supply unit+, -: 2 plug-in terminals with 1 screwed connection each for 0.2 ... 10 mm²
Product component belonging to2x blade-type fuse 40 A, 58 V DC
Width of the enclosure322 mm
Height of the enclosure187 mm
Depth of the enclosure110 mm
Installation width322 mm
Installation height207 mm
Weight, approx.13 kg
InstallationKeyhole mounting for hooking in to M4 screws
Reference code acc. to DIN EN 81346-2G
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)