6EP3436-8MB00-2CY0
SITOP PSU8600 20A/4X5A PN

From SIEMENS

SITOP PSU8600 20A/4X5A PN
SITOP PSU8600 20 A/4x5 A PN Stabilized power supply input: 400-500 V 3 AC output: 24 V DC/20 A/4x 5 A with PN/IE connection Web server integrated OPC UA server integrated
Input
Input3-phase AC
Rated voltage value Vin rated400 ... 500 V
Voltage range AC320 ... 575 V
NoteDerating 320 … 360 and 530 … 575 V
Wide-range inputYes
Mains buffering at Iout rated, min.15 ms; at Vin = 400 V; Prioritized supply Output 1 at power failure can be selected via DIP switch
Rated line frequency 150 Hz
Rated line frequency 260 Hz
Rated line range47 ... 63 Hz
Input current
at rated input voltage 400 V1.4 A
at rated input voltage 500 V1.1 A
Switch-on current limiting (+25 °C), max.14 A
I²t, max.1.2 A²·s
Built-in incoming fusenone
Protection in the mains power input (IEC 898)Required: 3-pole connected miniature circuit breaker 6 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
Output
OutputControlled, isolated DC voltage
Number of outputs4
Rated voltage Vout DC24 V
Output voltage
at output 1 at DC Rated value24 V
at output 2 at DC Rated value24 V
at output 3 at DC Rated value24 V
at output 4 at DC Rated value24 V
Total tolerance, static ±3 %
Static mains compensation, approx.0.2 %
Static load balancing, approx.0.1 %
Residual ripple peak-peak, max.100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz)200 mV
Adjustment range4 ... 28 V
Product function Output voltage adjustableYes
Output voltage settingvia potentiometer; Derating > 24 V: 4%/V; max. 120 W per output, max. 480 W overall system
Status display3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED per output for operating state output; LED green for parallel operation Output 1 and 2 / 3 and 4
SignalingRelay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK"
On/off behaviorNo overshoot of Vout (soft start)
Startup delay, max.1 s; Without on-delay of the outputs
connection of outputs operatingSimultaneous connecting-in of all outputs after device booting or delay time of 25 ms, 100 ms or "load-optimized" for sequential cutting-in of the outputs via DIP switches can be set
Voltage increase time of the output voltage maximum500 ms
Rated current value Iout rated20 A
Output current
per output5 A
at output 1 Rated value5 A
at output 2 Rated value5 A
at output 3 Rated value5 A
at output 4 Rated value5 A
Current range0 ... 20 A
Note+50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 240 W
Supplied active power typical480 W
Product feature parallel switching of outputsYes; Parallel circuit Output 1 with 2 or Output 3 with 4 can be selected via DIP switch
Parallel switching for enhanced performanceNo
Efficiency
Efficiency at Vout rated, Iout rated, approx.93 %
Power loss at Vout rated, Iout rated, approx.34 W
Power loss [W] during no-load operation maximum12 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max.0.1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.0.4 %
Setting time maximum10 ms
Protection and monitoring
Output overvoltage protection< 35 V
Property of the output Short-circuit proofYes
Short-circuit protectionelectronic overload cut-off; optionally constant current operation can be selected for Output 4 via DIP switches
adjustable response value current of current-dependent overload trip0.5 ... 5 A
type of threshold value settingvia potentiometer
characteristics of electronic overload switch-offIa >1.0…<1.5 x Ia threshold permissible for 5 s; Ia limit (= 1.5 x Ia threshold) permissible for 200 ms
characteristics of constant current operationIa limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous
ResetVia sensor per output
Remote resetNon-electrically isolated 24 V input (signal level "high" at > 15 V)
Overcurrent overload capability in normal operationTotal system overloadable 150% Ia rated to 5 s/min
Overload/short-circuit indicator3-color LED for operating state device; 3-color LED per output for operating state output
Interface
Specification interfaceEthernet/PROFINET
Safety
Primary/secondary isolationYes
Galvanic isolationSafety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection classClass I
Leakage current
maximum3.5 mA
CE markYes
UL/cUL (CSA) approvalcULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protectionIECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4
FM approval-
CB approvalYes
Marine approvalABS, DNV GL
Degree of protection (EN 60529)IP20
EMC
Emitted interferenceEN 55022 Class B
Supply harmonics limitationEN 61000-3-2
Noise immunityEN 61000-6-2
Operating data
Ambient temperature
during operation-25 ... +60 °C
— Notewith natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
Humidity class according to EN 60721Climate class 3K3; in addition 95% maximum relative humidity, but without condensation
Mechanics
Connection technologyPlug-in terminals with screwed connection
Connections
Supply inputL1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.2 ... 4 mm² single-wire / fine stranded
Output1, 2, 3, 4: Two plug-in terminals (1, 2 and 3, 4) with 2 screwed connections each for 0.2 ... 2.5 mm²; 0 V: Plug-in terminal with 3 screwed connections for 0.2 ... 4 mm²
AuxiliaryRST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm²
Connections signaling contact11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm²
Product function
removable terminal at inputYes
removable terminal at outputYes
Design of the interface for communicationPROFINET/Ethernet: two RJ45 sockets (2-port switch)
Suitability for interaction modular systemYes
Width of the enclosure100 mm
Height of the enclosure125 mm
Depth of the enclosure150 mm
Required spacing
top50 mm
bottom50 mm
left0 mm
right0 mm
Weight, approx.2 kg
Product feature of the enclosure housing for side-by-side mountingYes
InstallationSnaps onto DIN rail EN 60715 35x15
Electrical accessoriesExpansion modules CNX8600, buffer modules BUF8600
Mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C243 178 h
Other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)

External links